R603.1 General.

Elements shall be straight and free of any defects that would significantly affect structural performance. Coldformed steel wall framing members shall be in accordance with the requirements of this section.

R603.1.1 Applicability limits. The provisions of this section shall control the construction of exterior cold-formed steel wall framing and interior load-bearing cold-formed steel wall framing for buildings not more than 60 feet (18 288 mm) long perpendicular to the joist or truss span, not more than 40 feet (12 192 mm) wide parallel to the joist or truss span, and less than or equal to three stories above grade plane. Exterior walls installed in accordance with the provisions of this section shall be considered as loadbearing walls. Cold-formed steel walls constructed in accordance with the provisions of this section shall be limited to sites where the ultimate design wind speed is less than 140 miles per hour (63 m/s), Exposure Category B or C, and the ground snow load is less than or equal to 70 pounds per square foot (3.35 kPa).

R603.1.1.1 Alternate applications. Cold-formed steel wall framing for buildings exceeding the applicability limits of Section R603.1.1 are permitted to be designed and constructed in accordance with AISI S230, subject to the limits therein.

R603.1.2 In-line framing. Load-bearing cold-formed steel studs constructed in accordance with Section R603 shall be located inline with joists, trusses and rafters in accordance with the tolerances specified in AISI S240, Section B1.2.3.

R603.2 Structural framing.

Load-bearing cold-formed steel wall framing members shall be in accordance with this section.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

R603.2.1 Material. Load-bearing cold-formed steel framing members shall be cold formed to shape from structural-quality sheet steel complying with the requirements of AISI S240, Section A3.

R603.2.2 Corrosion protection. Load-bearing cold-formed steel framing shall have a protective coating complying with AISI S240, Section A4.

R603.2.3 Dimension, thickness and material grade. Load-bearing cold-formed steel wall framing members shall comply with the dimensional and thickness requirements specified in AISI S230, Section A4.3 and material grade requirements as specified in AISI S230, Section A4.4.

R603.2.4 Identification. Load-bearing cold-formed steel framing members shall meet the product identification requirements of AISI S240, Section A5.5.

R603.2.5 Fastening. Screws for steel-to-steel connections shall be installed with a minimum edge distance and center-to-center spacing of [1] / 2 inch (12.7 mm), shall be self-drilling tapping and shall conform to ASTM C1513. Structural sheathing shall be attached to cold-formed steel studs with minimum No. 8 self-drilling tapping screws that conform to ASTM C1513. Screws for attaching structural sheathing to cold-formed steel wall framing shall have a minimum head diameter of 0.292 inch (7.4 mm) with countersunk heads and shall be installed with a minimum edge distance of [3] / 8 inch (9.5 mm). Gypsum board shall be attached to cold-formed steel wall framing with minimum No. 6 screws conforming to ASTM C954 or ASTM C1513 with a bugle-head style and shall be installed in accordance with Section R702. For connections, screws shall extend through the steel not fewer than three exposed threads. Fasteners shall have rust-inhibitive coating suitable for the installation in which they are being used, or be manufactured from material not susceptible to corrosion.

R603.2.6 Web holes, web hole reinforcing and web hole patching. Web holes in wall studs shall comply with the conditions as prescribed in AISI S230, Section A4.5. Web holes not in conformance to the conditions as prescribed in AISI S230, Section A4.5 shall be reinforced in accordance with the provisions of AISI S230, Section A4.6 or patched in accordance with the provisions of AISI S230, Section A4.7.

R603.3 Wall construction.

Exterior cold-formed steel framed walls and interior load-bearing cold-formed steel framed walls shall be constructed in accordance with the provisions of this section.

R603.3.1 Wall to foundation or floor connection. Cold-formed steel framed walls shall be anchored to foundations or floors in accordance with Table R603.3.1 and Figure R603.3.1(1), R603.3.1(2), R603.3.1(3) or R603.3.1(4). Anchor bolts shall be located not more than 12 inches (305 mm) from corners or the termination of bottom tracks. Anchor bolts shall extend not less than 15 inches (381 mm) into masonry or 7 inches (178 mm) into concrete. Foundation anchor straps shall be permitted, in lieu of anchor bolts, if spaced as required to provide equivalent anchorage to the required anchor bolts and installed in accordance with manufacturer’s requirements.

TABLE R603.3.1—WALL TO FOUNDATION OR FLOOR CONNECTION REQUIREMENTSa, b

FRAMING CONDITION ULTIMATE WIND SPEED AND EXPOSURE CATEGORY (mph) ULTIMATE WIND SPEED AND EXPOSURE CATEGORY (mph) ULTIMATE WIND SPEED AND EXPOSURE CATEGORY (mph) ULTIMATE WIND SPEED AND EXPOSURE CATEGORY (mph) ULTIMATE WIND SPEED AND EXPOSURE CATEGORY (mph) ULTIMATE WIND SPEED AND EXPOSURE CATEGORY (mph)
FRAMING CONDITION 115 B 120 B 130 B or
115 C
< 140 B or
120 C
130 C < 140 C
Wall bottom track to floor per
Figure R603.3.1(1)
1-No. 8 screw
at 12″ o.c.
1-No. 8 screw
at 8″ o.c.
2-No. 8 screws
at 8″ o.c.
2-No. 8 screws
at 6″ o.c.
3-No. 8 screws
at 8″ o.c.
3-No. 8 screws
at 6″ o.c.
Wall bottom track to foundation per
Figure R603.3.1(2)d
1/2″ minimum
diameter
anchor bolt at
6′ o.c.
1/2″ minimum
diameter
anchor bolt at
6′ o.c.
1/2″ minimum
diameter
anchor bolt at
4′ o.c.
1/2″ minimum
diameter
anchor bolt at
4′ o.c.
1/2″ minimum
diameter
anchor bolt at
3′-4″ o.c.
1/2″ minimum
diameter
anchor bolt at
2′-8″ o.c.
Wall bottom track to wood sill per
Figure R603.3.1(3)
Steel plate
spaced at
4′ o.c., with
4-No. 8 screws
and 4-10d or
6-8d common
nails
Steel plate
spaced at
4′ o.c., with
4-No. 8 screws
and 4-10d or
6-8d common
nails
Steel plate
spaced at
3′ o.c., with
4-No. 8 screws
and 4-10d or
6-8d common
nails
Steel plate
spaced at
3′ o.c., with
4-No. 8 screws
and 4-10d or
6-8d common
nails
Steel plate
spaced at
2′ o.c., with
4-No. 8 screws
and 4-10d or
6-8d common
nails
Steel plate
spaced at
1′-4″ o.c., with
4-No. 8 screws
and 4-10d or
6-8d common
nails

6-54 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.3.1—WALL TO FOUNDATION OR FLOOR CONNECTION REQUIREMENTSa, b—continued

FRAMING CONDITION FRAMING CONDITION FRAMING CONDITION ULTIMATE WIND SPEED AND EXPOSURE CATEGORY (mph) ULTIMATE WIND SPEED AND EXPOSURE CATEGORY (mph) ULTIMATE WIND SPEED AND EXPOSURE CATEGORY (mph) ULTIMATE WIND SPEED AND EXPOSURE CATEGORY (mph) ULTIMATE WIND SPEED AND EXPOSURE CATEGORY (mph) ULTIMATE WIND SPEED AND EXPOSURE CATEGORY (mph)
FRAMING CONDITION FRAMING CONDITION FRAMING CONDITION 115 B 120 B 130 B or
115 C
< 140 B or
120 C
130 C < 140 C
Wind uplift
connector
strength (lb)c, e
Stud
Spacing
(inches)
Roof
Span
(feet)
Wind uplift
connector
strength (lb)c, e
16 24 NR NR NR NR NR NR
Wind uplift
connector
strength (lb)c, e
16 28 NR NR NR NR NR 339
Wind uplift
connector
strength (lb)c, e
16 32 NR NR NR NR NR 382
Wind uplift
connector
strength (lb)c, e
16 36 NR NR NR NR 333 426
Wind uplift
connector
strength (lb)c, e
16 40 NR NR NR NR 368 470
Wind uplift
connector
strength (lb)c, e
24 24 NR NR NR NR 343 443
Wind uplift
connector
strength (lb)c, e
24 28 NR NR NR NR 395 508
Wind uplift
connector
strength (lb)c, e
24 32 NR NR NR 330 447 573
Wind uplift
connector
strength (lb)c, e
24 36 NR NR NR 371 500 639
Wind uplift
connector
strength (lb)c, e
24 40 NR NR 345 411 552 704

For SI: 1 inch = 25.4 mm, 1 mile per hour = 0.447 m/s, 1 foot = 304.8 mm, 1 pound = 4.45 N.
a. Anchor bolts are to be located not more than 12 inches from corners or the termination of bottom tracks, such as at door openings or corners. Bolts are to extend not less than
15 inches into masonry or 7 inches into concrete.
b. All screw sizes shown are minimum.
c. NR = Uplift connector not required.
d. Foundation anchor straps are permitted in place of anchor bolts, if spaced as required to provide equivalent anchorage to the required anchor bolts and installed in accor-
dance with manufacturer’s requirements.
e. See Figure R603.3.1(4) for details.

FIGURE R603.3.1(1)—WALL TO FLOOR CONNECTION

FLOOR JOIST

FLOOR SHEATHING

NO. 8 SCREWS SPACED PER TABLE R603.3.1

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TRACK

For SI: 1 inch = 25.4 mm.

For SI: 1 mil = 0.0254 mm, 1 inch = 25.4 mm.

FIGURE R603.3.1(2)—WALL TO FOUNDATION CONNECTION

NO. 8 SCREW THROUGH EACH FLANGE

4 NO. 8 SCREWS THROUGH EACH FLANGE

STUD BLOCKING INSIDE WALL TRACK (MINIMUM THICKNESS OF STUD)

ANCHOR BOLT OR OTHER CONNECTION AS REQUIRED

FOUNDATION OR SLAB ON GRADE

SILL SEALER AS REQUIRED

FIGURE R603.3.1(3)—WALL TO WOOD SILL CONNECTION

MINIMUM 3 ″ x 4 ″ x 33 MIL

METAL PLATE

4-10d OR 6-8d COMMON NAIL

NO. 8 SCREW THROUGH EACH FLANGE

MINIMUM 4 NO. 8 SCREWS

ANCHOR BOLT THROUGH WOOD SILL OR OTHER CONNECTION AS REQUIRED

6-56 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

FIGURE R603.3.1(4)—WIND UPLIFT CONNECTOR

CONTINUOUS 1.25 IN. .33 MIL STEEL STRAP UNDER WOOD SILL ATTACHED TO EACH FLANGE OF STUD

ANCHOR BOLT OR OTHER CONNECTOR AS REQUIRED

For SI: 1 mil = 0.0254 mm, 1 inch = 25.4 mm.

WOOD FOUNDATION SILL

CON
STRA
TO E
WOOD FOUN

R603.3.1.1 Gable endwalls. Gable endwalls with heights greater than 10 feet (3048 mm) shall be anchored to foundations or floors in accordance with Table R603.3.1.1(1) or R603.3.1.1(2).

TABLE R603.3.1.1(1)—GABLE ENDWALL TO FLOOR CONNECTION REQUIREMENTSa, b, c

** ULTIMATE WIND SPEED**
(mph)
** ULTIMATE WIND SPEED**
(mph)
** WALL BOTTOM TRACK TO FLOOR JOIST OR TRACK CONNECTION** ** WALL BOTTOM TRACK TO FLOOR JOIST OR TRACK CONNECTION** ** WALL BOTTOM TRACK TO FLOOR JOIST OR TRACK CONNECTION**
** Exposure Category** ** Exposure Category** ** Stud height,****h
(feet)**
** Stud height,****h
(feet)**
** Stud height,****h
(feet)**
** B** ** C** ** 10 <****h ≤ 14** ** 14 <****h ≤ 18** ** 18 <****h ≤ 22**
115 1-No. 8 screw @ 12″ o.c. 1-No. 8 screw @ 12″ o.c. 1-No. 8 screw @ 12″ o.c.
120 1-No. 8 screw @ 12″ o.c. 1-No. 8 screw @ 12″ o.c. 1-No. 8 screw @ 12″ o.c.
130 115 1-No. 8 screw @ 12″ o.c. 1-No. 8 screw @ 12″ o.c. 2-No. 8 screws @ 12″ o.c.
< 140 120 1-No. 8 screw @ 12″ o.c. 1-No. 8 screw @ 12″ o.c. 2-No. 8 screws @ 12″ o.c.
130 2-No. 8 screws @ 12″ o.c. 1-No. 8 screw @ 8″ o.c. 2-No. 8 screws @ 8″ o.c.
< 140 2-No. 8 screws @ 12″ o.c. 1-No. 8 screw @ 8″ o.c. 2-No. 8 screws @ 8″ o.c.
For SI: 1 inch = 25.4 mm, 1 mile per hour = 0.447 m/s, 1 foot = 304.8 mm.
a. Refer to Table R603.3.1.1(2) for gable endwall bottom track to foundation connections.
b. Where attachment is not given, special design is required.
c. Stud height,h, is measured from wall bottom track to wall top track or brace connection height.

TABLE R603.3.1.1(2)—GABLE ENDWALL BOTTOM TRACK TO FOUNDATION CONNECTION REQUIREMENTSa, b, c

** ULTIMATE WIND SPEED**
(mph)
** ULTIMATE WIND SPEED**
(mph)
** MINIMUM SPACING FOR1/2-INCH-DIAMETER ANCHOR BOLTSd** ** MINIMUM SPACING FOR1/2-INCH-DIAMETER ANCHOR BOLTSd** ** MINIMUM SPACING FOR1/2-INCH-DIAMETER ANCHOR BOLTSd**
** Exposure Category** ** Exposure Category** ** Stud height,****h
(feet)**
** Stud height,****h
(feet)**
** Stud height,****h
(feet)**
** B** ** C** ** 10 <****h ≤ 14** ** 14 <****h ≤ 18** ** 18 <****h ≤ 22**
115 6′-0″ o.c. 6′-0″ o.c. 6′-0″ o.c.
120 6′-0″ o.c. 5′-7″ o.c. 6′-0″ o.c.
130 115 5′-0″ o.c. 6′-0″ o.c. 6′-0″ o.c.
< 140 120 6′-0″ o.c. 5′-6″ o.c. 6′-0″ o.c.
130 5′-3″ o.c. 6′-0″ o.c. 6′-0″ o.c.
< 140 3′-0″ o.c. 3′-0″ o.c. 3′-0″ o.c.

