Skip to content

Earlier editions: 2026-09

Title 15 — BUILDINGS AND CONSTRUCTION

Kingsburg Municipal Code Ch. 15.06 California Code of Regulations Title 24

Kingsburg Municipal Code · 2026-10 edition · updated 2026-10-04 · Kingsburg

Cite as: Kingsburg Municipal Code Chapter 15.06 · Text as of 2026-10-04

15.06.010 - California Code of Regulations Title 24 adopted.

A. The California Code of Regulations, Title 24, 2022 Edition, Parts 1, 2, 2.5, 3, 4, 5, 6, 8, 9, 10, 11, and 12, as approved by the California Building Standards Commission, are hereby adopted by reference as if set forth in full, except as amended herein. Copies are on file in the office of the building division.

B. California Building Code, 2022 Edition.

  1. The following appendix chapters to the California Building Code, 2022 Edition, are hereby adopted by reference as if set forth in full. Copies are on file in the office of the Building Division.

a. Appendix H Patio Signs.

b. Appendix I Patio Covers.

c. Appendix N Replicable Buildings.

d. Appendix P Emergency Housing.

  1. The following California Building Code, 2022 section is hereby amended as follows:

a. Section 101.1. Insert City of Kingsburg.

  1. CBC 903.2.7.3 is added:

a. 903.2.7.3 Pet boarding. An automatic sprinkler system shall be installed in fire areas containing pet boarding.

  1. CBC 903.2.21 is added:

a. 903.2.21 Pet boarding. An automatic sprinkler system shall be installed in fire areas containing pet boarding in Group B occupancies.

  1. CBC Table 906.1 is amended to read:

a. Table 906.1 Additional Required Portable Fire Extinguishers

Portions of table not shown remain unchanged.

Section Subject
4204.1 Pet Boarding
  1. CBC 907.2.2.3 is added:

a. 907.2.2.3 Pet boarding. Smoke Detection shall be installed pet boarding facilities in the locations specified in Section 4204.2 of the California Fire Code. Carbon Monoxide detection shall be installed in pet boarding facilities in the locations specified in Section 4204.3 of the California Fire Code.

  1. CBC 907.2.7.2 is added:

a. 907.2.7.2 Pet boarding. Smoke Detection shall be installed pet boarding facilities in the locations specified in Section 4204.2 of the California Fire Code. Carbon Monoxide detection shall be installed in pet boarding facilities in the locations specified in Section 4204.3 of the California Fire Code.

  1. CBC 1512.6 is Added:

a. 1512.6 Fall arrestor anchor point. Where a reroof of all or any portion of a building necessitates the removal and replacement of existing roof mounted equipment or appliance(s) requiring service, or an installed photovoltaic (PV) system, a permanent corrosion-resistant fall arrestor anchor point system with a minimum 5,000 pounds tensile strength shall be installed within 72 inches (1829 mm) of the centerline of the service side of the existing equipment or appliance and at the highest point of the ridge. The fall arrestor anchor point shall be installed in accordance with manufacturer's specifications.

Exceptions:

(1) The existing roof mounted equipment is serviced by a level platform installed in accordance with California Mechanical Code section 304.2.

(2) The highest finished elevation of the building of which the equipment, appliance, or PV services is less than 72 inches (1829 mm) above the highest level of finished grade.

  1. CBC 3111.3.7 is Added:

a. 3111.3.7 Fall arrestor anchor point. Where new photovoltaic (PV) systems are installed on roof assemblies at or exceeding 72 inches (1829 mm) above the highest finished grade level, a permanent corrosion-resistant fall arrestor anchor point system with a minimum 5,000 pounds tensile strength shall be installed at the highest point of the roof assembly. The fall arrestor anchor point shall be installed in accordance with manufacturer's specifications.

C. California Residential Code, 2022 Edition.

  1. The following appendix chapters to the California Residential Code, 2022 Edition, are hereby adopted by reference as if set forth in full. Copies are on file in the office of the Building Division.

a. Appendix AH Patio Covers.

b. Appendix AQ Tiny Houses.

c. Appendix AR Light Straw-Clay Construction.

d. Appendix AS Strawbale Construction.

e. Appendix AU Cob Construction.

f. Appendix AW 3D-Printed Building Construction

g. Appendix AX Swimming Pool Safety Act.

h. Appendix AZ Emergency Housing.

