SEC. 92.0302. PRIVATE RESIDENCE INCLINED ELEVATORS.
Los Angeles Rent Rules (LAMC excerpts) · 2025 edition · ingested 2026-07-08 · Los Angeles
(Amended by Ord. No. 185,587, Eff. 7/16/18.)
All inclined elevators in private residences shall comply with the provisions of ASME A 17.1 and this article. Part 5, Section 5.4 of ASME A 17.1- 2004 is adopted by reference, with the following exceptions and modifications: ASME Sections 5.3.1.7.7, 5.3.1.18.4, 5.3.1.18.5 and 5.4.8 are not adopted.
(a) Suspension Means. Suspension means shall comply with Part 5, Section 5.3.1.12 of ASME A 17.1-2004.
(b) Machine and Controls. Machine and controls shall be located as follows:
Machines, controls and disconcerting means shall not be mounted on cars, and shall be located outside of the hoistway in spaces dedicated to the elevator equipment.
The machine room shall have a head clearance of at least seven feet, and shall be provided with permanent electric lighting and a duplex receptacle rated at not less than 15A at 120V.
Required workspace clearance for elevator control and/or machinery spaces shall be located entirely within the interior of the building.
(c) Maintenance. The owner shall develop, implement, and maintain a written maintenance program for Private Residence Inclined Elevators in accordance with the manufacturer's recommendations. The maintenance shall be performed by a registered Journey-Level Elevator Mechanic as required by LAMC 92.0119. A log of all repairs and maintenance shall be kept at the location.