Skip to content

Appendix BJ — STRAWBALE CONSTRUCTION

Section BJ105 — STRAWBALE WALLS—GENERAL

2025 California Residential Code (Title 24, Part 2.5) · 2025 edition · updated 2026-07-27 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

BJ105.1 General.

S trawbale walls shall be designed and constructed in accordance with this section and with Figures BJ105.1(1) through BJ105.1(4) or an approved alternative design. Strawbale structural walls shall be in accordance with the additional requirements of Section BJ106.

FIGURE BJ105.1(1)—TYPICAL BASE OF PLASTERED STRAWBALE WALL ON CONCRETE SLAB AND FOOTING

For SI: 1 inch = 25.4 mm.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

APPENDIX BJ STRAWBALE CONSTRUCTION

FIGURE BJ105.1(2)—TYPICAL BASE OF PLASTERED STRAWBALE WALL OVER RAISED FLOOR

For SI: 1 inch = 25.4 mm.

BJ105.1(3)—TYPICAL TOP OF LOAD-BEARING STRAWBALE WALL

BOUNDARY NAILING PER TABLE R602.3(1)

ROOF SYSTEM PER CHAPTER 8

CAPACITY AT MAX. 2' O.C.

2X BLOCKING FOR DIRECT

BEARING ONTO PLASTER PER

SECTION BJ106.11

METAL CONNECTOR WITH MIN. 400

LB CAPACITY AT MAX. 2' O.C. FOR

BRACED WALL PANELS

FOR BRACED WALL PANELS

INSULATION FILL

STRAW BALES PER SECTIONS BJ103

AND BJ106.4 SHOWN LAID FLAT.

ON-EDGE IS PERMITTED.

For SI inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 2.2 kg.

2X BLOCKING FOR DIRECT BEARING

ONTO PLASTER PER SECTION

BJ106.11

HEADER AT WALL OPENINGS PER TABLE R602.7(1) AND SECTION BJ106.12.3

16d NAILS @ 4 "

MESH STAPLES PER TABLE BJ106.13(1) FOR BRACED WALL PANELS FOR WIND UPLIFT, PER SECTION BJ106.14.

MULTIPLE 2X WHERE REQUIRED FOR HEADERS PER TABLE R602.7(1)

PLASTER FOR LOAD-BEARING

WALLS PER TABLE BJ106.12 AND PER TABLE BJ106.13(1) WHERE WALL IS ALSO USED AS A BRACED

WALL PANEL

MESH AS REQUIRED PER TABLE BJ106.12 OR BJ106.13(1) OR SECTION BJ106.14

APPENDIX BJ-8 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

APPENDIX BJ STRAWBALE CONSTRUCTION

FIGURE BJ105.1(4)—TYPICAL TOP OF POST-AND-BEAM WALL WITH PLASTERED STRAWBALE INFILL

BOUNDARY NAILING PER TABLE R602.3(1)

ROOF SYSTEM PER

CHAPTER 8

2X BLOCKING PER SECTION

BJ106.11 FOR BRACED WALL

PANELS

MESH STAPLES PER TABLE BJ106.13(1) FOR BRACED WALL PANELS

PLASTER, PLYWOOD OR GYPSUM BOARD PER SECTION BJ104.2

STRAW BALES PER SECTIONS BJ103

AND BJ106.4 SHOWN LAID FLAT.

ON-EDGE IS PERMITTED.

NOTE:

NOTE:

NONPLASTER FINISHES ARE

For SI: 1 inch = 25.4 mm.

MESH STAPLES PER TABLE BJ106.13(1) FOR BRACED WALL PANELS

2X BLOCKING PER SECTION

BJ106.11 FOR BRACED WALL

PANELS

BEAM PER TABLE R602.7(1) AND SECTION BJ106.15, WITH MIN. 1½ ″ BEARING OVER POSTS

POSTS BEYOND, AT SPACING PER SPAN IN TABLE R602.7(1). POST = NJ + 1 WITH APPROVED

CONNECTION TO BEAM.

PLASTER PER SECTION BJ104.4 OR PER TABLE BJ106.13(1) WHERE WALL IS USED AS A BRACED WALL

PANEL

MESH WHERE REQUIRED PER SECTION BJ104.4 OR TABLE BJ106.13(1)

BJ105.2 Building limitations and requirements for use of strawbale nonstructural walls.