  1. The following California Residential Code, 2022 section is hereby amended as follows:

a. Section 101.1. Insert City of Kingsburg.

  1. CRC R324.9 is Added:

a. R324.9 Fall arrestor anchor point. Where new photovoltaic (PV) systems are installed on roof assemblies at or exceeding 72 inches (1829 mm) above the highest finished grade level, a permanent corrosion-resistant fall arrestor anchor point system with a minimum 5,000 pounds tensile strength shall be installed at the highest point of the roof assembly. The fall arrestor anchor point shall be installed in accordance with manufacturer's specifications.

  1. CRC R908.7 is Added

a. R908.7 Fall arrestor anchor point. Where a reroof of all or any portion of a building necessitates the removal and replacement of existing roof mounted equipment or appliance(s) requiring service, or an installed flush-mounted photovoltaic (PV) system, a permanent corrosion-resistant fall arrestor anchor point system with a minimum 5,000 pounds tensile strength shall be installed within 72 inches (1829 mm) of the centerline of the service side of the existing equipment or appliance and at the highest point of the ridge. The fall arrestor anchor point shall be installed in accordance with manufacturer's specifications.

Exceptions:

i. The existing roof mounted equipment is serviced by a level platform installed in accordance with California Mechanical Code section 304.2.

ii. The ridge of the building of which the equipment, appliance, or PV services is less than 72 inches (1829 mm) above highest level of finished grade.

D. California Plumbing Code, 2022 Edition.

  1. The following appendix chapters to the California Plumbing Code, 2022 Edition, are hereby adopted by reference as if set forth in full. Copies are on file in the office of the Building Division.

a. Appendix A Recommended Rules for Sizing the Water Supply System.

b. Appendix B Explanatory Notes on Combination Waste and Vent Systems.

c. Appendix I Installation Standard for PEX Tubing Systems for Hot- and Cold- Water Distribution.

d. Appendix J Combination of Indoor and Outdoor Combustion and Ventilation Opening Design.

E. California Mechanical Code, 2022 Edition.

  1. The following appendix chapters to the California Mechanical Code, 2022 edition, are hereby adopted by reference as if set forth in full. Copies are on file in the office of the Building Division.

a. Appendix B Procedures to be Followed to Place Gas Equipment in Operation.

  1. CMC 304.2 is amended to read:

a. 304.2 Sloped roof. Where equipment or appliances that require service are installed on a roof having a slope greater than or equal to 4 units vertical in 12 units horizontal (33 percent slope) or more, a level platform of not less than 30 inches by 30 inches (762 mm by 762 mm) shall be provided at the service side of the equipment or appliance. Where equipment or appliances that require service are installed on a roof having a slope greater than or equal to 2 units vertical in 12 units horizontal (17 percent slope) to 4 units vertical in 12 units horizontal (33 percent slope), a level platform of not less than 30 inches by 30 inches (762 mm by 762 mm) shall be provided at the service side of the equipment or appliance, or a permanent corrosion-resistant fall arrestor anchor point system minimum 5,000 pounds tensile strength shall be installed within 72 inches (1829 mm) of the centerline of the service side of the equipment or appliance. The fall arrestor anchor point shall be installed in accordance with manufacturer's specifications.

F. California Fire Code, 2022 Edition.

  1. The following appendix chapters to the California Fire Code, 2022 Edition, are hereby adopted by reference as if set forth in full. Copies are on file in the office of the Building Division.

a. Appendix 4 Special Detailed Requirements Based on Use and Occupancy.

b. Appendix A Board of Appeals.

c. Appendix B Fire-Flow Requirements for Buildings.

d. Appendix C Fire Hydrant Locations and Distribution.

e. Appendix D Fire Apparatus Access Roads.

f. Appendix E Hazard Categories.

g. Appendix F Hazard Ranking.

h. Appendix H Hazardous Materials Management Plan and Hazardous Materials Inventory Statements.

i. Appendix I Fire Protection Systems Noncompliant Conditions.

j. Appendix J Building Information Sign.

k. Appendix K Construction Requirements for Existing Ambulatory Care Facilities.

l. Appendix L Requirements for Fire Fighter Air Replenishment Systems.

m. Appendix N Indoor Trade Shows and Exhibitions

n. Appendix O Temporary Haunted Houses, Ghost Walks and Similar Amusement Uses.

