Chapter 7 — ALTERATIONS—LEVEL 1
Section 705 — REROOFING
2025 California Existing Building Code (Title 24, Part 10) · 2025 edition · updated 2026-07-29 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
[BS] 705.1 General. Materials and methods of application used for recovering or replacing an existing roof covering shall comply with the requirements of Chapter 15 of the California Building Code .
Exceptions:
- Roof replacement or roof recover of existing low-slope roof coverings shall not be required to meet the minimum design slope requirement of [1] / 4 unit vertical in 12 units horizontal (2-percent slope) in Section 1507 of the California Building Code for roofs that provide positive roof drainage and meet the requirements of Sections 1608.3 and 1611.2 of the Cali- fornia Building Code .
- Recovering or replacing an existing roof covering shall not be required to meet the requirement for secondary (emergency overflow) drains or scuppers in Section 1502 of the California Building Code for roofs that provide for positive roof drainage and meet the requirements of Sections 1608.3 and 1611.2 of the California Building Code . For the purposes of this exception, existing secondary drainage or scupper systems required in accordance with this code shall not be removed unless they are replaced by secondary drains or scuppers designed and installed in accordance with Section 1502 of the California Building Code .
[BS] 705.2 Roof replacement. Roof replacement shall include the removal of all existing layers of roof coverings down to the roof deck.
Exceptions:
- Where the existing roof assembly includes an ice barrier membrane that is adhered to the roof deck and the existing sheathing is not water-soaked or deteriorated to the point that it is not adequate as a base for additional roofing, the existing ice barrier membrane shall be permitted to remain in place and covered with an additional layer of ice barrier membrane in accordance with Section 1507 of the California Building Code where permitted by the roof-covering manufacturer and new ice-barrier underlayment manufacturer.
7-4 2025 CALIFORNIA EXISTING BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ALTERATIONS—LEVEL 1
- Where the existing roof includes a self-adhered underlayment and the existing sheathing is not water-soaked or deteriorated to the point that it is not adequate as a base for additional roofing, the existing self-adhered underlayment shall be permitted to remain in place and covered with an underlayment complying with Tables 1507.1.1(1), 1507.1.1(2) and 1507.1.1(3) of the California Building Code .
- Where the existing roof includes one layer of self-adhered underlayment and the existing layer cannot be removed without damaging the roof deck, a second layer of self-adhered underlayment is permitted to be installed over the existing self-adhered underlayment provided all of the following conditions are met: 3.1. It is permitted by the roof-covering manufacturer and self-adhered underlayment manufacturer. 3.2. The existing sheathing is not water-soaked or deteriorated to the point that it is not adequate as a base for additional roofing. 3.3. The second layer of self-adhered underlayment is installed such that buildup of material at walls, valleys, roof edges, end laps and side laps does not exceed two layers.
[BS] 705.3 Roof recover. The installation of a new roof covering over an existing roof covering shall be permitted where any of the following conditions occur:
- The new roof covering is installed in accordance with the roof covering manufacturer’s approved instructions.
- Complete and separate roofing systems, such as standing-seam metal roof panel systems, that are designed to transmit the roof loads directly to the building’s structural system and that do not rely on existing roofs and roof coverings for support, shall not require the removal of existing roof coverings.
- Metal panel, metal shingle and concrete and clay tile roof coverings shall be permitted to be installed over existing wood shake roofs when applied in accordance with Section 705.3.1.
- The application of a new protective roof coating over an existing protective roof coating, a metal roof panel, built-up roof, spray polyurethane foam roofing system, metal roof shingles, mineral-surfaced roll roofing, modified bitumen roofing or thermoset and thermoplastic single-ply roofing shall be permitted without tear off of existing roof coverings.
Exception: A roof recover shall not be permitted where any of the following conditions occur:
- Where the existing roof or roof covering is water-soaked or has deteriorated to the point that the existing roof or roof covering is not adequate as a base for additional roofing.
- Where the existing roof covering is slate, clay, cement or asbestos-cement tile.
- Where the existing roof has two or more applications of any type of roof covering.
[BS] 705.3.1 Roof recovering over wood shingles or shakes. Where the application of a new roof covering over wood shingle or shake roofs creates a combustible concealed space, the entire existing surface shall be covered with gypsum panel products, mineral fiber, glass fiber or other approved materials securely fastened in place.
[BS] 705.4 Reinstallation of materials. Existing slate, clay or cement tile shall be permitted for reinstallation, except that damaged, cracked or broken slate or tile shall not be reinstalled. Existing vent flashing, metal edgings, drain outlets, collars and metal counterflashings shall not be reinstalled where rusted, damaged or deteriorated. Existing ballast that is damaged, cracked or broken shall not be reinstalled. Existing aggregate surfacing materials from built-up roofs shall not be reinstalled.
[BS] 705.5 Flashings. Flashings shall be reconstructed in accordance with approved manufacturer’s installation instructions. Metal flashing to which bituminous materials are to be adhered shall be primed prior to installation.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Existing Building Code (Title 24, Part 10)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — PROVISIONS FOR ALL COMPLIANCE METHODS
- Chapter 3A — PROVISIONS FOR ALL COMPLIANCE METHODS
- Chapter 4 — REPAIRS
- Chapter 4A — REPAIRS
- Chapter 5 — PRESCRIPTIVE COMPLIANCE METHOD
- Chapter 5A — PRESCRIPTIVE COMPLIANCE METHOD
- Chapter 6 — CLASSIFICATION OF WORK
- Chapter 8 — ALTERATIONS—LEVEL 2
- Chapter 9 — ALTERATIONS—LEVEL 3
- Chapter 10 — CHANGE OF OCCUPANCY
- Chapter 11 — ADDITIONS
- Chapter 12 — HISTORIC BUILDINGS
- Chapter 13 — PERFORMANCE COMPLIANCE METHODS
- Chapter 14 — RELOCATED OR MOVED BUILDINGS
- Chapter 15 — CONSTRUCTION SAFEGUARDS
- Chapter 16 — REFERENCED STANDARDS
- Appendix A — GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING B…
- Appendix B — SUPPLEMENTARY ACCESSIBILITY REQUIREMENTS FOR EXIS…
- Appendix C — GUIDELINES FOR THE WIND RETROFIT OF EXISTING BUIL…
- Appendix D — BOARD OF APPEALS
- Appendix E — TEMPORARY EMERGENCY USES
- Appendix A — GUIDELINES ON FIRE RATINGS OF ARCHAIC MATERIALS A…