For SI: 1 inch = 25.4 mm, 1 mile per hour = 0.447 m/s, 1 foot = 304.8 mm.
a. Refer to Table R603.3.1.1(1) for gable endwall bottom track to floor joist or track connection connections.
b. Where attachment is not given, special design is required.
c. Stud height,h, is measured from wall bottom track to wall top track or brace connection height.
d. Foundation anchor straps are permitted in place of anchor bolts if spaced as required to provide equivalent anchorage to the required anchor bolts and installed in accor-
dance with manufacturer’s requirements.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

R603.3.2 Minimum stud sizes. Cold-formed steel walls shall be constructed in accordance with Figure R603.3.1(1), R603.3.1(2) or R603.3.1(3), as applicable. Exterior wall stud size and thickness shall be determined in accordance with the limits set forth in Tables R603.3.2(2) through R603.3.2(16). Interior load-bearing wall stud size and thickness shall be determined in accordance with the limits set forth in Tables R603.3.2(2) through R603.3.2(16) based on an ultimate design wind speed of 115 miles per hour (51 m/s), Exposure Category B, and the building width, stud spacing and ground snow load, as appropriate. Fastening requirements shall be in accordance with Section R603.2.5 and Table R603.3.2(1). Top and bottom tracks shall have the same minimum thickness as the wall studs.

Exterior wall studs shall be permitted to be reduced to the next thinner size, as shown in Tables R603.3.2(2) through R603.3.2(16), but not less than 33 mils (0.84 mm), where both of the following conditions exist:

  1. Minimum of [1] / 2 -inch (12.7 mm) gypsum board is installed and fastened on the interior surface in accordance with Section R702.

  2. Wood structural sheathing panels of minimum [7] / 16 -inch-thick (11.1 mm) oriented strand board or [15] / 32 -inch-thick (12 mm) plywood are installed and fastened in accordance with Section R603.9.1 and Table R603.3.2(1) on the outside surface.

Interior load-bearing walls shall be permitted to be reduced to the next thinner size, as shown in Tables R603.3.2(2) through R603.3.2(16), but not less than 33 mils (0.84 mm), where not less than [1] / 2 -inch (12.7 mm) gypsum board is installed and fastened in accordance with Section R702 on both sides of the wall. The tabulated stud thickness for load-bearing walls shall be used where the attic load is 10 pounds per square foot (480 Pa) or less. A limited attic storage load of 20 pounds per square foot (960 Pa) shall be permitted provided that the next higher snow load column is used to select the stud size from Tables R603.3.2(2) through R603.3.2(16).

For two-story buildings, the tabulated stud thickness for walls supporting one floor, roof and ceiling shall be used where the second-floor live load is 30 pounds per square foot (1440 Pa). Second-floor live loads of 40 psf (1920 Pa) shall be permitted provided that the next higher snow load column is used to select the stud size from Tables R603.3.2(2) through R603.3.2(11).

For three-story buildings, the tabulated stud thickness for walls supporting one or two floors, roof and ceiling shall be used where the third-floor live load is 30 pounds per square foot (1440 Pa). Third-floor live loads of 40 pounds per square foot (1920 Pa) shall be permitted provided that the next higher snow load column is used to select the stud size from Tables R603.3.2(12) through R603.3.2(16).

hree-story buildings, the tabulated stud thickness for walls supporting one or two floors, roof and ceiling shall be used where the third-floor live load is 30 pounds per square foot (1440 Pa). Third-floor live loads of 40 pounds per square foot (1920 Pa) shall be permitted provided that the next higher snow load column is used to select the stud size from Tables R603.3.2(12) through R603.3.2(16).

TABLE R603.3.2(1)—WALL FASTENING SCHEDULEa

DESCRIPTION OF BUILDING ELEMENT NUMBER AND SIZE OF FASTENERSa SPACING OF FASTENERS
Wall stud to top or bottom track 2-No. 8 screws Each end of stud, one per flange
Structural sheathing to wall studs No. 8 screwsb 6″ o.c. on edges and 12″ o.c. at intermediate supports
1/2″ gypsum board to framing No. 6 screws 12″ o.c.
For SI: 1 inch = 25.4 mm.
a. All screw sizes shown are minimum.
b. Screws for attachment of structural sheathing panels are to be bugle-head, flat-head, or similar head styles with a minimum head diameter of 0.29 inch.

6-58 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.3.2(2)—24-FOOT-WIDE BUILDING SUPPORTING ROOF AND CEILING ONLYa, b, c, d

ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
8-foot studs 8-foot studs 8-foot studs 8-foot studs 9-foot studs 9-foot studs 9-foot studs 9-foot studs 10-foot studs 10-foot studs 10-foot studs 10-foot studs
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
Ground snow load (psf) Ground snow load (psf) Ground snow load (psf) Ground snow load (psf) Ground snow load (psf) Ground snow load (psf) Ground snow load (psf) Ground snow load (psf) Ground snow load (psf) Ground snow load (psf) Ground snow load (psf) Ground snow load (psf)
Exp. B Exp. C Exp. C Exp. C 20 30 50 70 20 30 50 70 20 30 50 70
115 350S162 16 33 33 33 33 33 33 33 33 33 33 33 33
115 350S162 24 33 33 33 43 33 33 33 43 33 33 43 43
115 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
115 550S162 24 33 33 33 33 33 33 33 33 33 33 33 43
120 350S162 16 33 33 33 33 33 33 33 33 33 33 33 33
120 350S162 24 33 33 33 43 33 33 33 43 43 43 43 43
120 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
120 550S162 24 33 33 33 43 33 33 33 33 33 33 33 43
130 115 350S162 16 33 33 33 33 33 33 33 33 33 33 33 33
130 115 350S162 24 33 33 43 43 43 43 43 43 43 43 43 54
130 115 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
130 115 550S162 24 33 33 33 43 33 33 33 43 33 33 33 43
< 140 120 350S162 16 33 33 33 33 33 33 33 33 33 33 33 43
< 140 120 350S162 24 33 33 43 43 43 43 43 43 54 54 54 54
< 140 120 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
< 140 120 550S162 24 33 33 33 43 33 33 33 43 43 43 43 43
130 350S162 16 33 33 33 33 33 33 33 33 43 43 43 43
130 350S162 24 43 43 43 43 54 54 54 54 54 54 54 54
130 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
130 550S162 24 33 33 33 43 43 43 43 43 43 43 43 43
< 140 350S162 16 33 33 33 33 43 43 43 43 43 43 43 43
< 140 350S162 24 43 43 43 54 54 54 54 54 54 54 54 54
< 140 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
< 140 550S162 24 43 43 43 43 43 43 43 43 43 43 43 43

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criterion:L/240.
b. Design load assumptions:
Second-floor dead load is 10 psf.
Second-floor live load is 30 psf.
Roof/ceiling dead load is 12 psf.
Attic live load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the wall studs.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.3.2(3)—28-FOOT-WIDE BUILDING SUPPORTING ROOF AND CEILING ONLYa, b, c, d

ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
8-foot studs 8-foot studs 8-foot studs 8-foot studs 9-foot studs 9-foot studs 9-foot studs 9-foot studs 10-foot studs 10-foot studs 10-foot studs 10-foot studs
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
Ground snow load (psf) Ground snow load (psf) Ground snow load (psf) Ground snow load (psf) Ground snow load (psf) Ground snow load (psf) Ground snow load (psf) Ground snow load (psf) Ground snow load (psf) Ground snow load (psf) Ground snow load (psf) Ground snow load (psf)
Exp. B Exp. C Exp. C Exp. C 20 30 50 70 20 30 50 70 20 30 50 70
115 350S162 16 33 33 33 33 33 33 33 33 33 33 33 33
115 350S162 24 33 33 43 43 33 33 43 43 33 33 43 54
115 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
115 550S162 24 33 33 33 43 33 33 33 43 33 33 33 43
120 350S162 16 33 33 33 33 33 33 33 33 33 33 33 33
120 350S162 24 33 33 43 43 33 33 43 43 43 43 43 54
120 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
120 550S162 24 33 33 33 43 33 33 33 43 33 33 33 43
130 115 350S162 16 33 33 33 33 33 33 33 33 33 33 33 43
130 115 350S162 24 33 33 43 54 43 43 43 54 43 43 43 54
130 115 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
130 115 550S162 24 33 33 33 43 33 33 33 43 33 33 33 43
< 140 120 350S162 16 33 33 33 33 33 33 33 33 33 33 33 43
< 140 120 350S162 24 33 33 43 54 43 43 43 54 54 54 54 54
< 140 120 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
< 140 120 550S162 24 33 33 33 43 33 33 33 43 43 43 43 43
130 350S162 16 33 33 33 33 33 33 33 43 43 43 43 43
130 350S162 24 43 43 43 54 54 54 54 54 54 54 54 54
130 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
130 550S162 24 33 33 33 43 43 43 43 43 43 43 43 43
< 140 350S162 16 33 33 33 43 43 43 43 43 43 43 43 43
< 140 350S162 24 43 43 43 54 54 54 54 54 54 54 54 54
< 140 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
< 140 550S162 24 43 43 43 43 43 43 43 43 43 43 43 43

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criterion:L/240.
b. Design load assumptions:
Second-floor dead load is 10 psf.
Second-floor live load is 30 psf.
Roof/ceiling dead load is 12 psf.
Attic live load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the wall studs.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

6-60 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.3.2(4)—32-FOOT-WIDE BUILDING SUPPORTING ROOF AND CEILING ONLYa, b, c, d

ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
8-foot studs 8-foot studs 8-foot studs 8-foot studs 9-foot studs 9-foot studs 9-foot studs 9-foot studs 10-foot studs 10-foot studs 10-foot studs 10-foot studs
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Exp. B Exp. C Exp. C Exp. C 20 30 50 70 20 30 50 70 20 30 50 70
115 350S162 16 33 33 33 33 33 33 33 33 33 33 33 43
115 350S162 24 33 33 43 54 33 33 43 54 43 43 43 54
115 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
115 550S162 24 33 33 33 43 33 33 33 43 33 33 33 43
120 350S162 16 33 33 33 33 33 33 33 33 33 33 33 43
120 350S162 24 33 33 43 54 33 33 43 54 43 43 43 54
120 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
120 550S162 24 33 33 33 43 33 33 33 43 33 33 43 43
130 115 350S162 16 33 33 33 43 33 33 33 43 33 33 33 43
130 115 350S162 24 33 33 43 54 43 43 43 54 43 43 54 54
130 115 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
130 115 550S162 24 33 33 43 43 33 33 33 43 33 33 43 43
< 140 120 350S162 16 33 33 33 43 33 33 33 43 33 33 33 43
< 140 120 350S162 24 33 33 43 54 43 43 43 54 54 54 54 54
< 140 120 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
< 140 120 550S162 24 33 33 43 43 33 33 33 43 43 43 43 43
130 350S162 16 33 33 33 43 33 33 33 43 43 43 43 43
130 350S162 24 43 43 43 54 54 54 54 54 54 54 54 54
130 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
130 550S162 24 33 33 43 43 43 43 43 43 43 43 43 43
< 140 350S162 16 33 33 33 43 43 43 43 43 43 43 43 43
< 140 350S162 24 43 43 54 54 54 54 54 54 54 54 54 54
< 140 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
< 140 550S162 24 43 43 43 43 43 43 43 43 43 43 43 43

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criterion:L/240.
b. Design load assumptions:
Second-floor dead load is 10 psf.
Second-floor live load is 30 psf.
Roof/ceiling dead load is 12 psf.
Attic live load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the wall studs.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.3.2(5)—36-FOOT-WIDE BUILDING SUPPORTING ROOF AND CEILING ONLYa, b, c, d

ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
8-foot studs 8-foot studs 8-foot studs 8-foot studs 9-foot studs 9-foot studs 9-foot studs 9-foot studs 10-foot studs 10-foot studs 10-foot studs 10-foot studs
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Exp. B Exp. C Exp. C Exp. C 20 30 50 70 20 30 50 70 20 30 50 70
115 350S162 16 33 33 33 43 33 33 33 43 33 33 33 43
115 350S162 24 33 33 43 54 33 33 43 54 43 43 54 54
115 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
115 550S162 24 33 33 43 43 33 33 43 43 33 33 43 43
120 350S162 16 33 33 33 43 33 33 33 43 33 33 33 43
120 350S162 24 33 33 43 54 33 33 43 54 43 43 54 54
120 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
120 550S162 24 33 33 43 43 33 33 43 43 33 33 43 43
130 115 350S162 16 33 33 33 43 33 33 33 43 33 33 43 43
130 115 350S162 24 33 43 43 54 43 43 43 54 43 43 54 54
130 115 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
130 115 550S162 24 33 33 43 43 33 33 43 43 33 33 43 43
< 140 120 350S162 16 33 33 33 43 33 33 33 33 33 33 43 43
< 140 120 350S162 24 43 43 43 54 43 43 43 54 54 54 54 54
< 140 120 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
< 140 120 550S162 24 33 33 43 43 33 33 43 43 43 43 43 54
130 350S162 16 33 33 33 43 33 33 33 43 43 43 43 43
130 350S162 24 43 43 54 54 54 54 54 54 54 54 54 54
130 550S162 16 33 33 33 33 33 33 33 33 33 33 33 43
130 550S162 24 33 33 43 54 43 43 43 43 43 43 43 54
< 140 350S162 16 33 33 33 43 43 43 43 43 43 43 43 54
< 140 350S162 24 43 43 54 54 54 54 54 54 54 54 54 68
< 140 550S162 16 33 33 33 33 33 33 33 33 33 33 33 43
< 140 550S162 24 43 43 43 54 43 43 43 43 43 43 43 54

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criterion:L/240.
b. Design load assumptions:
Second-floor dead load is 10 psf.
Second-floor live load is 30 psf.
Roof/ceiling dead load is 12 psf.
Attic live load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the wall studs.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

6-62 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.3.2(6)—40-FOOT-WIDE BUILDING SUPPORTING ROOF AND CEILING ONLYa, b, c, d

ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
8-foot studs 8-foot studs 8-foot studs 8-foot studs 9-foot studs 9-foot studs 9-foot studs 9-foot studs 10-foot studs 10-foot studs 10-foot studs 10-foot studs
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Exp. B Exp. C Exp. C Exp. C 20 30 50 70 20 30 50 70 20 30 50 70
115 350S162 16 33 33 33 43 33 33 33 43 33 33 43 43
115 350S162 24 33 33 43 54 33 43 43 54 43 43 54 54
115 550S162 16 33 33 33 43 33 33 33 33 33 33 33 33
115 550S162 24 33 33 43 54 33 33 43 43 33 33 43 54
120 350S162 16 33 33 33 43 33 33 33 43 33 33 43 43
120 350S162 24 33 43 43 54 33 43 43 54 43 43 54 54
120 550S162 16 33 33 33 43 33 33 33 33 33 33 33 43
120 550S162 24 33 33 43 54 33 33 43 43 33 33 43 54
130 115 350S162 16 33 33 33 43 33 33 33 43 33 33 43 43
130 115 350S162 24 43 43 54 54 43 43 54 54 43 54 54 54
130 115 550S162 16 33 33 33 43 33 33 33 33 33 33 33 43
130 115 550S162 24 33 33 43 54 33 33 43 54 33 33 43 54
< 140 120 350S162 16 33 33 33 43 33 33 33 43 33 33 43 43
< 140 120 350S162 24 43 43 54 54 43 43 54 54 54 54 54 54
< 140 120 550S162 16 33 33 33 43 33 33 33 33 33 33 33 43
< 140 120 550S162 24 33 33 43 54 33 33 43 54 43 43 43 54
130 350S162 16 33 33 43 43 33 33 43 43 43 43 43 54
130 350S162 24 43 43 54 54 54 54 54 54 54 54 54 68
130 550S162 16 33 33 33 43 33 33 33 43 33 33 33 43
130 550S162 24 33 33 43 54 43 43 43 54 43 43 43 54
< 140 350S162 16 33 33 43 43 43 43 43 43 43 43 43 54
< 140 350S162 24 43 43 54 54 54 54 54 54 54 54 54 68
< 140 550S162 16 33 33 33 43 33 33 33 43 33 33 33 43
< 140 550S162 24 43 43 43 54 43 43 43 54 43 43 43 54