  1. The following California Fire Code, 2022 section is hereby amended as follows:

a. Section 101.1 Insert City of Kingsburg

  1. CFC Section 112.5 is Added:

a. 112.5 Cost Recovery. The fire code official may seek cost recovery as outlined in this section for the cost of providing service from the Kingsburg Fire Department and any other public agencies deemed necessary to mitigate a hazard. The fire code official may seek cost recovery for hazardous materials response, fire suppression, and protection of the public from fire and life safety hazards.

The recovery of such cost is authorized in the following statutes:

Health and Safety Code Sections 13007-13009.1

Government Code Section 53150

i. Any person who causes or allows the existence of a hazard, as defined by this Code, shall be liable for all costs associated with mitigation as determined to have been caused by such hazard, or is a major contributor of said hazard, and such expense shall be a charge against the person. Cost Recovery shall be in accordance with the Kingsburg Municipal Code and City policy.

ii. Any person who is under the influence of an alcoholic beverage or any drug, whose negligent actions caused by that influence proximately causes any incident resulting in an appropriate emergency response, and any person whose intentionally wrongful conduct proximately causes any incident resulting in an appropriate emergency response, is liable for the expense of an emergency response by a public agency to the incident. Cost Recovery shall be in accordance with the Kingsburg Municipal Code and City policy.

iii. Any person that is involved in an action that requires the police department to utilize the fire department in response to illegal activities is liable for the expense by the fire department response to the incident. Recovery shall be in accordance with the Kingsburg Municipal Code and City policy.

iv. Utility company's equipment or distribution network which causes an emergency response from a public agency for an incident is liable for the expense of an emergency response by a public agency to the incident. Cost Recovery shall be in accordance with the Kingsburg Municipal Code and City policy.

v. Any person who causes a fire, sets a fire, allows a fire to be set, or allows a fire kindled or attended by him or her to escape onto any public or private property is liable for the expense of an emergency response by a public agency to the incident. Cost Recovery shall be in accordance with the Kingsburg Municipal Code and City policy.

vi. Any person who releases a hazardous material, allows a hazardous material to be released, causes, or allows a hazardous material attended by him or her to escape onto any public or private property, is liable for the expense of an emergency response by a public agency to the incident. Cost Recovery shall be in accordance with the Kingsburg Municipal Code and City policy.

vii. After responding to three (3) false alarms at the same facility in any consecutive twelve (12) month period, the Fire Code Official is authorized to charge the property owner for the cost of response. The cost of response will be billed at a minimum rate of one-half hour for all responding apparatus and personnel, or actual time spent on the alarm event, whichever is greater.

  1. Section 903.2 of the CBC and Section 903.2 of the CFC are amended to read:

a. 903.2 Where required. Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in this section and in Sections 903.2.1 through 903.2.21. Notwithstanding any other provisions of Sections 903.2.1 through 903.2.21, an approved fire sprinkler system shall be provided throughout all newly constructed buildings of any occupancy group when the gross floor area is equal to or exceeds 5,000 square feet (465 m 2 ), regardless of the presence of fire barrier and fire partition walls.

Exceptions:

i. Detached Group U occupancies accessory to a Group R-3, one- or two-family dwelling.

ii. In existing buildings, other than Group R-3 and Group U occupancies accessory to Group R-3 occupancies, not equipped with an automatic fire sprinkler system, the following shall apply:

(A) When an addition causes the building to exceed 5,000 square feet (465 m 2 ) in gross floor area and such addition is equal to or greater than 50% of the existing square footage, the entire building shall be provided with an automatic sprinkler system. The 50% threshold for the installation of fire sprinklers shall be cumulative over the life of the building.

(B) For existing buildings larger than 5,000 square feet (465 m 2 ) in gross floor area, when a change of use occurs that, in the opinion of the Building Official, increases the risk of fire, or increases the danger to occupants in a fire, the entire building shall be provided with an automatic sprinkler system.

(C) Spaces or areas in telecommunications buildings used exclusively for telecommunications equipment, associated electrical power distribution equipment, batteries and standby engines, provided that those spaces or areas are equipped throughout with an automatic smoke detection system in accordance with Section 907.2 and are separated from the remainder of the building by not less than 1-hour fire barriers constructed in accordance with Section 707 or not less than 2-hour horizontal assemblies constructed in accordance with Section 711, or both.