Buildings using strawbale nonstructural walls shall be subject to the following limitations and requirements:

  1. Number of stories: not more than one, except that two stories shall be allowed with an approved engineered design.
  2. Building height: not more than 25 feet (7620 mm), except that greater heights shall be allowed with an approved engineered design.
  3. Wall height: in accordance with Table BJ105.4.
  4. Braced wall panel lengths: in accordance with Section R602.10.3, with the additional requirements that Table R602.10.3(3) shall apply to all buildings in Seismic Design Category C, and the minimum total length of braced wall panels in Table R602.10.3(3) shall be increased by 60 percent for buildings in Seismic Design Categories C, D 0, D 1 and D 2 .

BJ105.3 Sill plates.

Sill plates shall be installed in accordance with Figure BJ105.1(1) or BJ105.1(2). Sill plates shall support and be flush with each face of the straw bales above and shall be of naturally durable or preservative-treated wood where required by this code. Sill plates shall be not less than nominal 2 inches by 4 inches (51 mm by 102 mm) with anchoring complying with Section R403.1.6 and the additional requirements of Table BJ105.4, where applicable, and Sections BJ106.13.2 and BJ106.13.3 for strawbale braced wall panels.

BJ105.3.1 Exterior sill plate flashing. Exterior sill plates shall receive flashing across the joint between the sill plate and the slab or foundation.

BJ105.4 Out-of-plane resistance methods and unrestrained wall dimension limits.

Strawbale walls shall employ a method of out-of-plane load resistance in accordance with Table BJ105.4 and comply with its associated limits and requirements.

TABLE BJ105.4—OUT-OF-PLANE LOAD RESISTANCE METHODS AND UNRESTRAINED WALL DIMENSION LIMITS

METHOD OF OUT-OF-PLANE
LOAD RESISTANCEa
FOR ULTIMATE
DESIGN WIND
SPEEDS
(mph)
FOR SEISMIC
DESIGN
CATEGORIES
UNRESTRAINED WALL DIMENSIONS,****H b UNRESTRAINED WALL DIMENSIONS,****H b MESH STAPLE
SPACING AT
BOUNDARY
RESTRAINTS
METHOD OF OUT-OF-PLANE
LOAD RESISTANCEa
FOR ULTIMATE
DESIGN WIND
SPEEDS
(mph)
FOR SEISMIC
DESIGN
CATEGORIES
Absolute
limit in feet
Limit based on bale
thicknessT c in feet
(mm)
Limit based on bale
thicknessT c in feet
(mm)
Nonplaster finish or unreinforced
plaster
≤ 130 A, B, C, D0 H ≤ 8 H ≤ 5_T_ None required
Pins per Section BJ105.4.2 ≤ 130 A, B, C, D0 H ≤ 12 H ≤ 8_T_ None required
Pins per Section BJ105.4.2 ≤ 140 A, B, C, D0, D1, D2 H ≤ 10 H ≤ 7_T_ None required
Reinforcedd clay plaster ≤ 140 A, B, C, D0, D1, D2 H ≤ 10 H ≤ 8_T_ 0.5
(H ≤ 140_T_ 0.5)
≤ 6 inches