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criterion:L/240.
b. Design load assumptions:
Second-floor dead load is 10 psf.
Second-floor live load is 30 psf.
Roof/ceiling dead load is 12 psf.
Attic live load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the wall studs.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.3.2(7)—24-FOOT-WIDE BUILDING SUPPORTING ONE FLOOR, ROOF AND CEILINGa, b, c, d

ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
8-foot studs 8-foot studs 8-foot studs 8-foot studs 9-foot studs 9-foot studs 9-foot studs 9-foot studs 10-foot studs 10-foot studs 10-foot studs 10-foot studs
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Exp. B Exp. C Exp. C Exp. C 20 30 50 70 20 30 50 70 20 30 ** 50** 70
115 350S162 16 33 33 33 33 33 33 33 33 33 33 33 43
115 350S162 24 33 33 43 43 43 43 43 43 43 43 43 54
115 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
115 550S162 24 33 33 33 43 33 33 33 43 33 33 33 43
120 350S162 16 33 33 33 33 33 33 33 33 33 33 33 43
120 350S162 24 43 43 43 43 43 43 43 43 43 43 54 54
120 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
120 550S162 24 33 33 33 43 33 33 33 43 33 33 33 43
130 115 350S162 16 33 33 33 43 33 33 33 43 43 43 43 43
130 115 350S162 24 43 43 43 54 43 43 54 54 54 54 54 54
130 115 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
130 115 550S162 24 33 33 33 43 33 33 33 43 33 33 43 43
< 140 120 350S162 16 33 33 33 43 33 33 43 43 43 43 43 43
< 140 120 350S162 24 43 43 43 54 43 54 54 54 54 54 54 54
< 140 120 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
< 140 120 550S162 24 33 33 43 43 33 33 33 43 43 43 43 43
130 350S162 16 33 33 33 43 43 43 43 43 43 43 43 54
130 350S162 24 43 43 54 54 54 54 54 54 54 54 54 54
130 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
130 550S162 24 33 33 43 43 43 43 43 43 43 43 43 43
< 140 350S162 16 43 43 43 43 43 43 43 43 54 54 54 54
< 140 350S162 24 54 54 54 54 54 54 54 54 54 54 54 54
< 140 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
< 140 550S162 24 43 43 43 43 43 43 43 43 43 43 43 43

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criterion:L/240.
b. Design load assumptions:
Second-floor dead load is 10 psf.
Second-floor live load is 30 psf.
Roof/ceiling dead load is 12 psf.
Attic live load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the wall studs.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

6-64 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.3.2(8)—28-FOOT-WIDE BUILDING SUPPORTING ONE FLOOR, ROOF AND CEILINGa, b, c, d

ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
8-foot studs 8-foot studs 8-foot studs 8-foot studs 9-foot studs 9-foot studs 9-foot studs 9-foot studs 10-foot studs 10-foot studs 10-foot studs 10-foot studs
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Exp. B Exp. C Exp. C Exp. C 20 30 50 70 20 30 50 70 20 30 50 70
115 350S162 16 33 33 33 43 33 33 33 43 33 33 43 43
115 350S162 24 43 43 43 54 43 43 43 54 43 43 54 54
115 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
115 550S162 24 33 33 43 43 33 33 43 43 33 33 43 43
120 350S162 16 33 33 33 43 33 33 33 43 33 33 43 43
120 350S162 24 43 43 43 54 43 43 43 54 54 54 54 54
120 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
120 550S162 24 33 33 43 43 33 33 43 43 33 33 43 43
130 115 350S162 16 33 33 33 43 33 33 43 43 43 43 43 43
130 115 350S162 24 43 43 43 54 43 54 54 54 54 54 54 54
130 115 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
130 115 550S162 24 33 33 43 43 33 33 43 43 43 43 43 43
< 140 120 350S162 16 33 33 33 43 43 43 43 43 43 43 43 43
< 140 120 350S162 24 43 43 54 54 54 54 54 54 54 54 54 54
< 140 120 550S162 16 33 33 33 33 33 33 33 33 33 33 33 33
< 140 120 550S162 24 33 33 43 43 33 33 43 43 43 43 43 43
130 350S162 16 33 33 43 43 43 43 43 43 43 43 54 54
130 350S162 24 54 54 54 54 54 54 54 54 54 54 54 54
130 550S162 16 33 33 33 33 33 33 33 33 33 33 33 43
130 550S162 24 33 33 43 43 43 43 43 43 43 43 43 43
< 140 350S162 16 43 43 43 43 43 43 43 43 54 54 54 54
< 140 350S162 24 54 54 54 54 54 54 54 54 54 54 54 54
< 140 550S162 16 33 33 33 33 33 33 33 33 33 33 33 43
< 140 550S162 24 43 43 43 43 43 43 43 43 43 43 43 54

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criterion:L/240.
b. Design load assumptions:
Second-floor dead load is 10 psf.
Second-floor live load is 30 psf.
Roof/ceiling dead load is 12 psf.
Attic live load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the wall studs.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.3.2(9)—32-FOOT-WIDE BUILDING SUPPORTING ONE FLOOR, ROOF AND CEILINGa, b, c, d

ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
8-foot studs 8-foot studs 8-foot studs 8-foot studs 9-foot studs 9-foot studs 9-foot studs 9-foot studs 10-foot studs 10-foot studs 10-foot studs 10-foot studs
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Exp. B Exp. C Exp. C Exp. C 20 30 50 70 20 30 50 70 20 30 50 70
115 350S162 16 33 33 33 43 33 33 33 43 33 43 43 43
115 350S162 24 43 43 43 54 43 43 43 54 54 54 54 54
115 550S162 16 33 33 33 43 33 33 33 33 33 33 33 43
115 550S162 24 33 43 43 54 33 33 43 43 33 33 43 43
120 350S162 16 33 33 33 43 33 33 33 43 43 43 43 43
120 350S162 24 43 43 43 54 43 43 43 54 54 54 54 54
120 550S162 16 33 33 33 43 33 33 33 33 33 33 33 43
120 550S162 24 33 43 43 54 33 33 43 43 33 33 43 54
130 115 350S162 16 33 33 43 43 43 43 43 43 43 43 43 43
130 115 350S162 24 43 43 54 54 54 54 54 54 54 54 54 54
130 115 550S162 16 33 33 33 43 33 33 33 33 33 33 33 43
130 115 550S162 24 33 43 43 54 33 33 43 43 43 43 43 54
< 140 120 350S162 16 33 33 43 43 43 43 43 43 43 43 43 54
< 140 120 350S162 24 43 54 54 54 54 54 54 54 54 54 54 54
< 140 120 550S162 16 33 33 33 43 33 33 33 43 33 33 33 43
< 140 120 550S162 24 33 43 43 54 33 43 43 43 43 43 43 54
130 350S162 16 43 43 43 43 43 43 43 43 43 54 54 54
130 350S162 24 54 54 54 54 54 54 54 54 54 54 54 54
130 550S162 16 33 33 33 43 33 33 33 43 33 33 33 43
130 550S162 24 43 43 43 54 43 43 43 54 43 43 43 54
< 140 350S162 16 43 43 43 43 43 43 43 54 54 54 54 54
< 140 350S162 24 54 54 54 54 54 54 54 54 54 54 54 68
< 140 550S162 16 33 33 33 43 33 33 33 43 33 33 33 43
< 140 550S162 24 43 43 43 54 43 43 43 54 43 43 43 54

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criterion:L/240.
b. Design load assumptions:
Second-floor dead load is 10 psf.
Second-floor live load is 30 psf.
Roof/ceiling dead load is 12 psf.
Attic live load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the wall studs.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

6-66 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.3.2(10)—36-FOOT-WIDE BUILDING SUPPORTING ONE FLOOR, ROOF AND CEILINGa, b, c, d

ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
8-foot studs 8-foot studs 8-foot studs 8-foot studs 9-foot studs 9-foot studs 9-foot studs 9-foot studs 10-foot studs 10-foot studs 10-foot studs 10-foot studs
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Exp. B Exp. C Exp. C Exp. C 20 30 50 70 20 30 50 70 20 30 50 70
115 350S162 16 33 33 43 43 33 33 43 43 43 43 43 43
115 350S162 24 43 43 54 54 43 43 54 54 54 54 54 54
115 550S162 16 33 33 33 43 33 33 33 43 33 33 33 43
115 550S162 24 43 43 43 54 43 43 43 54 43 43 43 54
120 350S162 16 33 33 43 43 33 33 43 43 43 43 43 43
120 350S162 24 43 43 54 54 43 43 54 54 54 54 54 54
120 550S162 16 33 33 33 43 33 33 33 43 33 33 33 43
120 550S162 24 43 43 43 54 43 43 43 54 43 43 43 54
130 115 350S162 16 33 33 43 43 43 43 43 43 43 43 43 54
130 115 350S162 24 43 54 54 54 54 54 54 54 54 54 54 68
130 115 550S162 16 33 33 33 43 33 33 33 43 33 33 33 43
130 115 550S162 24 43 43 43 54 43 43 43 54 43 43 43 54
< 140 120 350S162 16 43 43 43 43 43 43 43 43 43 43 54 54
< 140 120 350S162 24 54 54 54 54 54 54 54 54 54 54 54 68
< 140 120 550S162 16 33 33 33 43 33 33 33 43 33 33 33 43
< 140 120 550S162 24 43 43 43 54 43 43 43 54 43 43 43 54
130 350S162 16 43 43 43 43 43 43 43 43 54 54 54 54
130 350S162 24 54 54 54 54 54 54 54 54 54 54 54 68
130 550S162 16 33 33 33 43 33 33 33 43 33 33 33 43
130 550S162 24 43 43 43 54 43 43 43 54 43 43 43 54
< 140 350S162 16 43 43 43 54 43 43 54 54 54 54 54 54
< 140 350S162 24 54 54 54 54 54 54 54 54 54 54 54 68
< 140 550S162 16 33 33 33 43 33 33 33 43 33 33 43 43
< 140 550S162 24 43 43 43 54 43 43 43 54 43 43 54 54

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criterion:L/240.
b. Design load assumptions:
Second-floor dead load is 10 psf.
Second-floor live load is 30 psf.
Roof/ceiling dead load is 12 psf.
Attic live load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the wall studs.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.3.2(11)—40-FOOT-WIDE BUILDING SUPPORTING ONE FLOOR, ROOF AND CEILINGa, b, c, d

ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
8-foot studs 8-foot studs 8-foot studs 8-foot studs 9-foot studs 9-foot studs 9-foot studs 9-foot studs 10-foot studs 10-foot studs 10-foot studs 10-foot studs
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Exp. B Exp. C Exp. C Exp. C 20 ** 30** 50 70 20 30 50 70 20 30 50 70
115 350S162 16 33 33 43 43 33 33 43 43 43 43 43 54
115 350S162 24 43 43 54 54 43 43 54 54 54 54 54 68
115 550S162 16 33 33 33 43 33 33 33 43 33 33 33 43
115 550S162 24 43 43 54 54 43 43 43 54 43 43 43 54
120 350S162 16 33 33 43 43 33 33 43 43 43 43 43 54
120 350S162 24 43 43 54 54 54 54 54 54 54 54 54 68
120 550S162 16 33 33 33 43 33 33 33 43 33 33 33 43
120 550S162 24 43 43 54 54 43 43 43 54 43 43 43 54
130 115 350S162 16 43 43 43 54 43 43 43 43 43 43 54 54
130 115 350S162 24 54 54 54 54 54 54 54 54 54 54 54 68
130 115 550S162 16 33 33 43 43 33 33 33 43 33 33 43 43
130 115 550S162 24 43 43 54 54 43 43 43 54 43 43 54 54
< 140 120 350S162 16 43 43 43 54 43 43 43 54 43 43 54 54
< 140 120 350S162 24 54 54 54 54 54 54 54 54 54 54 54 68
< 140 120 550S162 16 33 33 43 43 33 33 33 43 33 33 43 43
< 140 120 550S162 24 43 43 54 54 43 43 43 54 43 43 54 54
130 350S162 16 43 43 43 54 43 43 43 54 54 54 54 54
130 350S162 24 54 54 54 68 54 54 54 54 54 54 68 68
130 550S162 16 33 33 43 43 33 33 33 43 33 33 43 43
130 550S162 24 43 43 54 54 43 43 43 54 43 43 54 54
< 140 350S162 16 43 43 43 54 43 43 54 54 54 54 54 54
< 140 350S162 24 54 54 54 68 54 54 54 68 54 54 68 68
< 140 550S162 16 33 33 43 43 33 33 43 43 33 43 43 43
< 140 550S162 24 43 43 54 54 43 43 43 54 43 43 54 54

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criterion:L/240.
b. Design load assumptions:
Second-floor dead load is 10 psf.
Second-floor live load is 30 psf.
Roof/ceiling dead load is 12 psf.
Attic live load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the wall studs.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

6-68 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.3.2(12)—24-FOOT-WIDE BUILDING SUPPORTING TWO FLOORS, ROOF AND CEILINGa, b, c, d

ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
8-foot studs 8-foot studs 8-foot studs 8-foot studs 9-foot studs 9-foot studs 9-foot studs 9-foot studs 10-foot studs 10-foot studs 10-foot studs 10-foot studs
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Exp. B Exp. C Exp. C Exp. C 20 30 50 70 20 30 50 70 20 30 50 70
115 350S162 16 43 43 43 43 33 33 33 43 43 43 43 43
115 350S162 24 54 54 54 54 54 54 54 54 54 54 54 54
115 550S162 16 33 33 43 43 33 33 33 33 33 33 33 43
115 550S162 24 43 43 54 54 43 43 43 43 43 43 43 54
120 350S162 16 43 43 43 43 33 33 43 43 43 43 43 43
120 350S162 24 54 54 54 54 54 54 54 54 54 54 54 54
120 550S162 16 33 33 43 43 33 33 33 33 33 33 33 43
120 550S162 24 43 43 54 54 43 43 43 43 43 43 43 54
130 115 350S162 16 43 43 43 43 43 43 43 43 43 43 43 54
130 115 350S162 24 54 54 54 54 54 54 54 54 54 54 54 54
130 115 550S162 16 33 33 43 43 33 33 33 33 33 33 33 43
130 115 550S162 24 43 43 54 54 43 43 43 43 43 43 43 54
< 140 120 350S162 16 43 43 43 43 43 43 43 43 43 43 54 54
< 140 120 350S162 24 54 54 54 54 54 54 54 54 54 54 54 54
< 140 120 550S162 16 33 33 43 43 33 33 33 33 33 33 33 43
< 140 120 550S162 24 43 43 54 54 43 43 43 43 43 43 43 54
130 350S162 16 43 43 43 43 43 43 43 43 54 54 54 54
130 350S162 24 54 54 54 54 54 54 54 54 54 54 68 68
130 550S162 16 33 33 43 43 33 33 33 33 33 33 33 43
130 550S162 24 43 43 54 54 43 43 43 43 43 43 43 54
< 140 350S162 16 43 43 43 43 43 43 54 54 54 54 54 54
< 140 350S162 24 54 54 54 54 54 54 54 54 54 54 68 68
< 140 550S162 16 33 33 43 43 33 33 33 33 33 33 43 43
< 140 550S162 24 43 43 54 54 43 43 43 43 54 54 54 54

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criterion:L/240.
b. Design load assumptions:
Top- and middle-floor dead load is 10 psf.
Top-floor live load is 30 psf.
Middle-floor live load is 40 psf.
Roof/ceiling dead load is 12 psf.
Attic live load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the wall studs.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.3.2(13)—28-FOOT-WIDE BUILDING SUPPORTING TWO FLOORS, ROOF AND CEILINGa, b, c, d

ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
8-foot studs 8-foot studs 8-foot studs 8-foot studs 9-foot studs 9-foot studs 9-foot studs 9-foot studs 10-foot studs 10-foot studs 10-foot studs 10-foot studs
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Exp. B Exp. C Exp. C Exp. C 20 30 50 70 20 30 50 70 20 30 ** 50** 70
115 350S162 16 43 43 43 43 43 43 43 43 43 43 43 43
115 350S162 24 54 54 54 54 54 54 54 54 54 54 54 54
115 550S162 16 43 43 43 43 43 43 43 43 43 43 43 43
115 550S162 24 54 54 54 54 54 54 54 54 54 54 54 54
120 350S162 16 43 43 43 43 43 43 43 43 43 43 43 43
120 350S162 24 54 54 54 54 54 54 54 54 54 54 54 54
120 550S162 16 43 43 43 43 43 43 43 43 43 43 43 43
120 550S162 24 54 54 54 54 54 54 54 54 54 54 54 54
130 115 350S162 16 43 43 43 43 43 43 43 43 43 43 54 54
130 115 350S162 24 54 54 54 54 54 54 54 54 54 54 54 68
130 115 550S162 16 43 43 43 43 43 43 43 43 43 43 43 43
130 115 550S162 24 54 54 54 54 54 54 54 54 54 54 54 54
< 140 120 350S162 16 43 43 43 43 43 43 43 43 54 54 54 54
< 140 120 350S162 24 54 54 54 54 54 54 54 54 54 54 68 68
< 140 120 550S162 16 43 43 43 43 43 43 43 43 43 43 43 43
< 140 120 550S162 24 54 54 54 54 54 54 54 54 54 54 54 54
130 350S162 16 43 43 43 43 43 43 43 54 54 54 54 54
130 350S162 24 54 54 54 54 54 54 54 54 68 68 68 68
130 550S162 16 43 43 43 43 43 43 43 43 43 43 43 43
130 550S162 24 54 54 54 54 54 54 54 54 54 54 54 54
< 140 350S162 16 43 43 43 54 54 54 54 54 54 54 54 54
< 140 350S162 24 54 54 54 54 54 54 54 68 68 68 68 68
< 140 550S162 16 43 43 43 43 43 43 43 43 43 43 43 43
< 140 550S162 24 54 54 54 54 54 54 54 54 54 54 54 54

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criterion:L/240.
b. Design load assumptions:
Top- and middle-floor dead load is 10 psf.
Top-floor live load is 30 psf.
Middle-floor live load is 40 psf.
Roof/ceiling dead load is 12 psf.
Attic live load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the wall studs.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

6-70 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.3.2(14)—32-FOOT-WIDE BUILDING SUPPORTING TWO FLOORS, ROOF AND CEILINGa, b, c, d

ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
8-foot studs 8-foot studs 8-foot studs 8-foot studs 9-foot studs 9-foot studs 9-foot studs 9-foot studs 10-foot studs 10-foot studs 10-foot studs 10-foot studs
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Exp. B Exp. C Exp. C Exp. C 20 30 50 70 20 30 50 70 20 30 50 70
115 350S162 16 43 43 43 54 43 43 43 43 43 43 43 54
115 350S162 24 54 54 54 68 54 54 54 54 54 54 54 68
115 550S162 16 43 43 43 43 43 43 43 43 43 43 43 43
115 550S162 24 54 54 54 54 54 54 54 54 54 54 54 54
120 350S162 16 43 43 43 54 43 43 43 43 43 43 43 54
120 350S162 24 54 54 54 68 54 54 54 54 54 54 54 68
120 550S162 16 43 43 43 43 43 43 43 43 43 43 43 43
120 550S162 24 54 54 54 54 54 54 54 54 54 54 54 54
130 115 350S162 16 43 43 43 54 43 43 43 43 54 54 54 54
130 115 350S162 24 54 54 54 68 54 54 54 54 54 68 68 68
130 115 550S162 16 43 43 43 43 43 43 43 43 43 43 43 43
130 115 550S162 24 54 54 54 54 54 54 54 54 54 54 54 54
< 140 120 350S162 16 43 43 43 54 43 43 43 54 54 54 54 54
< 140 120 350S162 24 54 54 54 68 54 54 54 54 68 68 68 68
< 140 120 550S162 16 43 43 43 43 43 43 43 43 43 43 43 43
< 140 120 550S162 24 54 54 54 54 54 54 54 54 54 54 54 54
130 350S162 16 43 43 43 54 43 54 54 54 54 54 54 54
130 350S162 24 54 54 54 68 54 54 54 68 68 68 68 68
130 550S162 16 43 43 43 43 43 43 43 43 43 43 43 43
130 550S162 24 54 54 54 54 54 54 54 54 54 54 54 54
< 140 350S162 16 43 43 54 54 54 54 54 54 54 54 54 54
< 140 350S162 24 54 54 54 68 54 68 68 68 68 68 68 68
< 140 550S162 16 43 43 43 43 43 43 43 43 43 43 43 43
< 140 550S162 24 54 54 54 54 54 54 54 54 54 54 54 54

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criterion:L/240.
b. Design load assumptions:
Top- and middle-floor dead load is 10 psf.
Top-floor live load is 30 psf.
Middle-floor live load is 40 psf.
Roof/ceiling dead load is 12 psf.
Attic live load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the wall studs.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.3.2(15)—36-FOOT-WIDE BUILDING SUPPORTING TWO FLOORS, ROOF AND CEILINGa, b, c, d

ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
8-foot studs 8-foot studs 8-foot studs 8-foot studs 9-foot studs 9-foot studs 9-foot studs 9-foot studs 10-foot studs 10-foot studs 10-foot studs 10-foot studs
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Exp. B Exp. C Exp. C Exp. C 20 30 50 70 20 30 50 70 20 30 50 70
115 350S162 16 54 54 54 54 43 43 43 54 54 54 54 54
115 350S162 24 68 68 68 68 54 54 54 68 68 68 68 68
115 550S162 16 43 43 43 54 43 43 43 43 43 43 43 43
115 550S162 24 54 54 54 54 54 54 54 54 54 54 54 54
120 350S162 16 54 54 54 54 43 43 43 54 54 54 54 54
120 350S162 24 68 68 68 68 54 54 54 68 68 68 68 68
120 550S162 16 43 43 43 54 43 43 43 43 43 43 43 43
120 550S162 24 54 54 54 54 54 54 54 54 54 54 54 54
130 115 350S162 16 54 54 54 54 43 43 43 54 54 54 54 54
130 115 350S162 24 68 68 68 68 54 54 54 68 68 68 68 68
130 115 550S162 16 43 43 43 54 43 43 43 43 43 43 43 43
130 115 550S162 24 54 54 54 54 54 54 54 54 54 54 54 54
< 140 120 350S162 16 54 54 54 54 43 43 54 54 54 54 54 54
< 140 120 350S162 24 68 68 68 68 54 54 54 68 68 68 68 68
< 140 120 550S162 16 43 43 43 54 43 43 43 43 43 43 43 43
< 140 120 550S162 24 54 54 54 54 54 54 54 54 54 54 54 54
130 350S162 16 54 54 54 54 54 54 54 54 54 54 54 54
130 350S162 24 68 68 68 68 54 54 68 68 68 68 68 68
130 550S162 16 43 43 43 54 43 43 43 43 43 43 43 43
130 550S162 24 54 54 54 54 54 54 54 54 54 54 54 54
< 140 350S162 16 54 54 54 54 54 54 54 54 54 54 54 54
< 140 350S162 24 68 68 68 68 68 68 68 68 68 68 68 68
< 140 550S162 16 43 43 43 54 43 43 43 43 43 43 43 43
< 140 550S162 24 54 54 54 54 54 54 54 54 54 54 54 54

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criterion:L/240.
b. Design load assumptions:
Top- and middle-floor dead load is 10 psf.
Top-floor live load is 30 psf.
Middle-floor live load is 40 psf.
Roof/ceiling dead load is 12 psf.
Attic live load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the wall studs.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

6-72 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.3.2(16)—40-FOOT-WIDE BUILDING SUPPORTING TWO FLOORS, ROOF AND CEILINGa, b, c, d

ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
8-foot studs 8-foot studs 8-foot studs 8-foot studs 9-foot studs 9-foot studs 9-foot studs 9-foot studs 10-foot studs 10-foot studs 10-foot studs 10-foot studs
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD
SPACING
(inches)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Ground snow load
(psf)
Exp. B Exp. C Exp. C Exp. C 20 30 50 70 20 30 50 70 20 30 50 70
115 350S162 16 54 54 54 54 54 54 54 54 54 54 54 54
115 350S162 24 68 68 68 68 68 68 68 68 68 68 68 68
115 550S162 16 54 54 54 54 43 43 54 54 43 43 54 54
115 550S162 24 54 54 54 68 54 54 54 54 54 54 54 54
120 350S162 16 54 54 54 54 54 54 54 54 54 54 54 54
120 350S162 24 68 68 68 68 68 68 68 68 68 68 68 68
120 550S162 16 54 54 54 54 43 43 54 54 43 43 54 54
120 550S162 24 54 54 54 68 54 54 54 54 54 54 54 54
130 115 350S162 16 54 54 54 54 54 54 54 54 54 54 54 54
130 115 350S162 24 68 68 68 68 68 68 68 68 68 68 68 68
130 115 550S162 16 54 54 54 54 43 43 54 54 43 43 54 54
130 115 550S162 24 54 54 54 68 54 54 54 54 54 54 54 54
< 140 120 350S162 16 54 54 54 54 54 54 54 54 54 54 54 54
< 140 120 350S162 24 68 68 68 68 68 68 68 68 68 68 68 68
< 140 120 550S162 16 54 54 54 54 43 43 54 54 43 43 54 54
< 140 120 550S162 24 54 54 54 68 54 54 54 54 54 54 54 54
130 350S162 16 54 54 54 54 54 54 54 54 54 54 54 54
130 350S162 24 68 68 68 68 68 68 68 68 68 68 68 68
130 550S162 16 54 54 54 54 43 43 54 54 43 43 54 54
130 550S162 24 54 54 54 68 54 54 54 54 54 54 54 54
< 140 350S162 16 54 54 54 54 54 54 54 54 54 54 54 54
< 140 350S162 24 68 68 68 68 68 68 68 68 68 68 68 68
< 140 550S162 16 54 54 54 54 43 43 54 54 43 43 54 54
< 140 550S162 24 54 54 54 68 54 54 54 54 54 54 54 54

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criterion:L/240.
b. Design load assumptions:
Top- and middle-floor dead load is 10 psf.
Top-floor live load is 30 psf.
Middle-floor live load is 40 psf.
Roof/ceiling dead load is 12 psf.
Attic live load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the wall studs.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

R603.3.2.1 Gable endwalls. The size and thickness of gable endwall studs with heights less than or equal to 10 feet (3048 mm) shall be permitted in accordance with the limits set forth in Table R603.3.2.1(1). The size and thickness of gable endwall studs with heights greater than 10 feet (3048 mm) shall be determined in accordance with the limits set forth in Table R603.3.2.1(2).

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.3.2.1(1)—ALL BUILDING WIDTHS GABLE ENDWALLS 8, 9 OR 10 FEET IN HEIGHTa, b, c, d

ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
ULTIMATE WIND SPEED
AND EXPOSURE CATEGORY
(mph)
MEMBER SIZE STUD SPACING
(inches)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
Exp. B Exp. C Exp. C Exp. C 8-foot studs 9-foot studs 10-foot studs
115 350S162 16 33 33 33
115 350S162 24 33 33 33
115 550S162 16 33 33 33
115 550S162 24 33 33 33
120 350S162 16 33 33 33
120 350S162 24 33 33 43
120 550S162 16 33 33 33
120 550S162 24 33 33 33
130 115 350S162 16 33 33 33
130 115 350S162 24 33 43 43
130 115 550S162 16 33 33 33
130 115 550S162 24 33 33 33
< 140 120 350S162 16 33 33 43
< 140 120 350S162 24 33 43 54
< 140 120 550S162 16 33 33 33
< 140 120 550S162 24 33 33 33
130 350S162 16 33 33 43
130 350S162 24 43 43 54
130 550S162 16 33 33 33
130 550S162 24 33 43 43
< 140 350S162 16 33 43 43
< 140 350S162 24 43 54 54
< 140 550S162 16 33 33 33
< 140 550S162 24 43 43 43
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criterion_L_/240.
b. Design load assumptions:
Ground snow load is 70 psf.
Roof/ceiling dead load is 12 psf.
Floor dead load is 10 psf.
Floor live load is 40 psf.
Attic dead load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the wall studs.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

6-74 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.3.2.1(2)—ALL BUILDING WIDTHS GABLE ENDWALLS OVER 10 FEET IN HEIGHTa, b, c, d