  1. CFC Section 503.2.1 is amended to read:

a. 503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of 20 feet (6096 mm) measured from the base of curb to base of curb, exclusive of shoulders, and an unobstructed vertical clearance of not less than 13 feet 6 inches (4115 mm).

  1. CBC 502.1 and CFC 505.1 are amended to read:

a. CBC 502.1 Address identification and CFC 505.1 Address identification.

New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. Where required by the fire code official, address numbers shall be provided in additional approved locations to facilitate emergency response. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be a minimum of 4 inches high with a minimum stroke width of 0.5 inch for single family homes, a minimum of 5 inches high with a minimum stroke width of 0.5 inch for multi-family residential buildings, and a minimum of 12 inches high with a minimum stroke width of 1.5 inch for commercial buildings. Where access is by means of a private road and the building cannot be viewed from the public way, a monument, pole or other sign or means shall be used to identify the structure. Address numbers shall be maintained.

  1. CFC 105.5.41 is added:

a. 105.5.41 Pet boarding. An operational permit is required for pet boarding.

  1. CFC Chapter 42 is added:

CHAPTER 42 PET BOARDING

SECTION 4201

GENERAL

a. 4201.1 Scope. Occupancies containing pet boarding shall comply with this chapter.

b. 4201.2 Permit. A permit shall be required for pet boarding as set forth in Section 105.5.

SECTION 4202

DEFINITIONS

a. 4202.1 Definitions. The following terms are defined in Chapter 2: PET BOARDING.

b. Add new definition in CFC Chapter 2 as follows:

PET BOARDING. Use of a Group B or Group M Occupancy to house a cumulative total of 10 or more dogs or cats for more than 12 hours per day that are available for sale or housed inside of a building as a service to the dog or cat owner.

SECTION 4203

FIRE SAFETY PRECAUTIONS

a. 4203.1 Fire safety plan. An approved fire safety and evacuation plan in accordance with Section 404 shall be prepared and maintained for pet boarding.

b. 4203.1.1 Fire safety plan additions. In addition to the requirements of Section 404.2.2, fire safety plans for pet boarding shall include all of the following:

i. Sequence of procedures to be followed in the event of a fire.

ii. Procedures for evacuating pets, including the location of any special keys or tools required to evacuate pets.

iii. Items to be inspected when conducting daily safety inspections.

iv. Procedures for training employees to know the locations of portable fire extinguishers and how to properly use them.

v. Procedures for maintaining proper clearances between combustibles and ignition sources in a pet boarding area in accordance with Section 305.

vi. Procedures to ensure that there are no open flames in a pet boarding area.

vii. Procedures to ensure that cooking and heating in a pet boarding area are conducted in accordance with Chapter 41.

viii. Procedures to ensure that use of current taps, relocatable power taps and extension cords in a pet boarding area is done in a safe manner and complies with Sections 603.5 and 603.6.

ix. Procedures for ensuring that trash and other combustible waste are removed from pet boarding areas not less than once per day.

x. Procedures for ensuring that clothes dryer vents are kept clear of lint accumulation in accordance with Section 610.1.2.

xi. Procedures for maintaining a staffing plan that specifies hours of operation, minimum staffing, staff names, and staff contact information.

c. 4203.1.2 Posting of fire safety plan. The sequence of procedures to be followed in the event of a fire shall be prominently posted next to each egress door or opening leading out of the pet boarding area.

d. 4203.2 Removal of combustible waste. Trash and other combustible waste shall be removed from pet boarding areas not less than once per day.

e. 4203.3 Staffing. Staffing for pet boarding shall comply with Sections 4203.3.1 and 4203.3.2.

f. 4203.3.1 Staffing plan. A staffing plan shall be prepared and maintained that includes current hours of operation, minimum staffing, staff names, and staff contact information.

g. 4203.3.2 Minimum staffing. At least one staff member shall be responsible for boarded pets, remaining in or immediately adjacent to pet boarding areas and awake at all times when a cumulative total of 10 or more dogs and cats are present, including overnight, for pet boarding in a fire area that is not equipped with an automatic sprinkler system in accordance with Section 4204.4

h. 4203.4 Safety inspections. Safety inspections specified in the approved fire safety plan shall be conducted at least once per day. A record of such safety inspection shall be maintained on the premises to document the date and time of each inspection and shall include the name of the individual who conducted the inspection.

i. 4203.5 Sources of ignition. Sources of ignition in pet boarding areas shall comply with Sections 4203.5.1 through 4203.5.3.

j. 4203.5.1 Cooking and heating. Cooking and heating in pet boarding areas shall comply with Chapter 41. Heating pads used for warming animals shall be listed and labeled by a nationally recognized testing laboratory.

k. 4203.5.2 Open flames. Open flames shall be prohibited in pet boarding areas.

l. 4203.5.3 Smoking. Smoking shall be prohibited in occupancies containing a pet boarding area. "No Smoking" signs shall be provided in accordance with Section 310.

