Section R607 — GLASS UNIT MASONRY
2025 California Residential Code (Title 24, Part 2.5) · 2025 edition · updated 2026-07-29 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
R607.1 General. ¶
Panels of glass unit masonry located in load-bearing and nonload-bearing exterior and interior walls shall be constructed in accordance with this section.
R607.2 Materials. ¶
Hollow glass units shall be partially evacuated and have a minimum average glass face thickness of [3] / 16 inch (5 mm). The surface of units in contact with mortar shall be treated with a polyvinyl butyral coating or latex-based paint. The use of reclaimed units is prohibited.
R607.3 Units. Hollow or solid glass block units shall be standard or thin units. ¶
R607.3.1 Standard units. The specified thickness of standard units shall be not less than 3 [7] / 8 inches (98 mm). R607.3.2 Thin units. The specified thickness of thin units shall be not less than 3 [1] / 8 inches (79 mm) for hollow units and not less than 3 inches (76 mm) for solid units.
R607.4 Isolated panels. ¶
Isolated panels of glass unit masonry shall conform to the requirements of this section.
R607.4.1 Exterior standard-unit panels. The maximum area of each individual standard-unit panel shall be 144 square feet (13.4 m [2] ) where the design wind pressure is 20 pounds per square foot (958 Pa). The maximum area of such panels subjected to design wind pressures other than 20 pounds per square foot (958 Pa) shall be in accordance with Figure R607.4.1. The maximum panel dimension between structural supports shall be 25 feet (7620 mm) in width or 20 feet (6096 mm) in height.
FIGURE R607.4.1—GLASS UNIT MASONRY DESIGN WIND LOAD RESISTANCE
70
60
50
40
30
20
10
00 50 100 150
| STAND PANELS |
ARD UNIT |
||||
200 250 300
MAXIMUM AREA OF PANEL (SQUARE FEET)
For SI: 1 square foot = 0.0929 m [2], 1 pound per square foot = 0.0479 kPa.
6-106 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
WALL CONSTRUCTION
R607.4.2 Exterior thin-unit panels. The maximum area of each individual thin-unit panel shall be 85 square feet (7.9 m [2] ). The maximum dimension between structural supports shall be 15 feet (4572 mm) in width or 10 feet (3048 mm) in height. Thin units shall not be used in applications where the design wind pressure as stated in Table R301.2.1(1) exceeds 20 pounds per square foot (958 Pa).
R607.4.3 Interior panels. The maximum area of each individual standard-unit panel shall be 250 square feet (23.2 m [2] ). The maximum area of each thin-unit panel shall be 150 square feet (13.9 m [2] ). The maximum dimension between structural supports shall be 25 feet (7620 mm) in width or 20 feet (6096 mm) in height.
R607.4.4 Curved panels. The width of curved panels shall conform to the requirements of Sections R607.4.1, R607.4.2 and R607.4.3, except additional structural supports shall be provided at locations where a curved section joins a straight section, and at inflection points in multiple-curve walls.
R607.5 Panel support. ¶
Glass unit masonry panels shall conform to the support requirements of this section. R607.5.1 Deflection. The maximum total deflection of structural members that support glass unit masonry shall not exceed [l] / 600 .
R607.5.2 Lateral support. Glass unit masonry panels shall be laterally supported along the top and sides of the panel. Lateral supports for glass unit masonry panels shall be designed to resist not less than 200 pounds per lineal feet (2918 N/m) of panel, or the actual applied loads, whichever is greater. Except for single-unit panels, lateral support shall be provided by panel anchors along the top and sides spaced not greater than 16 inches (406 mm) on center or by channel-type restraints. Single-unit panels shall be supported by channel-type restraints.
Exceptions:
- Lateral support is not required at the top of panels that are one unit wide.
- Lateral support is not required at the sides of panels that are one unit high.
R607.5.2.1 Panel anchor restraints. Panel anchors shall be spaced not greater than 16 inches (406 mm) on center in both jambs and across the head. Panel anchors shall be embedded not less than 12 inches (305 mm) and shall be provided with two fasteners so as to resist the loads specified in Section R607.5.2.
R607.5.2.2 Channel-type restraints. Glass unit masonry panels shall be recessed not less than 1 inch (25 mm) within channels and chases. Channel-type restraints shall be oversized to accommodate expansion material in the opening, packing and sealant between the framing restraints, and the glass unit masonry perimeter units.
R607.6 Sills. ¶
Before the bedding of glass units, the sill area shall be covered with a water-base asphaltic emulsion coating. The coating shall be not less than [1] / 8 inch (3 mm) thick.