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

APPENDIX BJ STRAWBALE CONSTRUCTION

TABLE BJ105.4—OUT-OF-PLANE LOAD RESISTANCE METHODS AND UNRESTRAINED WALL DIMENSION LIMITS—continued

METHOD OF OUT-OF-PLANE
LOAD RESISTANCEa
FOR ULTIMATE
DESIGN WIND
SPEEDS
(mph)
FOR SEISMIC
DESIGN
CATEGORIES
UNRESTRAINED WALL DIMENSIONS,****H b UNRESTRAINED WALL DIMENSIONS,****H b MESH STAPLE
SPACING AT
BOUNDARY
RESTRAINTS
METHOD OF OUT-OF-PLANE
LOAD RESISTANCEa
FOR ULTIMATE
DESIGN WIND
SPEEDS
(mph)
FOR SEISMIC
DESIGN
CATEGORIES
Absolute
limit in feet
Limit based on bale
thicknessT c in feet
(mm)
Limit based on bale
thicknessT c in feet
(mm)
Reinforcedd clay plaster ≤ 140 A, B, C, D0, D1, D2 10 <H ≤ 12 H ≤ 8_T_ 0.5
(H ≤ 140_T_ 0.5)
≤ 4 inchese
Reinforcedd cement, cement-lime,
lime or soil-cement plaster
≤ 140 A, B, C, D0, D1, D2 H ≤ 10 H ≤ 9_T_ 0.5
(H ≤ 157_T_ 0.5)
≤ 6 inches
Reinforcedd cement, cement-lime,
lime or soil-cement plaster
≤ 155 A, B, C, D0, D1, D2 H ≤ 12 H ≤ 9_T_ 0.5
(H ≤ 157_T_ 0.5)
≤ 4 inchese
2 × 6 load-bearing wood studsf at
max. 6′ o.c.
≤ 140 A, B, C, D0, D1, D2 H g ≤ 9 NA None required
2 × 6 load-bearing wood studsf at
max. 4′ o.c.
≤ 140 A, B, C, D0, D1, D2 H g ≤ 10 NA None required
2 × 6 load-bearing wood studsf at
max. 2′ o.c.
≤ 140 A, B, C, D0, D1, D2 H g ≤ 12 NA None required
2 × 4 load-bearing wood studsf at
max. 2′ o.c.
≤ 140 A, B, C, D0, D1, D2 H g ≤ 10 NA None required
2 × 6 nonload-bearing wood studsf
at max. 6′ o.c.
≤ 140 A, B, C, D0, D1, D2 H g ≤ 12 NA None required

TABLE BJ105.4—OUT-OF-PLANE LOAD RESISTANCE METHODS AND UNRESTRAINED WALL DIMENSION LIMITS—continued

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s.
NA = Not Applicable.
a. Finishes applied to both sides of stacked bales. Where different finishes are used on opposite sides of a wall, the more restrictive requirements shall apply.
b.H = Stacked bale height in feet (mm) between sill plate and top plate or other approved horizontal restraint, or the horizontal distance in feet (mm) between approved verti-
cal restraints. For load-bearing walls,H refers to vertical height only.
c.T = Bale thickness in feet (mm).
d. Plaster reinforcement shall be any mesh allowed in Table BJ106.13(1) for the matching plaster type, and with staple spacing in accordance with this table. Mesh shall be
installed in accordance with Section BJ106.9.
e. Sill plate attachment shall be with5/8-inch anchor bolts or approved equivalent at not more than 48 inches on center where staple spacing is required to be ≤ 4 inches.
f. Bales shall be attached to the studs by an approved method. Horizontal framing and attachment at top and bottom of studs shall be in accordance with Section R602 or an
approved alternative. Table R602.7(1) shall be used to determine the top framing member where load-bearing stud spacing exceeds 24 inches o.c.
g.H is vertical height only.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s.
NA = Not Applicable.
a. Finishes applied to both sides of stacked bales. Where different finishes are used on opposite sides of a wall, the more restrictive requirements shall apply.
b.H = Stacked bale height in feet (mm) between sill plate and top plate or other approved horizontal restraint, or the horizontal distance in feet (mm) between approved verti-
cal restraints. For load-bearing walls,H refers to vertical height only.
c.T = Bale thickness in feet (mm).
d. Plaster reinforcement shall be any mesh allowed in Table BJ106.13(1) for the matching plaster type, and with staple spacing in accordance with this table. Mesh shall be
installed in accordance with Section BJ106.9.
e. Sill plate attachment shall be with5/8-inch anchor bolts or approved equivalent at not more than 48 inches on center where staple spacing is required to be ≤ 4 inches.
f. Bales shall be attached to the studs by an approved method. Horizontal framing and attachment at top and bottom of studs shall be in accordance with Section R602 or an
approved alternative. Table R602.7(1) shall be used to determine the top framing member where load-bearing stud spacing exceeds 24 inches o.c.
g.H is vertical height only.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s.
NA = Not Applicable.
a. Finishes applied to both sides of stacked bales. Where different finishes are used on opposite sides of a wall, the more restrictive requirements shall apply.
b.H = Stacked bale height in feet (mm) between sill plate and top plate or other approved horizontal restraint, or the horizontal distance in feet (mm) between approved verti-
cal restraints. For load-bearing walls,H refers to vertical height only.
c.T = Bale thickness in feet (mm).
d. Plaster reinforcement shall be any mesh allowed in Table BJ106.13(1) for the matching plaster type, and with staple spacing in accordance with this table. Mesh shall be
installed in accordance with Section BJ106.9.
e. Sill plate attachment shall be with5/8-inch anchor bolts or approved equivalent at not more than 48 inches on center where staple spacing is required to be ≤ 4 inches.
f. Bales shall be attached to the studs by an approved method. Horizontal framing and attachment at top and bottom of studs shall be in accordance with Section R602 or an
approved alternative. Table R602.7(1) shall be used to determine the top framing member where load-bearing stud spacing exceeds 24 inches o.c.
g.H is vertical height only.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s.
NA = Not Applicable.
a. Finishes applied to both sides of stacked bales. Where different finishes are used on opposite sides of a wall, the more restrictive requirements shall apply.
b.H = Stacked bale height in feet (mm) between sill plate and top plate or other approved horizontal restraint, or the horizontal distance in feet (mm) between approved verti-
cal restraints. For load-bearing walls,H refers to vertical height only.
c.T = Bale thickness in feet (mm).
d. Plaster reinforcement shall be any mesh allowed in Table BJ106.13(1) for the matching plaster type, and with staple spacing in accordance with this table. Mesh shall be
installed in accordance with Section BJ106.9.
e. Sill plate attachment shall be with5/8-inch anchor bolts or approved equivalent at not more than 48 inches on center where staple spacing is required to be ≤ 4 inches.
f. Bales shall be attached to the studs by an approved method. Horizontal framing and attachment at top and bottom of studs shall be in accordance with Section R602 or an
approved alternative. Table R602.7(1) shall be used to determine the top framing member where load-bearing stud spacing exceeds 24 inches o.c.
g.H is vertical height only.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s.
NA = Not Applicable.
a. Finishes applied to both sides of stacked bales. Where different finishes are used on opposite sides of a wall, the more restrictive requirements shall apply.
b.H = Stacked bale height in feet (mm) between sill plate and top plate or other approved horizontal restraint, or the horizontal distance in feet (mm) between approved verti-
cal restraints. For load-bearing walls,H refers to vertical height only.
c.T = Bale thickness in feet (mm).