ULTIMATE
WIND SPEED AND
EXPOSURE CATEGORY
(mph)
ULTIMATE
WIND SPEED AND
EXPOSURE CATEGORY
(mph)
MEMBER
SIZE
STUD
SPACING
(inches)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
MINIMUM STUD THICKNESS
(mils)
ULTIMATE
WIND SPEED AND
EXPOSURE CATEGORY
(mph)
ULTIMATE
WIND SPEED AND
EXPOSURE CATEGORY
(mph)
MEMBER
SIZE
STUD
SPACING
(inches)
Stud height,****h
(feet)
Stud height,****h
(feet)
Stud height,****h
(feet)
Stud height,****h
(feet)
Stud height,****h
(feet)
Stud height,****h
(feet)
Exp. B Exp. C Exp. C Exp. C 10 <****h ≤ 12 12 <****h ≤ 14 14 <****h ≤ 16 16 <****h ≤ 18 18 <****h ≤ 20 20 <****h ≤ 22
115 350S162 16 33 43 68 97
115 350S162 24 43 68
115 550S162 16 33 33 33 43 43 54
115 550S162 24 33 43 43 54 68 97
120 350S162 16 43 54 97
120 350S162 24 54 97
120 550S162 16 33 33 43 43 54 68
120 550S162 24 33 43 54 54 68 97
130 115 350S162 16 43 54 97
130 115 350S162 24 54 97
130 115 550S162 16 33 33 43 54 54 97
130 115 550S162 24 43 43 54 68 97 97
< 140 120 350S162 16 43 68
< 140 120 350S162 24 68
< 140 120 550S162 16 33 43 43 54 68 97
< 140 120 550S162 24 43 54 54 68 97
130 350S162 16 54 97
130 350S162 24 97
130 550S162 16 33 43 54 68 97
130 550S162 24 43 54 54 97
< 140 350S162 16 54 97
< 140 350S162 24 97
< 140 550S162 16 43 43 54 97 97
< 140 550S162 24 54 54 68

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criterion_L_/240.
b. Design load assumptions:
Ground snow load is 70 psf.
Roof/ceiling dead load is 12 psf.
Floor dead load is 10 psf.
Floor live load is 40 psf.
Attic dead load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the wall studs.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

R603.3.3 Stud bracing. The flanges of cold-formed steel studs shall be laterally braced in accordance with one of the following:

  1. Gypsum board on both sides, structural sheathing on both sides, or gypsum board on one side and structural sheathing on the other side of load-bearing walls with gypsum board installed with minimum No. 6 screws in accordance with Section R702 and structural sheathing installed in accordance with Section R603.9 and Table R603.3.2(1).
  2. Horizontal steel straps fastened in accordance with Figure R603.3.3(1) on both sides at mid-height for 8-foot (2438 mm) walls, and at one-third points for 9-foot and 10-foot (2743 mm and 3048 mm) walls. Horizontal steel straps shall be not less than 1 [1] / 2 inches in width and 33 mils in thickness (38 mm by 0.84 mm). Straps shall be attached to the flanges of studs with one No. 8 screw. In-line blocking shall be installed between studs at the termination of straps and at 12-foot (3658 mm) intervals along the strap. Straps shall be fastened to the blocking with two No. 8 screws.
  3. Sheathing on one side and strapping on the other side fastened in accordance with Figure R603.3.3(2). Sheathing shall be installed in accordance with Item 1. Steel straps shall be installed in accordance with Item 2.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

FIGURE R603.3.3(1)—STUD BRACING WITH STRAPPING ONLY

TO FORM VERTICAL

1½ ″ x 33 MIL FLAT STRIP (MINIMUM)

WALL FRAMING

@ EACH STRAP TO STUD

For SI: 1 mil = 0.0254 mm, 1 inch = 25.4 mm, 1 foot = 304.8 mm.

FIGURE R603.3.3(2)—STUD BRACING WITH STRAPPING AND SHEATHING MATERIAL

STUD/TRACK BLOCKING

WALL FRAMING

1½ ″ x 33 MIL FLAT STRAP

BEND SECTION OR CLIP FLANGE TO FORM VERTICAL

2 NO. 8 SCREWS @ STRAP TO BLOCKING

NO. 8 SCREW

@ EACH STRAP TO STUD

For SI: 1 mil = 0.0254 mm, 1 inch = 25.4 mm, 1 foot = 304.8 mm.

R603.3.4 Cutting and notching. Flanges and lips of cold-formed steel studs and headers shall not be cut or notched.

R603.3.5 Splicing. Steel studs and other structural members shall not be spliced without an approved design. Tracks shall be spliced in accordance with Figure R603.3.5.

6-76 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

FIGURE R603.3.5—TRACK SPLICE

For SI: 1 inch = 25.4 mm.

R603.4 Corner framing.

In exterior walls, corner studs and the top tracks shall be installed in accordance with Figure R603.4.

FIGURE R603.4—CORNER FRAMING

4 NO. 8 SCREWS AT LAPPED TRACK

TRACK

PLAN

ALTERNATE PLAN

For SI: 1 inch = 25.4 mm.

R603.5 Exterior wall covering.

The method of attachment of exterior wall covering materials to cold-formed steel stud wall framing shall conform to the manufacturer’s installation instructions.

R603.6 Headers.

Headers shall be installed above all wall openings in exterior walls and interior load-bearing walls. Box beam headers and back-to-back headers each shall be formed from two equal sized C-shaped members in accordance with Figures R603.6(1) and R603.6(2), respectively, and Tables R603.6(1) through R603.6(6). L-shaped headers shall be permitted to be constructed in accordance with AISI S230. Alternately, headers shall be permitted to be designed and constructed in accordance with AISI S240.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.6(1)—BOX-BEAM AND BACK-TO-BACK HEADER SPANS
(HEADERS SUPPORTING ROOF AND CEILING ONLY)a, b, d

MEMBER
DESIGNATION
GROUND SNOW LOAD
(20 psf)
GROUND SNOW LOAD
(20 psf)
GROUND SNOW LOAD
(20 psf)
GROUND SNOW LOAD
(20 psf)
GROUND SNOW LOAD
(20 psf)
GROUND SNOW LOAD
(30 psf)
GROUND SNOW LOAD
(30 psf)
GROUND SNOW LOAD
(30 psf)
GROUND SNOW LOAD
(30 psf)
GROUND SNOW LOAD
(30 psf)
MEMBER
DESIGNATION
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
MEMBER
DESIGNATION
24 28 32 36 40 24 28 32 36 40
2-350S162-33 3′-3″ 2′-8″ 2′-2″ 2′-8″ 2′-2″
2-350S162-43 4′-2″ 3′-9″ 3′-4″ 2′-11″ 2′-7″ 3′-9″ 3′-4″ 2′-11″ 2′-7″ 2′-2″
2-350S162-54 6′-2″ 5′-10″ 5′-8″ 5′-3″ 4′-10″ 5′-11″ 5′-8″ 5′-2″ 4′-10″ 4′-6″
2-350S162-68 6′-7″ 6′-3″ 6′-0″ 5′-10″ 5′-8″ 6′-4″ 6′-1″ 5′-10″ 5′-8″ 5′-6″
2-550S162-33 4′-8″ 4′-0″ 3′-6″ 3′-0″ 2′-6″ 4′-1″ 3′-6″ 3′-0″ 2′-6″
2-550S162-43 6′-0″ 5′-4″ 4′-10″ 4′-4″ 3′-11″ 5′-5″ 4′-10″ 4′-4″ 3′-10″ 3′-5″
2-550S162-54 8′-9″ 8′-5″ 8′-1″ 7′-9″ 7′-3″ 8′-6″ 8′-1″ 7′-8″ 7′-2″ 6′-8″
2-550S162-68 9′-5″ 9′-0″ 8′-8″ 8′-4″ 8′-1″ 9′-1″ 8′-8″ 8′-4″ 8′-1″ 7′-10″
2-800S162-33 4′-5″ 3′-11″ 3′-5″ 3′-1″ 2′-10″ 3′-11″ 3′-6″ 3′-1″ 2′-9″ 2′-3″
2-800S162-43 7′-3″ 6′-7″ 5′-11″ 5′-4″ 4′-10″ 6′-7″ 5′-11″ 5′-4″ 4′-9″ 4′-3″
2-800S162-54 10′-10″ 10′-2″ 9′-7″ 9′-0″ 8′-5″ 10′-2″ 9′-7″ 8′-11″ 8′-4″ 7′-9″
2-800S162-68 12′-8″ 11′-10″ 11′-2″ 10′-7″ 10′-1″ 11′-11″ 11′-2″ 10′-7″ 10′-0″ 9′-6″
2-1000S162-43 7′-10″ 6′-10″ 6′-1″ 5′-6″ 5′-0″ 6′-11″ 6′-1″ 5′-5″ 4′-11″ 4′-6″
2-1000S162-54 12′-3″ 11′-5″ 10′-9″ 10′-2″ 9′-6″ 11′-6″ 10′-9″ 10′-1″ 9′-5″ 8′-9″
2-1000S162-68 14′-5″ 13′-5″ 12′-8″ 12′-0″ 11′-6″ 13′-6″ 12′-8″ 12′-0″ 11′-5″ 10′-10″
2-1200S162-54 12′-11″ 11′-3″ 10′-0″ 9′-0″ 8′-2″ 11′-5″ 10′-0″ 9′-0″ 8′-1″ 7′-4″
2-1200S162-68 15′-11″ 14′-10″ 14′-0″ 13′-4″ 12′-8″ 15′-0″ 14′-0″ 13′-3″ 12′-7″ 11′-11″

For SI: 1 mil = 0.0254 mm, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa, 1 pound per square inch = 6.895 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criteria:L/360 for live loads,L/240 for total loads.
b. Design load assumptions:
Roof/ceiling dead load is 12 psf.
Attic dead load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the header.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

6-78 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.6(2)—BOX-BEAM AND BACK-TO-BACK HEADER SPANS
(HEADERS SUPPORTING ROOF AND CEILING ONLY)a, b, d

MEMBER
DESIGNATION
GROUND SNOW LOAD
(50 psf)
GROUND SNOW LOAD
(50 psf)
GROUND SNOW LOAD
(50 psf)
GROUND SNOW LOAD
(50 psf)
GROUND SNOW LOAD
(50 psf)
GROUND SNOW LOAD
(70 psf)
GROUND SNOW LOAD
(70 psf)
GROUND SNOW LOAD
(70 psf)
GROUND SNOW LOAD
(70 psf)
GROUND SNOW LOAD
(70 psf)
MEMBER
DESIGNATION
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
MEMBER
DESIGNATION
24 28 32 36 40 24 28 32 36 40
2-350S162-33
2-350S162-43 2′-4″
2-350S162-54 4′-8″ 4′-2″ 3′-9″ 3′-5″ 3′-1″ 3′-7″ 3′-2″ 2′-9″ 2′-5″ 2′-0″
2-350S162-68 5′-7″ 5′-2″ 4′-9″ 4′-4″ 3′-11″ 4′-7″ 4′-1″ 3′-7″ 3′-2″ 2′-10″
2-550S162-33 2′-2″
2-550S162-43 3′-8″ 3′-1″ 2′-6″ 2′-3″
2-550S162-54 6′-11″ 6′-3″ 5′-9″ 5′-3″ 4′-9″ 5′-6″ 4′-11″ 4′-5″ 3′-11″ 3′-5″
2-550S162-68 8′-0″ 7′-6″ 6′-11″ 6′-5″ 5′-11″ 6′-9″ 6′-1″ 5′-6″ 5′-0″ 4′-7″
2-800S162-33 2′-7″
2-800S162-43 4′-6″ 3′-9″ 3′-1″ 2′-5″ 2′-10″
2-800S162-54 8′-0″ 7′-3″ 6′-8″ 6′-1″ 5′-7″ 6′-5″ 5′-9″ 5′-1″ 4′-7″ 4′-0″
2-800S162-68 9′-9″ 9′-0″ 8′-3″ 7′-8″ 7′-1″ 8′-0″ 7′-3″ 6′-7″ 6′-0″ 5′-6″
2-1000S162-43 4′-8″ 4′-1″ 3′-6″ 2′-9″ 3′-3″ 2′-2″
2-1000S162-54 9′-1″ 8′-2″ 7′-3″ 6′-7″ 6′-0″ 7′-0″ 6′-2″ 5′-6″ 5′-0″ 4′-6″
2-1000S162-68 11′-1″ 10′-2″ 9′-5″ 8′-8″ 8′-1″ 9′-1″ 8′-3″ 7′-6″ 6′-10″ 6′-3″
2-1200S162-54 7′-8″ 6′-9″ 6′-1″ 5′-6″ 5′-0″ 5′-10″ 5′-1″ 4′-7″ 4′-1″ 3′-9″
2-1200S162-68 12′-3″ 11′-3″ 10′-4″ 9′-7″ 8′-11″ 10′-1″ 9′-1″ 8′-3″ 7′-6″ 6′-10″

For SI: 1 mil = 0.0254 mm, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa, 1 pound per square inch = 6.895 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criteria:L/360 for live loads,L/240 for total loads.
b. Design load assumptions:
Roof/ceiling dead load is 12 psf.
Attic dead load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the header.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.6(3)—BOX-BEAM AND BACK-TO-BACK HEADER SPANS
(HEADERS SUPPORTING ONE FLOOR, ROOF AND CEILING)a, b, d

MEMBER
DESIGNATION
GROUND SNOW LOAD
(20 psf)
GROUND SNOW LOAD
(20 psf)
GROUND SNOW LOAD
(20 psf)
GROUND SNOW LOAD
(20 psf)
GROUND SNOW LOAD
(20 psf)
GROUND SNOW LOAD
(30 psf)
GROUND SNOW LOAD
(30 psf)
GROUND SNOW LOAD
(30 psf)
GROUND SNOW LOAD
(30 psf)
GROUND SNOW LOAD
(30 psf)
MEMBER
DESIGNATION
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
MEMBER
DESIGNATION
24 28 32 36 40 24 28 32 36 40
2-350S162-33
2-350S162-43 2′-2″ 2′-1″
2-350S162-54 4′-4″ 3′-10″ 3′-5″ 3′-1″ 2′-9″ 4′-3″ 2′-9″ 3′-4″ 3′-0″ 2′-8″
2-350S162-68 5′-0″ 4′-9″ 4′-7″ 4′-2″ 3′-9″ 4′-11″ 4′-8″ 4′-6″ 4′-1″ 3′-9″
2-550S162-33
2-550S162-43 3′-5″ 2′-9″ 2′-1″ 3′-3″ 2′-7″
2-550S162-54 6′-6″ 5′-10″ 5′-3″ 4′-9″ 4′-4″ 6′-4″ 5′-9″ 5′-2″ 4′-8″ 4′-3″
2-550S162-68 7′-2″ 6′-10″ 6′-5″ 5′-11″ 5′-6″ 7′-0″ 6′-9″ 6′-4″ 5′-10″ 5′-4″
2-800S162-33 2′-1″
2-800S162-43 4′-2″ 3′-4″ 2′-7″ 4′-0″ 3′-3″ 2′-5″
2-800S162-54 7′-6″ 6′-9″ 6′-2″ 5′-7″ 5′-0″ 7′-5″ 6′-8″ 6′-0″ 5′-5″ 4′-11″
2-800S162-68 9′-3″ 8′-5″ 7′-8″ 7′-1″ 6′-6″ 9′-1″ 8′-3″ 7′-7″ 7′-0″ 6′-5″
2-1000S162-43 4′-4″ 3′-9″ 2′-11″ 4′-3″ 3′-8″ 2′-9″
2-1000S162-54 8′-6″ 7′-6″ 6′-8″ 6′-0″ 5′-5″ 8′-4″ 7′-4″ 6′-6″ 5′-10″ 5′-4″
2-1000S162-68 10′-6″ 9′-7″ 8′-9″ 8′-0″ 7′-5″ 10′-4″ 9′-5″ 8′-7″ 7′-11″ 7′-3″
2-1200S162-54 7′-1″ 6′-2″ 5′-6″ 5′-0″ 4′-6″ 6′-11″ 6′-1″ 5′-5″ 4′-10″ 4′-5″
2-1200S162-68 11′-7″ 10′-7″ 9′-8″ 8′-11″ 8′-2″ 11′-5″ 10′-5″ 9′-6″ 8′-9″ 8′-0″

