4.506.1 Bathroom exhaust fans. Each bathroom shall be mechanically ventilated and shall comply with the following:

  1. Fans shall be ENERGY STAR compliant and be ducted to terminate outside the building.
  2. Unless functioning as a component of a whole house ventilation system, fans must be controlled by a humidity control. a. Humidity controls shall be capable of adjustment between a relative humidity range of ≤ 50 percent to a maximum of 80 percent. A humidity control may utilize manual or automatic means of adjustment. b. A humidity control may be a separate component to the exhaust fan and is not required to be integral (i.e., built-in).

Notes:

  1. For the purposes of this section, a bathroom is a room which contains a bathtub, shower or tub/shower combination.
  2. Lighting integral to bathroom exhaust fans shall comply with the California Energy Code.