TABLE BJ105.4—OUT-OF-PLANE LOAD RESISTANCE METHODS AND UNRESTRAINED WALL DIMENSION LIMITS—continued d. Plaster reinforcement shall be any mesh allowed in Table BJ106.13(1) for the matching plaster type, and with staple spacing in accordance with this table. Mesh shall be
installed in accordance with Section BJ106.9.
e. Sill plate attachment shall be with5/8-inch anchor bolts or approved equivalent at not more than 48 inches on center where staple spacing is required to be ≤ 4 inches.
f. Bales shall be attached to the studs by an approved method. Horizontal framing and attachment at top and bottom of studs shall be in accordance with Section R602 or an
approved alternative. Table R602.7(1) shall be used to determine the top framing member where load-bearing stud spacing exceeds 24 inches o.c.
g.H is vertical height only.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s.
NA = Not Applicable.
a. Finishes applied to both sides of stacked bales. Where different finishes are used on opposite sides of a wall, the more restrictive requirements shall apply.
b.H = Stacked bale height in feet (mm) between sill plate and top plate or other approved horizontal restraint, or the horizontal distance in feet (mm) between approved verti-
cal restraints. For load-bearing walls,H refers to vertical height only.
c.T = Bale thickness in feet (mm).
d. Plaster reinforcement shall be any mesh allowed in Table BJ106.13(1) for the matching plaster type, and with staple spacing in accordance with this table. Mesh shall be
installed in accordance with Section BJ106.9.
e. Sill plate attachment shall be with5/8-inch anchor bolts or approved equivalent at not more than 48 inches on center where staple spacing is required to be ≤ 4 inches.
f. Bales shall be attached to the studs by an approved method. Horizontal framing and attachment at top and bottom of studs shall be in accordance with Section R602 or an
approved alternative. Table R602.7(1) shall be used to determine the top framing member where load-bearing stud spacing exceeds 24 inches o.c.
g.H is vertical height only.|

BJ105.4.1 Determination of out-of-plane loading. Out-of-plane loading for the use of Table BJ105.4 shall be in terms of the ultimate design wind speed and seismic design category as determined in accordance with Sections R301.2.1 and R301.2.2, respectively. An approved engineered design for out-of-plane load resistance in accordance with Section R301.2.1 shall be required where the building is located in a special wind region or where wind design is required in accordance with Figure R301.2(2) and Section R301.2.1.1.