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa, 1 pound per square inch = 6.895 kPa.
a. Deflection criteria:L/360 for live loads,L/240 for total loads.
b. Design load assumptions:
Second-floor dead load is 10 psf.
Roof/ceiling dead load is 12 psf.
Second-floor live load is 30 psf.
Attic dead load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the header.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

6-80 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.6(4)—BOX-BEAM AND BACK-TO-BACK HEADER SPANS
(HEADERS SUPPORTING ONE FLOOR, ROOF AND CEILING)a, b, d

MEMBER
DESIGNATION
GROUND SNOW LOAD
(50 psf)
GROUND SNOW LOAD
(50 psf)
GROUND SNOW LOAD
(50 psf)
GROUND SNOW LOAD
(50 psf)
GROUND SNOW LOAD
(50 psf)
GROUND SNOW LOAD
(70 psf)
GROUND SNOW LOAD
(70 psf)
GROUND SNOW LOAD
(70 psf)
GROUND SNOW LOAD
(70 psf)
GROUND SNOW LOAD
(70 psf)
MEMBER
DESIGNATION
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
MEMBER
DESIGNATION
24 28 32 36 40 24 28 32 36 40
2-350S162-33
2-350S162-43
2-350S162-54 3′-5″ 3′-0″ 2′-7″ 2′-2″ 2′-8″ 2′-2″
2-350S162-68 4′-6″ 4′-1″ 3′-8″ 3′-3″ 2′-11″ 3′-9″ 3′-3″ 2′-10″ 2′-5″ 2′-1″
2-550S162-33
2-550S162-43 2′-0″
2-550S162-54 5′-3″ 3′-8″ 4′-1″ 3′-8″ 3′-2″ 4′-3″ 3′-8″ 3′-1″ 2′-7″ 2′-0″
2-550S162-68 6′-5″ 5′-10″ 5′-3″ 4′-9″ 4′-4″ 5′-5″ 4′-9″ 4′-3″ 3′-9″ 3′-4″
2-800S162-33
2-800S162-43 2′-6″
2-800S162-54 6′-1″ 5′-5″ 4′-10″ 4′-3″ 3′-9″ 4′-11″ 4′-3″ 3′-8″ 3′-0″ 2′-5″
2-800S162-68 7′-8″ 6′-11″ 6′-3″ 5′-9″ 5′-2″ 6′-5″ 5′-9″ 5′-1″ 4′-6″ 4′-0″
2-1000S162-43 2′-10″
2-1000S162-54 6′-7″ 5′-10″ 5′-3″ 4′-9″ 4′-3″ 5′-4″ 4′-9″ 4′-1″ 3′-5″ 2′-9″
2-1000S162-68 8′-8″ 7′-10″ 7′-2″ 6′-6″ 5′-11″ 7′-4″ 6′-6″ 5′-9″ 5′-1″ 4′-6″
2-1200S162-54 5′-6″ 4′-10″ 4′-4″ 3′-11″ 3′-7″ 4′-5″ 3′-11″ 3′-6″ 3′-2″ 2′-11″
2-1200S162-68 9′-7″ 8′-8″ 7′-11″ 7′-2″ 6′-6″ 8′-1″ 7′-2″ 6′-4″ 5′-8″ 5′-0″

For SI: 1 mil = 0.0254 mm, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa, 1 pound per square inch = 6.895 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criteria:L/360 for live loads,L/240 for total loads.
b. Design load assumptions:
Second-floor dead load is 10 psf.
Roof/ceiling dead load is 12 psf.
Second-floor live load is 30 psf.
Attic dead load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the header.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.6(5)—BOX-BEAM AND BACK-TO-BACK HEADER SPANS
(HEADERS SUPPORTING TWO FLOORS, ROOF AND CEILING)a, b, d

MEMBER
DESIGNATION
GROUND SNOW LOAD
(20 psf)
GROUND SNOW LOAD
(20 psf)
GROUND SNOW LOAD
(20 psf)
GROUND SNOW LOAD
(20 psf)
GROUND SNOW LOAD
(20 psf)
GROUND SNOW LOAD
(30 psf)
GROUND SNOW LOAD
(30 psf)
GROUND SNOW LOAD
(30 psf)
GROUND SNOW LOAD
(30 psf)
GROUND SNOW LOAD
(30 psf)
MEMBER
DESIGNATION
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
MEMBER
DESIGNATION
24 28 32 36 40 24 28 32 36 40
2-350S162-33
2-350S162-43
2-350S162-54 2′-5″ 2′-4″
2-350S162-68 3′-6″ 3′-0″ 2′-6″ 2′-1″ 3′-5″ 2′-11″ 2′-6″ 2′-0″
2-550S162-33
2-550S162-43
2-550S162-54 3′-11″ 3′-3″ 2′-8″ 2′-0″ 3′-10″ 3′-3″ 2′-7″
2-550S162-68 5′-1″ 4′-5″ 3′-10″ 3′-3″ 2′-9″ 5′-0″ 4′-4″ 3′-9″ 3′-3″ 2′-9″
2-800S162-33
2-800S162-43
2-800S162-54 4′-7″ 3′-10″ 3′-1″ 2′-5″ 4′-6″ 3′-9″ 3′-0″ 2′-4″
2-800S162-68 6′-0″ 5′-3″ 4′-7″ 3′-11″ 3′-4″ 6′-0″ 5′-2″ 4′-6″ 3′-11″ 3′-3″
2-1000S162-43
2-1000S162-54 5′-0″ 4′-4″ 3′-6″ 2′-9″ 4′-11″ 4′-3″ 3′-5″ 2′-7″
2-1000S162-68 6′-10″ 6′-0″ 5′-3″ 4′-6″ 3′-10″ 6′-9″ 5′-11″ 5′-2″ 4′-5″ 3′-9″
2-1200S162-54 4′-2″ 3′-7″ 3′-3″ 2′-11″ 4′-1″ 3′-7″ 3′-2″ 2′-10″
2-1200S162-68 7′-7″ 6′-7″ 5′-9″ 5′-0″ 4′-2″ 7′-6″ 6′-6″ 5′-8″ 4′-10″ 4′-1″

For SI: 1 mil = 0.0254 mm, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa, 1 pound per square inch = 6.895 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criteria:L/360 for live loads,L/240 for total loads.
b. Design load assumptions:
Second-floor dead load is 10 psf.
Roof/ceiling dead load is 12 psf.
Second-floor live load is 40 psf.
Third floor live load is 30 psf.
Attic live load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the header.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

6-82 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.6(6)—BOX-BEAM AND BACK-TO-BACK HEADER SPANS
(HEADERS SUPPORTING TWO FLOORS, ROOF AND CEILING)a, b, d

MEMBER
DESIGNATION
GROUND SNOW LOAD
(50 psf)
GROUND SNOW LOAD
(50 psf)
GROUND SNOW LOAD
(50 psf)
GROUND SNOW LOAD
(50 psf)
GROUND SNOW LOAD
(50 psf)
GROUND SNOW LOAD
(70 psf)
GROUND SNOW LOAD
(70 psf)
GROUND SNOW LOAD
(70 psf)
GROUND SNOW LOAD
(70 psf)
GROUND SNOW LOAD
(70 psf)
MEMBER
DESIGNATION
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
Building widthc
(feet)
MEMBER
DESIGNATION
24 28 32 36 40 24 28 32 36 40
2-350S162-33
2-350S162-43
2-350S162-54 2′-2″
2-350S162-68 3′-3″ 2′-9″ 2′-3″ 2′-11″ 2′-5″
2-550S162-33
2-550S162-43
2-550S162-54 3′-7″ 2′-11″ 2′-3″ 3′-3″ 2′-7″
2-550S162-68 4′-9″ 2′-1″ 3′-6″ 3′-0″ 2′-5″ 4′-4″ 3′-9″ 3′-2″ 2′-8″ 2′-1″
2-800S162-33
2-800S162-43
2-800S162-54 4′-3″ 3′-5″ 2′-8″ 3′-9″ 3′-0″ 2′-3″
2-800S162-68 5′-8″ 4′-11″ 4′-2″ 3′-7″ 2′-11″ 5′-3″ 4′-6″ 3′-10″ 3′-3″ 2′-7″
2-1000S162-43
2-1000S162-54 4′-8″ 3′-11″ 3′-1″ 2′-2″ 4′-3″ 3′-5″ 2′-7″
2-1000S162-68 6′-5″ 5′-7″ 4′-9″ 4′-1″ 3′-4″ 5′-11″ 5′-1″ 4′-5″ 3′-8″ 2′-11″
2-1200S162-54 3′-11″ 3′-5″ 3′-0″ 2′-4″ 3′-7″ 3′-2″ 2′-10″
2-1200S162-68 7′-1″ 6′-2″ 5′-3″ 4′-6″ 3′-8″ 6′-6″ 5′-8″ 4′-10″ 4′-0″ 3′-3″

For SI: 1 mil = 0.0254 mm, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa, 1 pound per square inch = 6.895 kPa, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection criteria:L/360 for live loads,L/240 for total loads.
b. Design load assumptions:
Second-floor dead load is 10 psf.
Roof/ceiling dead load is 12 psf.
Second-floor live load is 40 psf.
Third floor live load is 30 psf.
Attic live load is 10 psf.
c. Building width is in the direction of horizontal framing members supported by the header.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TRACK

TRACK

TRACK

TRACK OR C-SHAPE ATTACH WITH NO. 8 SCREWS (MINIMUM DEPTH = HEADER DEPTH MINUS ½ INCH)

KING STUD(S)

JACK STUD(S)

NO. 8 SCREWS THROUGH SHEATHING TO EACH JACK AND KING STUD

AT 12 ON CENTER ˝

STRUCTURAL SHEATHING

FIGURE R603.6(1)—BOX BEAM HEADER

For SI: 1 inch = 25.4 mm.

FIGURE R603.6(2)—BACK-TO-BACK HEADER

2-NO. 8 SCREWS

AT 24 ON CENTER ˝ (2 SCREWS THROUGH TOP FLANGES AND 2 SCREWS THROUGH BOTTOM FLANGES)

BACK-T0-BACK C-SHAPES

2-NO. 8 SCREWS

AT 24 ON CENTER ˝

CRIPPLE STUD

STRUCTURAL SHEATHING

TRACK

2 ˝ x 2 ˝ CLIP ANGLE ATTACHED

WITH NO. 8 SCREWS, MINIMUM LENGTH = WEB DEPTH MINUS ½ INCH

TRACK

JACK STUDS (AS REQUIRED)

KING STUDS (AS REQUIRED)

NO. 8 SCREWS THROUGH SHEATHING TO EACH JACK

& KING STUD AT 12 ON CENTER ˝

For SI: 1 inch = 25.4 mm.

R603.6.1 Headers in gable endwalls. Box beam and back-to-back headers in gable endwalls shall be permitted to be constructed in accordance with Section R603.6 or with the header directly above the opening in accordance with Figures R603.6.1(1) and R603.6.1(2) and the following provisions:

  1. Two 362S162-33 for openings less than or equal to 4 feet (1219 mm).
  2. Two 600S162-43 for openings greater than 4 feet (1219 mm) but less than or equal to 6 feet (1829 mm).
  3. Two 800S162-54 for openings greater than 6 feet (1829 mm) but less than or equal to 9 feet (2743 mm).

6-84 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

CRIPPLE STUD

HEAD TRACK

C-SHAPES

CRIPPLE STUD

HEAD TRACK

C-SHAPES

KING STUD(S)

TRACK OR C-SHAPE

JACK STUD(S)

KING STUD(S)

2 IN. x 2 IN. CLIP ANGLE

JACK STUD(S)

For SI: 1 inch = 25.4 mm.

FIGURE R603.6.1(1)—BOX BEAM HEADER IN GABLE ENDWALL

FIGURE R603.6.1(2)—BACK-TO-BACK HEADER IN GABLE ENDWALL

R603.7 Jack and king studs.

The number of jack and king studs installed on each side of a header shall comply with Table R603.7(1). King, jack and cripple studs shall be of the same dimension and thickness as the adjacent wall studs. Headers shall be connected to king studs in accordance with Table R603.7(2) and the following provisions:

  1. For box beam headers, one-half of the total number of required screws shall be applied to the header and one- half to the king stud by use of C-shaped or track member in accordance with Figure R603.6(1). The track or C-shaped sections shall extend the depth of the header minus [1] / 2 inch (12.7 mm) and shall have a minimum thickness not less than that of the wall studs.

  2. For back-to-back headers, one-half the total number of screws shall be applied to the header and one-half to the king stud by use of a minimum 2-inch by 2-inch (51 mm by 51 mm) clip angle in accordance with Figure R603.6(2). The clip angle shall extend the depth of the header minus [1] / 2 inch (12.7 mm) and shall have a minimum thickness not less than that of the wall studs. Jack and king studs shall be interconnected with structural sheathing in accordance with Figures R603.6(1) and R603.6(2).