SECTION 4204

FIRE PROTECTION AND LIFE SAFETY SYSTEMS

a. 4204.1 Portable fire extinguishers. Portable fire extinguishers rated 2-A:10-B:C and mounted in accordance with Section 906.9 shall be placed adjacent to each egress door or opening leading out of a pet boarding area, with additional extinguishers provided as necessary so that the travel distance to an extinguisher from anywhere in a fire area containing a pet boarding area does not exceed 50 feet (15240 mm).

b. 4204.2 Smoke detection system. An automatic smoke detection system that activates occupant notification in accordance with Section 907.5 and is monitored in accordance with Section 907.6.6 shall be installed in new and existing fire areas containing pet boarding. In locations where ambient conditions are incompatible with smoke detectors, heat detectors with a response time index of 50 (m×s) shall be permitted.

Exception: An automatic smoke detection system is not required in fire areas equipped with an automatic sprinkler system complying with Section 4204.4.

c. 4204.3 Carbon monoxide detection. In addition to the requirements in Section 915, carbon monoxide detection shall be provided in new and existing pet boarding areas where a carbon monoxide source is present.

d. 4204.4 Automatic sprinkler system. An automatic sprinkler system with quick-response sprinklers complying with Section 903.3.1 or a limited area automatic sprinkler system complying with Section 903.3.8 with quick-response sprinklers shall be installed in fire areas containing pet boarding.

  1. CFC 903.2.7.3 is added:

a. 903.2.7.3 Pet boarding. An automatic sprinkler system shall be installed in fire areas containing pet boarding.

  1. CFC 903.2.22 is added:

a. 903.2.21 Pet boarding. An automatic sprinkler system shall be installed in fire areas containing pet boarding in Group B occupancies.

  1. CFC Table 906.1 is amended to read:

a. TABLE 906.1 ADDITIONAL REQUIRED PORTABLE FIRE EXTINGUISHERS

Portions of table not shown remain unchanged.

Section Subject
4204.1 Pet Boarding
  1. CFC 907.2.2.3 is added:

a. 907.2.2.3 Pet boarding. A manual fire alarm system shall be installed in fire areas containing pet boarding.

  1. CFC 907.2.7.2 is added:

a. 907.2.7.2 Pet boarding. A manual fire alarm system shall be installed in fire areas containing pet boarding.

  1. CFC 907.2.2.3 is added:

a. 907.2.2.3 Pet boarding. Smoke Detection shall be installed pet boarding facilities in the locations specified in Section 4204.2. Carbon Monoxide detection shall be installed in pet boarding facilities in the locations specified in Section 4204.3.

  1. CFC 907.2.7.2 is added:

a. 907.2.7.2 Pet boarding. Smoke Detection shall be installed pet boarding facilities in the locations specified in Section 4204.2. Carbon Monoxide detection shall be installed in pet boarding facilities in the locations specified in Section 4204.3.

  1. CFC 1103.8.6 is added:

a. 1103.8.6 Smoke detection in existing Group B and Group M pet boarding facilities. Smoke detection shall be installed in the locations specified in Section 4204.2.

  1. CFC 1103.9.2 is added:

a. 1103.9.2 Carbon monoxide detection in existing Group B and Group M pet boarding facilities. Carbon monoxide detection shall be installed in the locations specified in Section 4204.3.

G. California Existing Building Code, 2022 Edition.

  1. The following California Existing Building Code, 2022 section is hereby amended as follows:

a. Section 101.1 Insert City of Kingsburg

  1. CEBC Chapter 1403 is added:

SECTION 1403

RELOCATION

a. 1403.1.1 Relocation permit required.