BJ105.4.2 Pins. Pins used for out-of-plane resistance shall comply with the following or shall be in accordance with an approved engineered design. Pins shall be external, internal or a combination of the two.

  1. Pins shall be [1] / 2 -inch-diameter (12.7 mm) steel, [3] / 4 -inch-diameter (19.1 mm) wood or [1] / 2 -inch-diameter (12.7 mm) bamboo.

  2. External pins shall be installed vertically on both sides of the wall at a spacing of not more than 24 inches (610 mm) on center. External pins shall have full lateral bearing on the sill plate and the top plate or roof-bearing element, and shall be tightly tied through the wall to an opposing pin with ties spaced not more than 32 inches (813 mm) apart and not more than 8 inches (203 mm) from each end of the pins.

  3. Internal pins shall be installed vertically within the center third of the bales, at spacing of not more than 24 inches (610 mm) and shall extend from top course to bottom course. The bottom course shall be connected to its support and the top course shall be connected to the roof- or floor-bearing member above with pins or other approved means. Internal pins shall be continuous or shall overlap through not less than one bale course.

BJ105.5 Connection of light-frame walls to strawbale walls.

Light-frame walls perpendicular to, or at an angle to, a strawbale wall assembly shall be fastened to the bottom and top wood members of the strawbale wall in accordance with requirements for wood or

                                                                                    cold-formed steel light-frame walls in this code, or the abutting stud shall be connected to alternating strawbale courses with a [1] / 2

inch diameter (12.7 mm) steel, [3] / 4 -inch-diameter (19.1 mm) wood or [5] / 8 -inch-diameter (15.9 mm) bamboo dowel, with not less than 8inch (203 mm) penetration.

BJ105.6 Moisture control.

Strawbale walls shall be protected from moisture intrusion and damage in accordance with Sections BJ105.6.1 through BJ105.6.9.

BJ105.6.1 Water-resistive barriers and vapor permeance ratings. Plastered bale walls shall be constructed without any membrane barrier between straw and plaster to facilitate transpiration of moisture from the bales, and to secure a structural bond between straw and plaster, except as permitted or required elsewhere in this appendix. Where a water-resistive barrier is

APPENDIX BJ-10 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

APPENDIX BJ STRAWBALE CONSTRUCTION

placed behind an exterior finish, it shall have a vapor permeance rating of not less than 5 perms, except as permitted or required elsewhere in this appendix.

BJ105.6.2 Interior vapor retarders. Wall finishes shall have an equivalent vapor permeance rating of a Class III vapor retarder on the interior side of exterior strawbale walls in Climate Zones 5, 6, 7, 8 and Marine 4, as defined in Chapter 11. Bale walls enclosing showers or steam rooms shall be protected on the interior side by a Class I or Class II vapor retarder.

BJ105.6.3 Penetrations in exterior strawbale walls. Penetrations in exterior strawbale walls shall be sealed with an approved sealant or gasket on the exterior side of the wall in all climate zones. Penetrations and joints at the floor and ceiling shall be sealed on the interior side of the wall in Climate Zones 5, 6, 7, 8 and Marine 4, as defined in Chapter 11.

BJ105.6.4 Horizontal surfaces. Bale walls and other bale elements shall be provided with a water-resistant barrier at weatherexposed horizontal surfaces. The water-resistant barrier shall be of a material and installation that will prevent water from entering the wall system. Horizontal surfaces shall include exterior window sills, sills at exterior niches and buttresses. Horizontal surfaces shall be sloped not less than 1 unit vertical in 12 units horizontal (8-percent slope) and shall drain away from bale walls and elements. Where the water-resistant barrier is below the finish material, it shall be sloped not less than 1 unit vertical in 12 units horizontal (8-percent slope) and shall drain to the outside surface of the bale wall’s vertical finish.

BJ105.6.5 Separation of bales and concrete. A sheet- or liquid-applied Class II vapor retarder shall be installed between bales and supporting concrete or masonry. The bales shall be separated from the vapor retarder by not less than [3] / 4 inch (19.1 mm), and that space shall be filled with an insulating material such as wood or rigid insulation, or a material that allows vapor dispersion such as gravel, or other approved insulating or vapor dispersion material. Sill plates shall be installed at this interface in accordance with Section BJ105.3. Where bales abut a concrete or masonry wall that retains earth, a Class II vapor retarder shall be provided between such wall and the bales.

an insulating material such as wood or rigid insulation, or a material that allows vapor dispersion such as gravel, or other approved insulating or vapor dispersion material. Sill plates shall be installed at this interface in accordance with Section BJ105.3. Where bales abut a concrete or masonry wall that retains earth, a Class II vapor retarder shall be provided between such wall and the bales.

