SEC. 91.6716. OPENINGS OTHER THAN DOORS OR GLAZED OPENINGS.
Los Angeles Building Code — LAMC Chapter IX · 2026-08 edition · updated 2026-09-09 · Los Angeles
(Added by Ord. No. 171,175, Eff. 7/25/96.)
91.6716.1. Security openings other than doors or glazed openings shall be protected in accordance with the requirements of this section.
91.6716.2. Hatchway covers of less than 1-3/4-inch thick solid wood construction shall be covered on the inside with 16–gauge sheet metal attached by screws around the perimeter spaced at six-inch maximum centers.
91.6716.3. Hatchway covers shall be secured from the inside with slide bars, slide bolts, and/or padlocks with hardened steel shackles. Hasps shall be hardened steel and bolted.
91.6716.4. Outside pin-type hinges shall be provided with non-removable pins.
91.6716.5. Openings within 40 inches of the required locking device of the door when said door is in the closed and locked position and when said door is openable without the use of a key shall not exceed two inches in their greatest dimension or shall be protected by metal bars or grilles having a pattern such that the openings of which do not exceed two inches in the greatest dimension.
91.6716.6. All other openings shall be protected by metal bars or grilles constructed to preclude human entry. Such bars or grilles shall have a pattern such that no less than one dimension of any opening shall be six inches or less.
EXCEPTION: Openings which are more than 40 inches from the required locking device of a door in the closed and locked position when the door is openable from the inside without the use of a key, and which do not exceed 96 square inches in area, with no less than one dimension thereof being six inches or less.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — Los Angeles Building Code — LAMC Chapter IX
- Chapter IX
- Chapter IX — BUILDING REGULATIONS
- Division 1
- Division 2
- Division 3
- Division 4
- Division 5
- Division 6
- Division 7
- Division 8
- Division 9
- Division 10
- Division 11
- Division 12
- Division 13
- Division 14
- Division 15
- Division 16
- Division 17
- Division 18
- Division 19
- Division 20
- Division 21
- Division 22
- Division 23
- Division 24
- Division 25
- Division 26
- Division 27
- Division 28
- Division 29
- Division 30
- Division 31
- Division 32
- Division 33
- Division 34
- Division 35
- Division 61
- Division 62
- Division 63
▸Division 67
Overview- SEC. 91.6701. PURPOSE.
- SEC. 91.6702. GENERAL.
- SEC. 91.6703. LIMITATIONS.
- SEC. 91.6704. ALTERNATE SECURITY PROVISIONS.
- SEC. 91.6705. DEFINITIONS.
- SEC. 91.6706. ENTRY VISION.
- SEC. 91.6707. APPURTENANT ACCESS.
- SEC. 91.6708. DOORS – GENERAL.
- SEC. 91.6709. SWINGING DOORS.
- SEC. 91.6710. SLIDING GLASS DOORS.
- SEC. 91.6711. OVERHEAD AND SLIDING DOORS.
- SEC. 91.6712. METAL ACCORDION-GRATE OR GRILLE-TYPE DOORS.
- SEC. 91.6713. GLAZED OPENING – GENERAL.
- SEC. 91.6714. GLAZING.
- SEC. 91.6715. WINDOWS.
- SEC. 91.6716. OPENINGS OTHER THAN DOORS OR GLAZED OPENINGS.
- SEC. 91.6717. TESTS – GENERAL.
- Division 70
- Division 71
- Division 72
- Division 82
- Division 83
- Division 85
- Division 88
- Division 89
- Division 90
- Division 91
- Division 92
- Division 93
- Division 94
- Division 95
- Division 96
- Division 5 — REGISTRATION
- Division 16A
- Division 17
- Division 18
- Division 19
- Division 20
- Division 21
- Division 17
- Division 18
- Division C
- Division D