Any person, firm or corporation, desiring to move any building in the city shall first obtain a relocation permit issued by the chief building official. The moving of any building shall include all buildings moved from one site to another within the city, from outside the city into the city, from a storage lot to another location within the city but shall not include buildings moved from the city to a site outside the city or to storage lots. No permit for the moving of any building or structure shall be issued until the chief building official has first issued to the owner of the premises to which the building is to be moved a permit to relocate the particular building upon those premises.

b. 1403.2.2 Application for relocation permit.

Every application for a relocation permit shall be in writing and shall include or be accompanied by the following information:

i. The existing location of the building;

ii. The proposed location and intended use or occupancy of the building;

iii. A plot plan, and building plan, if required by the chief building official, of the building as it is proposed to be located upon the new site;

iv. A plan and/or a statement of the remodeling, repairs and reconstruction proposed for the building;

v. A statement of a licensed structural pest control contractor stating the condition of the building as to the decay and pest infestation;

vi. A photograph of the building, if required by the chief building official; and

vii. Such other information as the chief building official may require.

c. 1403.3 Inspection and processing fees.

An application fee shall be paid to the city before any application for a relocation permit is accepted. The fee shall be as established by the city council. The fee shall be in addition to all other fees required by the California Building Code or other ordinances of the city and shall not be refunded regardless of whether or not the relocation is approved.

d. 1403.4 Posting.

When a relocation permit application is filed and the relocation permit fee paid to the city, a public notice shall be given of the proposed building relocation by posting in front of the property under consideration and adjacent thereto as hereinafter defined, notice of intention to move, printed in plain type with letters of not less than one inch in height and followed by a statement in six or eight point type. The notice shall: set forth the fact that a relocation permit has been applied for a building to be moved to the subject property; state the present location of the building to be moved thereto; and indicate the closing date by which protests must be filed with the chief building official in writing by adjacent property owners, if they desire to protest the relocation and have the planning commission hold a hearing thereon. The moving notice shall also be posted on the front of the building or structure to be moved, and notices shall be posted not more than one hundred (100) feet apart upon the street which said property fronts for a distance of not less than three hundred (300) feet in each direction from said property. The time of posting shall be seven continuous days, within which period protests may be filed.

e. 1403.5 Protest procedure.

i. Protests against the moving of said building or structure shall be signed by two or more individual property owners on the surrounding area and filed with the chief building official within the dates prescribed by this chapter and indicated on the notice of intention to move.

ii. Upon filing of a protest, the planning commission shall conduct a hearing within thirty (30) days upon receipt herein at which time the applicants for relocation and the protestants against such regulation shall be heard. The planning commission shall approve or deny such relocation and if approved, shall establish conditions as hereinafter enumerated. The chief building official shall thereafter issue or deny a relocation permit in accordance with the conditions set forth by the planning commission.

f. 1403.6 Alternate procedure.

i. If no written protests are filed, the chief building official is authorized to approve or deny the relocation permit upon the conditions enumerated in this article, and/or to establish such conditions for the relocation permit, in accordance with the intent of this article, as are necessary to assure compliance herewith.

ii. If the applicant for the relocation permit feels that denial of a permit or conditions imposed thereon by the chief building official are not in accordance with the intent of this article, he/she may appeal the chief building official's decision to the planning commission who will consider the matter at a public hearing, notice of which is given by posting as provided in Section E101.4.

g. 1403.7 Faithful performance bond.

A faithful performance bond shall be filed in the office of the chief building official before any relocation permit shall be issued. The bond shall be in an amount at least ten percent more than the chief building official's estimated cost of the work required under terms and conditions imposed upon the relocation permit. Said bond shall guarantee that the required work shall be completed within ninety (90) days of the date on which said building is moved to its new location; provided, however, that such time may be extended by the chief building official upon written application showing good cause therefore. In lieu of said faithful performance bond, a cash deposit in the required amount may be made with the chief building official.

h. 1403.8 Safety factors.

i. No permit shall be issued to relocate a building or structure, if the building or structure has any of the following deficiencies or characteristics:

(A) Constructed or in such a condition to be dangerous and unsanitary;

(B) Unfit for human habitation;

(C) Dilapidated, defective, unsightly, or in such condition of deterioration or disrepair that its relocation at the proposed site would cause appreciable harm to or be materially detrimental to the property or improvements in the district within a radius of one thousand (1,000) feet from the proposed site;