BJ105.6.6 Separation of bales and earth. Bales shall be separated from earth by not less than 8 inches (203 mm).

BJ105.6.7 Separation of exterior plaster and earth. Exterior plaster applied to straw bales shall be located not less than 6 inches (152 mm) above earth or 3 inches (76 mm) above paved areas.

BJ105.6.8 Separation of wood and plaster. Where wood framing or wood sheathing occurs at the exterior face of strawbale walls, such wood surfaces shall be separated from exterior plaster with two layers of Grade D paper, No. 15 asphalt felt or other approved material in accordance with Section R703.7.3, extending not less than 1 inch (25 mm) past the edges of the framing member.

Exceptions:

  1. Where the wood is preservative treated or naturally durable and is not greater than 1 [1] / 2 inches (38 mm) in width.
  2. Clay plaster shall not be required to be separated from untreated wood that is not greater than 1 [1] / 2 inches (38 mm) in width.

BJ105.6.9 Separation of exterior plaster and foundation. Exterior plaster shall be separated from the building foundation with a moisture barrier.

BJ105.7 Inspections.

The building official shall inspect the following aspects of strawbale construction in accordance with Section R109.1:

  1. Sill plate anchors, as part of and in accordance with Section R109.1.1.
  2. Mesh placement and attachment, where mesh is required by this appendix.
  3. Pins, where required by and in accordance with Section BJ105.4.

BJ105.8 Voids and stuffing.

Voids between bales and between bales and framing members shall not exceed 4 inches (102 mm) in width, and such voids shall be tightly stuffed with flakes, loose straw or straw-clay before application of finish.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Residential Code (Title 24, Part 2.5)
2025 California Residential Code (Title 24, Part 2.5)
  1. Chapter 1 — ADMINISTRATION
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — BUILDING PLANNING
  4. Chapter 4 — FOUNDATIONS
  5. Chapter 5 — FLOORS
  6. Chapter 6 — WALL CONSTRUCTION
  7. Chapter 7 — WALL COVERING
  8. Chapter 8 — ROOF-CEILING CONSTRUCTION
  9. Chapter 9 — ROOF ASSEMBLIES
  10. Chapter 10 — CHIMNEYS AND FIREPLACES
  11. Chapter 44 — REFERENCED STANDARDS
  12. Appendix AA — BOARD OF APPEALS
  13. Appendix AB — PERMIT FEES
  14. Appendix AC — RESERVED
  15. Appendix BA — RESERVED
  16. Appendix BB — TINY HOUSES
  17. Appendix BC — RESERVED
  18. Appendix BD — RESERVED
  19. Appendix BE — RADON CONTROL METHODS
  20. Appendix BF — PATIO COVERS
  21. Appendix BG — SOUND TRANSMISSION
  22. Appendix BH — AUTOMATIC VEHICULAR GATES
  23. Appendix BI — LIGHT STRAW-CLAY CONSTRUCTION
  24. Appendix BJ — STRAWBALE CONSTRUCTION
  25. Appendix BK — COB CONSTRUCTION (MONOLITHIC ADOBE)
  26. Appendix BL — HEMP-LIME (HEMPCRETE) CONSTRUCTION
  27. Appendix BM — 3D-PRINTED BUILDING CONSTRUCTION
  28. Appendix BN — EXTENDED PLATE WALL CONSTRUCTION
  29. Appendix BO — EXISTING BUILDINGS AND STRUCTURES
  30. Appendix CA — RESERVED
  31. Appendix CB — RESERVED
  32. Appendix CC — RESERVED
  33. Appendix CD — RESERVED
  34. Appendix CE — RESERVED
  35. Appendix CF — RESERVED
  36. Appendix CG — NONSEWERED SANITATION SYSTEMS
  37. Appendix CH — PRIVATE SEWAGE DISPOSAL
  38. Appendix CI — SWIMMING POOL SAFETY ACT
  39. Appendix CJ — EMERGENCY HOUSING
  40. Appendix CK — AREAS PROTECTED BY THE FACILITIES OF THE CENTRAL…

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.