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.7(1)—TOTAL NUMBER OF JACK AND KING STUDS REQUIRED AT EACH END OF AN OPENING

** SIZE OF OPENING**
(feet-inches)
** 24-INCH O.C. STUD SPACING** ** 24-INCH O.C. STUD SPACING** ** 16-INCH O.C. STUD SPACING** ** 16-INCH O.C. STUD SPACING**
** SIZE OF OPENING**
(feet-inches)
** No. of jack studs** ** No. of king studs** ** No. of jack studs** ** No. of king studs**
Up to 3′-6″ 1 1 1 1
> 3′-6″ to 5′-0″ 1 2 1 2
> 5′-0″ to 5′-6″ 1 2 2 2
> 5′-6″ to 8′-0″ 1 2 2 2
> 8′-0″ to 10′-6″ 2 2 2 3
> 10′-6″ to 12′-0″ 2 2 3 3
> 12′-0″ to 13′-0″ 2 3 3 3
> 13′-0″ to 14′-0″ 2 3 3 4
> 14′-0″ to 16′-0″ 2 3 3 4
> 16′-0″ to 18′-0″ 3 3 4 4
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

TABLE R603.7(2)—HEADER TO KING STUD CONNECTION REQUIREMENTSa, b, c, d

** HEADER SPAN**
(feet)
** ULTIMATE WIND SPEED (mph), EXPOSURE CATEGORY** ** ULTIMATE WIND SPEED (mph), EXPOSURE CATEGORY** ** ULTIMATE WIND SPEED (mph), EXPOSURE CATEGORY** ** ULTIMATE WIND SPEED (mph), EXPOSURE CATEGORY** ** ULTIMATE WIND SPEED (mph), EXPOSURE CATEGORY** ** ULTIMATE WIND SPEED (mph), EXPOSURE CATEGORY**
** HEADER SPAN**
(feet)
** 115 B** ** 120 B** ** 130 B** ** < 140 B** ** 130 C** ** <140 C**
** HEADER SPAN**
(feet)
** 115 B** ** 120 B** ** 115 C** ** 120 C** ** 120 C** ** 120 C**
≤ 4 4-No. 8 screws 4-No. 8 screws 4-No. 8 screws 4-No. 8 screws 6-No. 8 screws 6-No. 8 screws
> 4 to 8 4-No. 8 screws 4-No. 8 screws 4-No. 8 screws 6-No. 8 screws 8-No. 8 screws 8-No. 8 screws
> 8 to 12 4-No. 8 screws 6-No. 8 screws 6-No. 8 screws 8-No. 8 screws 10-No. 8 screws 12-No. 8 screws
> 12 to 16 4-No. 8 screws 6-No. 8 screws 8-No. 8 screws 10-No. 8 screws 12-No. 8 screws 14-No. 8 screws

For SI: 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s, 1 pound = 4.448 N.
a. All screw sizes shown are minimum.
b. For headers located on the first floor of a two-story building or the first or second floor of a three-story building, the total number of screws is permitted to be reduced by 2
screws, but the total number of screws shall be not less than four.
c. For roof slopes of 6:12 or greater, the required number of screws shall be permitted to be reduced by half, but the total number of screws shall be not less than four.
d. Screws can be replaced by an uplift connector that has a capacity of the number of screws multiplied by 164 pounds.

R603.8 Head and sill track.

Head track spans above door and window openings and sill track spans beneath window openings shall comply with Table R603.8. For openings less than 4 feet (1219 mm) in height that have both a head track and a sill track, multiplying the spans by 1.75 shall be permitted in Table R603.8. For openings less than or equal to 6 feet (1829 mm) in height that have both a head track and a sill track, multiplying the spans in Table R603.8 by 1.50 shall be permitted.

TABLE R603.8—HEAD AND SILL TRACK SPAN

** ULTIMATE WIND SPEED**
** AND EXPOSURE CATEGORY**
(mph)
** ULTIMATE WIND SPEED**
** AND EXPOSURE CATEGORY**
(mph)
** ALLOWABLE HEAD AND SILL TRACK SPANa, b, c
(feet-inches)**
** ALLOWABLE HEAD AND SILL TRACK SPANa, b, c
(feet-inches)**
** ALLOWABLE HEAD AND SILL TRACK SPANa, b, c
(feet-inches)**
** ALLOWABLE HEAD AND SILL TRACK SPANa, b, c
(feet-inches)**
** ALLOWABLE HEAD AND SILL TRACK SPANa, b, c
(feet-inches)**
** ALLOWABLE HEAD AND SILL TRACK SPANa, b, c
(feet-inches)**
** ULTIMATE WIND SPEED**
** AND EXPOSURE CATEGORY**
(mph)
** ULTIMATE WIND SPEED**
** AND EXPOSURE CATEGORY**
(mph)
** Track designationd** ** Track designationd** ** Track designationd** ** Track designationd** ** Track designationd** ** Track designationd**
** B** ** C** ** 350T125-33** ** 350T125-43** ** 350T125-54** ** 550T125-33** ** 550T125-43** ** 550T125-54**
115 5′-9″ 6′-9″ 9′-3″ 7′-3″ 9′-1″ 12′-5″
120 5′-6″ 6′-6″ 8′-11″ 7′-0″ 8′-9″ 11′-11″
130 115 4′-10″ 5′-9″ 7′-10″ 6′-2″ 7′-8″ 10′-6″
< 140 120 4′-8″ 5′-6″ 7′-6″ 5′-11″ 7′-4″ 10′-1″
130 4′-3″ 5′-1″ 6′-11″ 5′-6″ 6′-9″ 9′-4″
< 140 4′-0″ 4′-9″ 6′-5″ 5′-1″ 6′-4″ 8′-8″

For SI: 1 mil = 0.0254 mm, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s, 1 ksi = 1,000 psi = 6.895 MPa.
a. Deflection limit:L/240.
b. Head and sill track spans are based on components and cladding wind pressures and 48-inch tributary span.
c. For openings less than 4 feet in height that have both a head track and sill track, the spans are permitted to be multiplied by 1.75. For openings less than or equal to 6 feet in
height that have both a head track and a sill track, the spans are permitted to be multiplied by a factor of 1.5.
d. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.

6-86 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

R603.9 Structural sheathing.

Structural sheathing shall be installed in accordance with Figure R603.9 and this section on all sheathable exterior wall surfaces, including areas above and below openings.

FIGURE R603.9—STRUCTURAL SHEATHING FASTENING PATTERN

STRUCTURAL SHEATHING

R603.9.1 Sheathing materials. Structural sheathing panels shall consist of minimum [7] / 16 -inch-thick (11 mm) oriented strand board or [15] / 32 -inch-thick (12 mm) plywood.

R603.9.2 Determination of minimum length of full-height sheathing. The minimum length of full-height sheathing on each braced wall line shall be determined by multiplying the length of the braced wall line by the percentage obtained from Table R603.9.2(1) and by the plan aspect-ratio adjustment factors obtained from Table R603.9.2(2). The minimum length of full-height sheathing shall be not less than 20 percent of the braced wall line length.

To be considered full-height sheathing, structural sheathing shall extend from the bottom to the top of the wall without interruption by openings. Only sheathed, full-height wall sections, uninterrupted by openings, which are not less than 48 inches (1219 mm) wide, shall be counted toward meeting the minimum percentages in Table R603.9.2(1). In addition, structural sheathing shall comply with all of the following requirements:

  1. Be installed with the long dimension parallel to the stud framing and shall cover the full vertical height of wall from the bottom of the bottom track to the top of the top track of each story. Installing the long dimension perpendicular to the stud framing or using shorter segments shall be permitted provided that the horizontal joint is blocked as described in Item 2.

  2. Be blocked where the long dimension is installed perpendicular to the stud framing. Blocking shall be not less than 33 mil (0.84 mm) thickness. Each horizontal structural sheathing panel shall be fastened with No. 8 screws spaced at 6 inches (152 mm) on center to the blocking at the joint.

  3. Be applied to each end (corners) of each of the exterior walls with a minimum 48-inch-wide (1219 mm) panel.

Exception: Where stone or masonry veneer is installed, the required length of full-height sheathing and overturning anchorage required shall be determined in accordance with Section R603.9.5.

TABLE R603.9.2(1)—MINIMUM PERCENTAGE OF FULL-HEIGHT STRUCTURAL SHEATHING ON EXTERIOR WALLSa, b

** WALL SUPPORTING** ** ROOF SLOPE** ** ULTIMATE WIND SPEED AND EXPOSURE**
(mph)
** ULTIMATE WIND SPEED AND EXPOSURE**
(mph)
** ULTIMATE WIND SPEED AND EXPOSURE**
(mph)
** ULTIMATE WIND SPEED AND EXPOSURE**
(mph)
** ULTIMATE WIND SPEED AND EXPOSURE**
(mph)
** ULTIMATE WIND SPEED AND EXPOSURE**
(mph)
** WALL SUPPORTING** ** ROOF SLOPE** ** 115 B** ** 120 B** ** 130 B** ** < 140 B** ** < 130 C** ** < 140 C**
** WALL SUPPORTING** ** ROOF SLOPE** ** 115 B** ** 120 B** ** 115 C** ** 120 C** ** 120 C** ** 120 C**
Roof and ceiling only
(one story or top floor of two- or three-story building)
3:12 9 11 11 13 17 20
Roof and ceiling only
(one story or top floor of two- or three-story building)
6:12 13 15 17 22 28 35
Roof and ceiling only
(one story or top floor of two- or three-story building)
9:12 23 27 29 33 53 59
Roof and ceiling only
(one story or top floor of two- or three-story building)
12:12 32 39 40 44 70 76
One story, roof and ceiling
(first floor of a two-story building or second floor of a
three-story building)
3:12 26 32 34 39 53 67
One story, roof and ceiling
(first floor of a two-story building or second floor of a
three-story building)
6:12 27 33 34 44 61 75
One story, roof and ceiling
(first floor of a two-story building or second floor of a
three-story building)
9:12 38 45 46 61 78 92
One story, roof and ceiling
(first floor of a two-story building or second floor of a
three-story building)
12:12 43 53 57 72 106 116

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.9.2(1)—MINIMUM PERCENTAGE OF FULL-HEIGHT STRUCTURAL SHEATHING ON EXTERIOR WALLSa, b—continued

** WALL SUPPORTING** ** ROOF SLOPE** ** ULTIMATE WIND SPEED AND EXPOSURE**
(mph)
** ULTIMATE WIND SPEED AND EXPOSURE**
(mph)
** ULTIMATE WIND SPEED AND EXPOSURE**
(mph)
** ULTIMATE WIND SPEED AND EXPOSURE**
(mph)
** ULTIMATE WIND SPEED AND EXPOSURE**
(mph)
** ULTIMATE WIND SPEED AND EXPOSURE**
(mph)
** WALL SUPPORTING** ** ROOF SLOPE** ** 115 B** ** 120 B** ** 130 B** ** < 140 B** ** < 130 C** ** < 140 C**
** WALL SUPPORTING** ** ROOF SLOPE** ** 115 B** ** 120 B** ** 115 C** ** 120 C** ** 120 C** ** 120 C**
Two stories, roof and ceiling
(first floor of a three-story building)
3:12 43 53 57 64 89 113
Two stories, roof and ceiling
(first floor of a three-story building)
6:12 41 51 51 67 95 114
Two stories, roof and ceiling
(first floor of a three-story building)
9:12 53 63 63 89 104 126
Two stories, roof and ceiling
(first floor of a three-story building)
12:12 54 67 74 100 142 157
For SI: 1 mph = 0.447 m/s.
a. Linear interpolation is permitted.
b. For hip-roofed homes the minimum percentage of full-height sheathing, based on wind, is permitted to be multiplied by a factor of 0.95 for roof slopes not exceeding 7:12
and a factor of 0.9 for roof slopes greater than 7:12.

TABLE R603.9.2(2)—FULL-HEIGHT SHEATHING LENGTH ADJUSTMENT FACTORS

** PLAN ASPECT RATIO** ** LENGTH ADJUSTMENT FACTORS** ** LENGTH ADJUSTMENT FACTORS**
** PLAN ASPECT RATIO** ** Short wall** ** Long wall**
1:1 1.0 1.0
1.5:1 1.5 0.67
2:1 2.0 0.50
3:1 3.0 0.33
4:1 4.0 0.25

R603.9.2.1 Full-height sheathing. The minimum percentage of full-height structural sheathing shall be multiplied by 1.10 for 9-foot-high (2743 mm) walls and multiplied by 1.20 for 10-foot-high (3048 mm) walls.

R603.9.2.2 Full-height sheathing in lowest story. In the lowest story of a dwelling, multiplying the percentage of full-height sheathing required in Table R603.9.2(1) by 0.6 shall be permitted where hold-down anchors are provided in accordance with Section R603.9.4.2.

R603.9.3 Structural sheathing fastening. Edges and interior areas of structural sheathing panels shall be fastened to framing members and tracks in accordance with Figure R603.9 and Table R603.3.2(1). Screws for attachment of structural sheathing panels shall be bugle-head, flat-head, or similar head style with a minimum head diameter of 0.29 inch (8 mm).

For continuously sheathed braced wall lines using wood structural panels installed with No. 8 screws spaced 4 inches (102 mm) on center at all panel edges and 12 inches (304.8 mm) on center on intermediate framing members, the following shall apply:

  1. Multiplying the percentages of full-height sheathing in Table R603.9.2(1) by 0.72 shall be permitted.
  2. For bottom track attached to foundations or framing below, the bottom track anchor or screw connection spacing in Tables R505.3.1(1) and R603.3.1 shall be multiplied by two-thirds.

R603.9.4 Uplift connection requirements. Uplift connections shall be provided in accordance with this section.

R603.9.4.1 Ultimate design wind speeds greater than 130 mph. Where ultimate design wind speeds exceed 130 miles per hour (58 m/s), Exposure Category C walls shall be provided with direct uplift connections in accordance with AISI S230, Section E13.3, and AISI S230, Section F8.2, as required for 140 miles per hour (63 m/s), Exposure Category C.

R603.9.4.2 Hold-down anchor. Where the percentage of full-height sheathing is adjusted in accordance with Section R603.9.2.2, a hold-down anchor, with a strength of 4,300 pounds (19 kN), shall be provided at each end of each full-height sheathed wall section used to meet the minimum percent sheathing requirements of Section R603.9.2. Hold-down anchors shall be attached to back-to-back studs; structural sheathing panels shall have edge fastening to the studs, in accordance with Section R603.9.3 and AISI S230, Table E11-1.

A single hold-down anchor, installed in accordance with Figure R603.9.4.2, shall be permitted at the corners of buildings.

6-88 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

FIGURE R603.9.4.2—CORNER STUD HOLD-DOWN DETAIL

DOUBLE STUDS BACK-TO-BACK WITH

OUTSIDE STUD CAPPED WITH TRACK

NO. 8 SHEATHING ATTACHMENT SCREWS AS REQUIRED BY SECTION R603.9.3

NO. 8 SCREWS ATTACHING TRACK TO STUD AT 8 IN. O.C. EACH FLANGE

PLYWOOD, OSB OR GWB SHEATHING PER SHEARWALL REQUIREMENTS

OUTSIDE FACE

DOUBLE ROW OF NO. 8 SCREWS

-BACK WITH DOUBLE ROW OF NO. 8 SCR
WITH TRACK AT 12 IN. O.C.
HMENT HOLD DOWN AS REQUIRED
Y SECTION R603.9.4
NG
.
INSIDE FACE
WALLBOARD BACKING ST
ALL
E FACE INSIDE FACE

INSIDE FACE
INSIDE FACE
ALL
NG
.
HMENT
Y
E FACE
WALLBOARD BACKING ST
-BACK WITH
WITH TRACK
HOLD DOWN AS REQUIRED
SECTION R603.9.4
DOUBLE ROW OF NO. 8 SC
AT 12 IN. O.C.
INSIDE FACE
INSIDE FACE
ALL
NG
.
HMENT
Y
E FACE
WALLBOARD BACKING ST
-BACK WITH
WITH TRACK
HOLD DOWN AS REQUIRED
SECTION R603.9.4
DOUBLE ROW OF NO. 8 SC
AT 12 IN. O.C.
INSIDE FACE
INSIDE FACE
ALL
NG
.
HMENT
Y
E FACE
WALLBOARD BACKING ST
-BACK WITH
WITH TRACK
HOLD DOWN AS REQUIRED
SECTION R603.9.4
DOUBLE ROW OF NO. 8 SC
AT 12 IN. O.C.
INSIDE FACE
INSIDE FACE
ALL
NG
.
HMENT
Y
E FACE
WALLBOARD BACKING ST
-BACK WITH
WITH TRACK
HOLD DOWN AS REQUIRED
SECTION R603.9.4
DOUBLE ROW OF NO. 8 SC
AT 12 IN. O.C.
INSIDE FACE
INSIDE FACE
WALLBOARD BACKING ST

For SI: 1 inch = 25.4 mm.