(D) Prohibited in the zone in which it is to be relocated; or

(E) Prohibited at the proposed location by any fire district ordinance, or any other law or ordinance.

ii. If, in the judgment of the chief building official or planning commission, the structure admits the practical and effective repair, a relocation permit may be issued upon such conditions as the chief building official and planning commission may deem reasonable and proper. The conditions required prior to issuance of a relocation permit may include changes, alterations, additions or repairs to be made to the building or structure so that the relocation will not be materially detrimental or injurious to public health, safety or welfare, or to the surrounding property and improvements in the district to which it is to be moved.

iii. The conditions upon which each permit is granted shall be written upon the permit or appended in writing thereto.

i. 1403.9 Utilities.

i. Each person making application for a moving permit must make separate arrangements with public utilities for necessary utility relocations and for payment of all costs associated herewith. The city assumes no liability for route approval with respect to utility relocation.

ii. Signatures shall be required from all applicable utility providers acknowledging that all services have been disconnected from the structure to be moved.

j. 1403.10 Denial of permit.

A relocation permit shall be denied, if the unlawful, dangerous or defective condition of the building or structure proposed to be relocated is such that remedy or correction cannot practicably and effectively be made, or it is found that the structure will be materially detrimental to surrounding property.

  1. CEBC Chapter 1404 is added:

SECTION 1404

MOVING OF STRUCTURES UPON CITY STREETS

a. 1404.1 Lawful compliance.

It is unlawful for any person, firm or corporation to move any building, structure or portion of any building or structure on any street in the city without first filing a written application for a moving permit and securing a permit therefore from the city engineer in the manner provided by this article. The permit must be in the possession of the movers during the move and must be shown if requested by a police officer along the route.

b. 1404.2 Deposit and fees.

i. Each moving permit application shall be accompanied by a deposit. The amount of the deposit shall be based upon the size of the project and the amount of cleanup involved.

ii. A basic fee shall be charged for each permit for any structure to be moved.

iii. In addition to the basic fee, the city engineer shall determine when the interests of the city require that moving of the structure requires inspection by the city and assess a fee for each hour for such inspection.

iv. The chief of police of the city shall determine when public interest, in terms of traffic hazard abatement, require convoy by police of the structure being moved. The charge for such a convoy shall be based on the hourly rate for the personnel and equipment used.

v. The schedule of fees shall be those amounts established by resolution of the council adopted prior to the effective date of the ordinance codified in this chapter and shall remain in effect until otherwise changed by the council. Effective July 1, 2025, and each succeeding July 1 st thereafter, said schedule of fees shall be adjusted in accordance with the formula used by the city council to establish the expenditure control budget. If, in the determination of the city engineer, the adjustment of the schedule of fees produced by the above procedure is not representative of the actual change in costs of issuing the building relocation permit, the city engineer may, in lieu of the procedures set forth in this section, compute a new schedule of fees for adoption by resolution of the council. In the event of the adoption of a new schedule of fees by resolution of the council, such new schedule of fees shall become effective on adoption thereof by the council. The adjustment of such new schedule of fees shall begin the July 1 st next occurring after adoption of the new schedule.

vi. The foregoing fees, including the basic fee, shall be deducted from the deposit, and the balance remaining, if any, after completion of the moving of the structure to the new site, shall be returned to the permittee. If the total of such fees is greater than the deposit, the permittee shall pay all such fees.

vii. No deposit shall be returned until all debris and litter has been removed and all utilities and sewers disconnected and/or capped to the satisfaction of the city engineer and chief building official. If such removal, disconnection and/or capping is not performed to his/her satisfaction within fifteen (15) days, he/she shall proceed without notice to remove, disconnect or cap as required, deducting the cost of same from the deposit.

c. 1404.3 Moving permit application.