R607.7 Expansion joints. ¶
Glass unit masonry panels shall be provided with expansion joints along the top and sides at all structural supports. Expansion joints shall be not less than [3] / 8 inch (10 mm) in thickness and shall have sufficient thickness to accommodate displacements of the supporting structure. Expansion joints shall be entirely free of mortar and other debris and shall be filled with resilient material.
R607.8 Mortar. ¶
Glass unit masonry shall be laid with Type S or N mortar. Mortar shall not be retempered after initial set. Mortar unused within 1 [1] / 2 hours after initial mixing shall be discarded.
R607.9 Reinforcement. ¶
Glass unit masonry panels shall have horizontal joint reinforcement spaced not greater than 16 inches (406 mm) on center located in the mortar bed joint. Horizontal joint reinforcement shall extend the entire length of the panel but shall not extend across expansion joints. Longitudinal wires shall be lapped not less than 6 inches (152 mm) at splices. Joint reinforcement shall be placed in the bed joint immediately below and above openings in the panel. The reinforcement shall have not less than two parallel longitudinal wires of size W1.7 or greater, and have welded cross wires of size W1.7 or greater.
R607.10 Placement. ¶
Glass units shall be placed so head and bed joints are filled solidly. Mortar shall not be furrowed. Head and bed joints of glass unit masonry shall be [1] / 4 inch (6.4 mm) thick, except that vertical joint thickness of radial panels shall be not less than 1 / 8 inch (3 mm) or greater than 5 / 8 inch (16 mm). The bed joint thickness tolerance shall be minus 1 / 16 inch (1.6 mm) and plus 1 / 8 inch (3 mm). The head joint thickness tolerance shall be plus or minus [1] / 8 inch (3 mm).
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Residential Code (Title 24, Part 2.5)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — BUILDING PLANNING
- Chapter 4 — FOUNDATIONS
- Chapter 5 — FLOORS
-
▸ Chapter 6 — WALL CONSTRUCTION
Overview- Section R601 — GENERAL
- Section R602 — WOOD WALL FRAMING
- Section R603 — COLD-FORMED STEEL WALL FRAMING
- Section R604 — WOOD STRUCTURAL PANELS
- Section R605 — PARTICLEBOARD
- Section R606 — GENERAL MASONRY CONSTRUCTION
- Section R607 — GLASS UNIT MASONRY
- Section R608 — EXTERIOR CONCRETE WALL CONSTRUCTION
- Section R609 — EXTERIOR WINDOWS AND DOORS
- Section R610 — STRUCTURAL INSULATED PANEL WALL CONSTRUCTION
- Chapter 7 — WALL COVERING
- Chapter 8 — ROOF-CEILING CONSTRUCTION
- Chapter 9 — ROOF ASSEMBLIES
- Chapter 10 — CHIMNEYS AND FIREPLACES
- Chapter 44 — REFERENCED STANDARDS
- Appendix AA — BOARD OF APPEALS
- Appendix AB — PERMIT FEES
- Appendix AC — RESERVED
- Appendix BA — RESERVED
- Appendix BB — TINY HOUSES
- Appendix BC — RESERVED
- Appendix BD — RESERVED
- Appendix BE — RADON CONTROL METHODS
- Appendix BF — PATIO COVERS
- Appendix BG — SOUND TRANSMISSION
- Appendix BH — AUTOMATIC VEHICULAR GATES
- Appendix BI — LIGHT STRAW-CLAY CONSTRUCTION
- Appendix BJ — STRAWBALE CONSTRUCTION
- Appendix BK — COB CONSTRUCTION (MONOLITHIC ADOBE)
- Appendix BL — HEMP-LIME (HEMPCRETE) CONSTRUCTION
- Appendix BM — 3D-PRINTED BUILDING CONSTRUCTION
- Appendix BN — EXTENDED PLATE WALL CONSTRUCTION
- Appendix BO — EXISTING BUILDINGS AND STRUCTURES
- Appendix CA — RESERVED
- Appendix CB — RESERVED
- Appendix CC — RESERVED
- Appendix CD — RESERVED
- Appendix CE — RESERVED
- Appendix CF — RESERVED
- Appendix CG — NONSEWERED SANITATION SYSTEMS
- Appendix CH — PRIVATE SEWAGE DISPOSAL
- Appendix CI — SWIMMING POOL SAFETY ACT
- Appendix CJ — EMERGENCY HOUSING
- Appendix CK — AREAS PROTECTED BY THE FACILITIES OF THE CENTRAL…