R603.9.5 Structural sheathing for stone and masonry veneer. Where stone and masonry veneer are installed in accordance with Section R703.8, the length of full-height sheathing for exterior and interior wall lines backing or perpendicular to and laterally supporting walls with veneer shall comply with this section.

TABLE R603.9.5(1)—REQUIRED LENGTH OF FULL-HEIGHT SHEATHING AND ASSOCIATED OVERTURNING
ANCHORAGE FOR WALLS SUPPORTING WALLS WITH STONE OR MASONRY VENEER AND USING 33-MIL COLD-FORMED
STEEL FRAMING AND 6-INCH SCREW SPACING ON THE PERIMETER OF EACH PANEL OF STRUCTURAL SHEATHING

** SEISMIC**
DESIGN
CATEGORY
** STORY** ** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** SINGLE-
STORY
HOLD-
DOWN
FORCE
(pounds)**
** CUMULATIVE**
HOLD-DOWN
FORCE
(pounds)
** SEISMIC**
DESIGN
CATEGORY
** STORY** ** 10** ** 20** ** 30** ** 40** ** 50** ** 60** ** 60** ** 60**
** SEISMIC**
DESIGN
CATEGORY
** STORY** ** Minimum total length of braced wall panels required along each braced wall line**
(feet)
** Minimum total length of braced wall panels required along each braced wall line**
(feet)
** Minimum total length of braced wall panels required along each braced wall line**
(feet)
** Minimum total length of braced wall panels required along each braced wall line**
(feet)
** Minimum total length of braced wall panels required along each braced wall line**
(feet)
** Minimum total length of braced wall panels required along each braced wall line**
(feet)
** Minimum total length of braced wall panels required along each braced wall line**
(feet)
** Minimum total length of braced wall panels required along each braced wall line**
(feet)
D0 3.3 4.7 6.1 7.4 8.8 10.2 3,360
D0 5.3 8.7 12.1 15.4 18.8 22.2 3,360 6,720
D0 7.3 12.7 18.0 23.4 28.8 34.2 3,360 10,080
D1 4.1 5.8 7.5 9.2 10.9 12.7 3,360
D1 6.6 10.7 14.9 19.1 23.3 27.5 3,360 6,720
D1 9.0 15.7 22.4 29.0 35.7 42.2 3,360 10,080

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.9.5(1)—REQUIRED LENGTH OF FULL-HEIGHT SHEATHING AND ASSOCIATED OVERTURNING
ANCHORAGE FOR WALLS SUPPORTING WALLS WITH STONE OR MASONRY VENEER AND USING 33-MIL COLD-FORMED
STEEL FRAMING AND 6-INCH SCREW SPACING ON THE PERIMETER OF EACH PANEL OF STRUCTURAL SHEATHING—continued

** SEISMIC**
DESIGN
CATEGORY
** STORY** ** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** SINGLE-
STORY
HOLD-
DOWN
FORCE
(pounds)**
** CUMULATIVE**
HOLD-DOWN
FORCE
(pounds)
** SEISMIC**
DESIGN
CATEGORY
** STORY** ** 10** ** 20** ** 30** ** 40** ** 50** ** 60** ** 60** ** 60**
** SEISMIC**
DESIGN
CATEGORY
** STORY** ** Minimum total length of braced wall panels required along each braced wall line**
(feet)
** Minimum total length of braced wall panels required along each braced wall line**
(feet)
** Minimum total length of braced wall panels required along each braced wall line**
(feet)
** Minimum total length of braced wall panels required along each braced wall line**
(feet)
** Minimum total length of braced wall panels required along each braced wall line**
(feet)
** Minimum total length of braced wall panels required along each braced wall line**
(feet)
** Minimum total length of braced wall panels required along each braced wall line**
(feet)
** Minimum total length of braced wall panels required along each braced wall line**
(feet)
D2 5.7 8.2 10.6 13.0 15.4 17.8 3,360
D2 9.2 15.1 21.1 27.0 32.9 38.8 3,360 6,720
D2 12.7 22.1 31.5 40.9 50.3 59.7 3,360 10,080
For SI: 1 mil = 0.0254 mm, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound-force = 4.448 N.

TABLE R603.9.5(2)—REQUIRED LENGTH OF FULL-HEIGHT SHEATHING AND ASSOCIATED OVERTURNING
ANCHORAGE FOR WALLS SUPPORTING WALLS WITH STONE OR MASONRY VENEER AND USING 43-MIL COLD-FORMED
STEEL FRAMING AND 6-INCH SCREW SPACING ON THE PERIMETER OF EACH PANEL OF STRUCTURAL SHEATHING

** SEISMIC**
DESIGN
CATEGORY
** STORY** ** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** SINGLE-
STORY
HOLD-
DOWN
FORCE
(pounds)**

CUMULATIVE
HOLD-DOWN
FORCE
(pounds)
** SEISMIC**
DESIGN
CATEGORY
** STORY** ** 10** ** 20** ** 30** ** 40** ** 50** ** 60** ** 60** ** 60**
** SEISMIC**
DESIGN
CATEGORY
** STORY** ** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
D0 2.8 4.0 5.1 6.3 7.5 8.7 3,960
D0 4.5 7.4 10.2 13.1 16.0 18.8 3,960 7,920
D0 6.2 10.7 15.3 19.9 24.4 29.0 3,960 11,880
D1 3.5 4.9 6.4 7.8 9.3 10.7 3,960
D1 5.6 9.1 12.7 16.2 19.8 23.3 3,960 7,920
D1 7.7 13.3 19.0 24.6 30.3 35.9 3,960 11,880

6-90 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.9.5(2)—REQUIRED LENGTH OF FULL-HEIGHT SHEATHING AND ASSOCIATED OVERTURNING
ANCHORAGE FOR WALLS SUPPORTING WALLS WITH STONE OR MASONRY VENEER AND USING 43-MIL COLD-FORMED
STEEL FRAMING AND 6-INCH SCREW SPACING ON THE PERIMETER OF EACH PANEL OF STRUCTURAL SHEATHING—continued

** SEISMIC**
DESIGN
CATEGORY
** STORY** ** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** SINGLE-
STORY
HOLD-
DOWN
FORCE
(pounds)**

CUMULATIVE
HOLD-DOWN
FORCE
(pounds)
** SEISMIC**
DESIGN
CATEGORY
** STORY** ** 10** ** 20** ** 30** ** 40** ** 50** ** 60** ** 60** ** 60**
** SEISMIC**
DESIGN
CATEGORY
** STORY** ** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
D2 4.9 6.9 9.0 11.0 13.1 15.1 3,960
D2 7.8 12.9 17.9 22.9 27.9 32.9 3,960 7,920
D2 10.8 18.8 26.7 34.7 42.7 50.7 3,960 11,880
For SI: 1 mil = 0.0254 mm, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound-force = 4.448 N.

TABLE R603.9.5(3)—REQUIRED LENGTH OF FULL-HEIGHT SHEATHING AND ASSOCIATED OVERTURNING
ANCHORAGE FOR WALLS SUPPORTING WALLS WITH STONE OR MASONRY VENEER AND USING 33-MIL COLD-FORMED
STEEL FRAMING AND 4-INCH SCREW SPACING ON THE PERIMETER OF EACH PANEL OF STRUCTURAL SHEATHING

** SEISMIC**
DESIGN
CATEGORY
** STORY** ** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** SINGLE-
STORY
HOLD-
DOWN
FORCE
(pounds)**

CUMULATIVE
HOLD-DOWN
FORCE
(pounds)
** SEISMIC**
DESIGN
CATEGORY
** STORY** ** 10** ** 20** ** 30** ** 40** ** 50** ** 60** ** 60** ** 60**
** SEISMIC**
DESIGN
CATEGORY
** STORY** ** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
D0 2.5 3.6 4.6 5.7 6.8 7.8 4,392
D0 4.0 6.6 9.2 11.8 14.4 17.0 4,392 8,784
D0 5.6 9.7 13.8 17.9 22.0 26.2 4,392 13,176
D1 3.1 4.4 5.7 7.1 8.4 9.7 4,392
D1 5.0 8.2 11.4 14.6 17.8 21.0 4,392 8,784
D1 6.9 12.0 17.1 22.2 27.3 32.4 4,392 13,176

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

TABLE R603.9.5(3)—REQUIRED LENGTH OF FULL-HEIGHT SHEATHING AND ASSOCIATED OVERTURNING
ANCHORAGE FOR WALLS SUPPORTING WALLS WITH STONE OR MASONRY VENEER AND USING 33-MIL COLD-FORMED
STEEL FRAMING AND 4-INCH SCREW SPACING ON THE PERIMETER OF EACH PANEL OF STRUCTURAL SHEATHING—continued

** SEISMIC**
DESIGN
CATEGORY
** STORY** ** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** SINGLE-
STORY
HOLD-
DOWN
FORCE
(pounds)**

CUMULATIVE
HOLD-DOWN
FORCE
(pounds)
** SEISMIC**
DESIGN
CATEGORY
** STORY** ** 10** ** 20** ** 30** ** 40** ** 50** ** 60** ** 60** ** 60**
** SEISMIC**
DESIGN
CATEGORY
** STORY** ** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
D2 4.4 6.2 8.1 10.0 11.8 13.7 4,392
D2 7.1 11.6 16.1 20.6 25.1 29.7 4,392 8,784
D2 9.7 16.9 24.1 31.3 38.5 45.7 4,392 13,176
For SI: 1 mil = 0.0254 mm, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound-force = 4.448 N.

TABLE R603.9.5(4)—REQUIRED LENGTH OF FULL-HEIGHT SHEATHING AND ASSOCIATED OVERTURNING
ANCHORAGE FOR WALLS SUPPORTING WALLS WITH STONE OR MASONRY VENEER AND USING 43-MIL COLD-FORMED
STEEL FRAMING AND 4-INCH SCREW SPACING ON THE PERIMETER OF EACH PANEL OF STRUCTURAL SHEATHING

** SEISMIC**
DESIGN
CATEGORY
** STORY** ** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** BRACED WALL LINE LENGTH**
(feet)
** SINGLE-
STORY
HOLD-
DOWN
FORCE
(pounds)**

CUMULATIVE
HOLD-DOWN
FORCE
(pounds)
** SEISMIC**
DESIGN
CATEGORY
** STORY** ** 10** ** 20** ** 30** ** 40** ** 50** ** 60** ** 60** ** 60**
** SEISMIC**
DESIGN
CATEGORY
** STORY** ** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
** Minimum total length of braced wall panels required along each braced wall**
line (feet)
D0 1.9 2.7 3.4 4.2 5.0 5.8 5,928
D0 3.0 4.9 6.8 8.8 10.7 12.6 5,928 11,856
D1 2.3 3.3 4.3 5.2 6.2 7.2 5,928
D1 3.7 6.1 8.5 10.8 13.2 15.6 5,928 11,856
D2 3.3 4.6 6.0 7.4 8.7 10.1 5,928
D2 5.2 8.6 11.9 15.3 18.6 22.0 5,928 11,856
For SI: 1 mil = 0.0254 mm, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound-force = 4.448 N.

6-92 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

WALL CONSTRUCTION

R603.9.5.1 Seismic Design Category C. In Seismic Design Category C, the length of structural sheathing for walls supporting one story, roof and ceiling shall be the greater of the amounts required by Section R603.9.2, except Section R603.9.2.2 shall be permitted.

R603.9.5.2 Seismic Design Categories D 0 , D 1 and D 2 . In Seismic Design Categories D 0, D 1 and D 2, the required length of structural sheathing and overturning anchorage shall be determined in accordance with Tables R603.9.5(1), R603.9.5(2), R603.9.5(3), and R603.9.5(4). Overturning anchorage shall be installed on the doubled studs at the end of each full-height wall segment.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Residential Code (Title 24, Part 2.5)
2025 California Residential Code (Title 24, Part 2.5)
  1. Chapter 1 — ADMINISTRATION
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — BUILDING PLANNING
  4. Chapter 4 — FOUNDATIONS
  5. Chapter 5 — FLOORS
  6. Chapter 6 — WALL CONSTRUCTION
  7. Chapter 7 — WALL COVERING
  8. Chapter 8 — ROOF-CEILING CONSTRUCTION
  9. Chapter 9 — ROOF ASSEMBLIES
  10. Chapter 10 — CHIMNEYS AND FIREPLACES
  11. Chapter 44 — REFERENCED STANDARDS
  12. Appendix AA — BOARD OF APPEALS
  13. Appendix AB — PERMIT FEES
  14. Appendix AC — RESERVED
  15. Appendix BA — RESERVED
  16. Appendix BB — TINY HOUSES
  17. Appendix BC — RESERVED
  18. Appendix BD — RESERVED
  19. Appendix BE — RADON CONTROL METHODS
  20. Appendix BF — PATIO COVERS
  21. Appendix BG — SOUND TRANSMISSION
  22. Appendix BH — AUTOMATIC VEHICULAR GATES
  23. Appendix BI — LIGHT STRAW-CLAY CONSTRUCTION
  24. Appendix BJ — STRAWBALE CONSTRUCTION
  25. Appendix BK — COB CONSTRUCTION (MONOLITHIC ADOBE)
  26. Appendix BL — HEMP-LIME (HEMPCRETE) CONSTRUCTION
  27. Appendix BM — 3D-PRINTED BUILDING CONSTRUCTION
  28. Appendix BN — EXTENDED PLATE WALL CONSTRUCTION
  29. Appendix BO — EXISTING BUILDINGS AND STRUCTURES
  30. Appendix CA — RESERVED
  31. Appendix CB — RESERVED
  32. Appendix CC — RESERVED
  33. Appendix CD — RESERVED
  34. Appendix CE — RESERVED
  35. Appendix CF — RESERVED
  36. Appendix CG — NONSEWERED SANITATION SYSTEMS
  37. Appendix CH — PRIVATE SEWAGE DISPOSAL
  38. Appendix CI — SWIMMING POOL SAFETY ACT
  39. Appendix CJ — EMERGENCY HOUSING
  40. Appendix CK — AREAS PROTECTED BY THE FACILITIES OF THE CENTRAL…

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.