At least three days prior to the date of the actual move a completed application form shall be submitted to the city engineer on an approved application form. The following information shall be included on the application:

i. The kind of structure to be moved;

ii. The street location or other identifying description of the site to which the structure is to be moved;

iii. The route over, along, across, and upon which such structure is to be moved;

iv. The time it is proposed to move the structure and within which removal will be completed;

v. Signatures from the following utility companies acknowledging that they have seen and approved the proposed route over which the structure is to be moved;

(A) Southern California Edison,

(B) Pacific Bell,

(C) Continental Cablevision;

vi. The loaded height;

vii. The loaded length;

viii. The loaded weight;

ix. The type and number of wheels of the truck or dolly;

x. Other information as required by the city engineer to review the application.

d. 1404.4 Faithful performance bond.

i. Each application for a moving permit shall be accompanied by a faithful performance bond, in an amount specified by the city engineer not to exceed the sum of one thousand dollars ($1,000.00), guaranteeing completion of the moving work within the time specified in the moving permit. Said bond shall guarantee completion of the moving and the repair or costs of repair for damage to curbs, gutters, sidewalks, driveways, pavements, signs, trees, poles, signals and other facilities belonging to the city.

ii. Faithful performance bond for moving shall not be required for residential garages. When both a relocation and moving faithful performance bond are required, they may be combined as one bond. A continuing faithful performance bond in the minimum amount of one thousand dollars ($1,000.00) for moving only may be maintained on file with the city engineer by persons engaged in the business of house moving.

e. 1404.5 Certificate of insurance.

i. Every person, firm, company, corporation, or organization applying for a permit shall file with the engineering department a policy, true copy thereof, or certificate of insurance, accompanied by an endorsement signed by the underwriter or an authorized representative, as evidence that the applicant has obtained and maintains the following insurance requirements:

(A) Comprehensive general liability coverage with limits of not less than one million dollars ($1,000,000.00) combined single limit per occurrence for bodily injury, personal injury, and property damage;

(B) Automobile liability coverage with limits of not less than one million dollars ($1,000,000.00) combined single limit for occurrence for bodily injury, personal injury and property damage;

(C) Worker's compensation coverage with limits as required by the Labor Code of the state of California and employers liability coverage with limits of not less than one million dollars ($1,000,000.00) per accident.

ii. The city, its officers, agents and employees are to be named as additional insured with respect to the contractor's general liability. The contractor's insurance shall be considered primary with respect to any insurance or self-insurance programs maintained by the city. The contractor shall also agree to hold the city, its officers, agents and employees harmless from any and all causes of action, penalties, liabilities or loss resulting from claims or court actions arising out of any accidents, loss or damage to persons or property occurring as a result of any work performed by the contractor or his subcontractors. Franchised public utilities operating under the jurisdiction of the California Public Utilities Commission are exempt from the provisions of this article for work performed by their own forces.

f. 1404.6 Permit regulations.

House moving permits shall be conditional upon such requirements as may be established by the city engineer subject to the following regulations:

i. Any truck with metal tires used for moving buildings shall not exceed six hundred (600) pounds per inch of tire surface width while loaded.

ii. If rollers are used to move a building, planks shall be placed under the rollers of such width and in such a manner as to protect the surface of the street.

iii. Buildings shall be moved upon rollers or upon a truck or dolly having wheels equipped with pneumatic, solid rubber, or metal tires.

iv. Buildings shall be allowed to remain stationary on a street only where they will not obstruct an intersection or obstruct access to any fire hydrant, standpipe or other fire fighting equipment, located upon or adjacent to such street.

v. Structures shall not be allowed to be moved on the public right-of-way between the hours of thirty (30) minutes after sunset to thirty (30) minutes before sunrise.

vi. The fire, police, and engineering departments of the city shall be notified of the exact location of the building being moved twice each twenty-four (24) hours while the building is being moved. One time shall be between six p.m. and midnight of each twenty-four (24) hours.

vii. Provision shall be made for the protection of any tree, shrub or plant located in, or on any street, park boulevard, alley or public place in the city.

viii. Buildings shall not be moved upon any street at any other time, to any other destination or in any other manner than as stated in a valid permit.

ix. The local utilities shall be notified of the time and place where the moving operations will be carried on.

x. Preparation work on the structure to be moved will not be allowed prior to the issuance of the moving permit.

xi. The city engineer may require such additional regulations as he/she may deem necessary to protect the public health and safety.

(Added during 5-08 supplement: Ord. 2005-09 § 1 (part), 2005; Ord. 2005-08 § 1 (part), 2005)

(Ord. No. 2010-04, § 2, 1-5-2011; Ord. No. 2022-002, § 2, 11-16-2022; Ord. No. 2025-01, § 3, 2-5-2025)

Exceptions & meaning →

Get a plain-English answer with a citation back to this text.

Ask AI about this code
▸Contents — Kingsburg Municipal Code

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.