Skip to content

Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES

Section 722

California Building Code (Title 24, Part 2) · 2019 edition · updated 2026-09-12 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

722.1 General.

The provisions of this section contain procedures by which the fire resistance of specific materials or combinations of materials is established by calculations. These procedures apply only to the information contained in this section and shall not be otherwise used. The calculated fire resistance of concrete, concrete masonry and clay masonry assemblies shall be permitted in accordance with ACI 216.1/TMS 0216. The calculated fire resistance of steel assemblies shall be permitted in accordance with Chapter 5 of ASCE 29. The calculated fire resistance of exposed wood members and wood decking shall be permitted in accordance with Chapter 16 of ANSI/ AWC National Design Specification for Wood Construction (NDS).

722.2 Concrete assemblies.

The provisions of this section contain procedures by which the fire-resistance ratings of concrete assemblies are established by calculations.

722.2.1 Concrete walls. Cast-in-place and precast concrete walls shall comply with Section 722.2.1.1. Multiwythe concrete walls shall comply with Section 722.2.1.2. Joints between precast panels shall comply with Section 722.2.1.3. Concrete walls with gypsum wallboard or plaster finish shall comply with Section 722.2.1.4.

4 t t + - 1 te - t --- s -

where:

(Equation 7-3)

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(1) MINIMUM PROTECTION OF STRUCTURAL PARTS BASED ON TIME PERIODS FOR VARIOUS NONCOMBUSTIBLE INSULATING MATERIALSm
STRUCTURAL
PARTS TO BE
** PROTECTED**
ITEM
NUMBER
INSULATING MATERIAL USED MINIMUM THICKNESS OF
INSULATING MATERIAL
** FOR THE FOLLOWING**
** FIRE-RESISTANCE**
PERIODS (inches)
MINIMUM THICKNESS OF
INSULATING MATERIAL
** FOR THE FOLLOWING**
** FIRE-RESISTANCE**
PERIODS (inches)
MINIMUM THICKNESS OF
INSULATING MATERIAL
** FOR THE FOLLOWING**
** FIRE-RESISTANCE**
PERIODS (inches)
MINIMUM THICKNESS OF
INSULATING MATERIAL
** FOR THE FOLLOWING**
** FIRE-RESISTANCE**
PERIODS (inches)
STRUCTURAL
PARTS TO BE
** PROTECTED**
ITEM
NUMBER
INSULATING MATERIAL USED **4 **
hours
3
hours
**2 **
hours
**1 **
hour
1. Steel columns
and all of primary
trusses
(continued)
1-1.1 Carbonate, lightweight and sand-lightweight aggregate concrete, members 6" × 6" or
greater (not including sandstone, granite and siliceous gravel).a
21/2 2 11/2 1
1. Steel columns
and all of primary
trusses
(continued)
1-1.2 Carbonate, lightweight and sand-lightweight aggregate concrete, members 8" × 8" or
greater (not including sandstone, granite and siliceous gravel).a
2 11/2 1 1
1. Steel columns
and all of primary
trusses
(continued)
1-1.3 Carbonate, lightweight and sand-lightweight aggregate concrete, members
12" × 12" or greater (not including sandstone, granite and siliceous gravel).a
11/2 1 1 1
1. Steel columns
and all of primary
trusses
(continued)
1-1.4 Siliceous aggregate concrete and concrete excluded in Item 1-1.1, members 6" × 6" or
greater.a
3 2 11/2 1
1. Steel columns
and all of primary
trusses
(continued)
1-1.5 Siliceous aggregate concrete and concrete excluded in Item 1-1.1, members 8" × 8" or
greater.a
21/2 2 1 1
1. Steel columns
and all of primary
trusses
(continued)
1-1.6 Siliceous aggregate concrete and concrete excluded in Item 1-1.1, members
12" × 12" or greater.a
2 1 1 1
1. Steel columns
and all of primary
trusses
(continued)
1-2.1 Clay or shale brick with brick and mortar fill.a 33/4 21/4
1. Steel columns
and all of primary
trusses
(continued)
1-3.1 4" hollow clay tile in two 2" layers;1/2" mortar between tile and column;3/8" metal
mesh 0.046" wire diameter in horizontal joints; tile fill.a
4
1. Steel columns
and all of primary
trusses
(continued)
1-3.2 2" hollow clay tile;3/4" mortar between tile and column;3/8" metal mesh 0.046" wire
diameter in horizontal joints; limestone concrete filla; plastered with3/4" gypsum plas-
ter.
3
1. Steel columns
and all of primary
trusses
(continued)
1-3.3 2" hollow clay tile with outside wire ties 0.08" diameter at each course of tile or3/8"
metal mesh 0.046" diameter wire in horizontal joints; limestone or trap-rock concrete
filla extending 1" outside column on all sides.
3
1. Steel columns
and all of primary
trusses
(continued)
1-3.4 2" hollow clay tile with outside wire ties 0.08" diameter at each course of tile with or
without concrete fill;3/4" mortar between tile and column.
2
1. Steel columns
and all of primary
trusses
(continued)
1-4.1 Cement plaster over metal lath wire tied to3/4" cold-rolled vertical channels with 0.049"
(No. 18 B.W. gage) wire ties spaced 3" to 6" on center. Plaster mixed
1:21/2 by volume, cement to sand.
21/2
b
7/8
1. Steel columns
and all of primary
trusses
(continued)
1-5.1 Vermiculite concrete, 1:4 mix by volume over paperbacked wire fabric lath wrapped
directly around column with additional 2" × 2" 0.065"/0.065" (No. 16/16 B.W. gage)
wire fabric placed3/4" from outer concrete surface. Wire fabric tied with 0.049" (No. 18
B.W. gage) wire spaced 6" on center for inner layer and 2" on center for outer layer.
2
1. Steel columns
and all of primary
trusses
(continued)
1-6.1 Perlite or vermiculite gypsum plaster over metal lath wrapped around column and
furred 11/4" from column flanges. Sheets lapped at ends and tied at 6" intervals with
0.049" (No. 18 B.W. gage) tie wire. Plaster pushed through to flanges.
11/2 1
1. Steel columns
and all of primary
trusses
(continued)
1-6.2 Perlite or vermiculite gypsum plaster over self-furring metal lath wrapped directly
around column, lapped 1" and tied at 6" intervals with 0.049" (No. 18 B.W. gage) wire.
13/4 13/8 1
1. Steel columns
and all of primary
trusses
(continued)
1-6.3 Perlite or vermiculite gypsum plaster on metal lath applied to3/4" cold-rolled channels
spaced 24" apart vertically and wrapped flatwise around column.
11/2
1. Steel columns
and all of primary
trusses
(continued)
1-6.4 Perlite or vermiculite gypsum plaster over two layers of1/2" plain full-length gypsum
lath applied tight to column flanges. Lath wrapped with 1" hexagonal mesh of No. 20
gage wire and tied with doubled 0.035" diameter (No. 18 B.W. gage) wire ties spaced
23" on center. For three-coat work, the plaster mix for the second coat shall not exceed
100 pounds of gypsum to 21/2 cubic feet of aggregate for the 3-hour system.
21/2 2

(continued)

244 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

TABLE 721.1(1)—continued MINIMUM PROTECTION OF STRUCTURAL PARTS BASED ON TIME PERIODS FOR VARIOUS NONCOMBUSTIBLE INSULATING MATERIALSm
STRUCTURAL
PARTS TO BE
** PROTECTED**
ITEM
NUMBER
INSULATING MATERIAL USED MINIMUM THICKNESS OF
INSULATING MATERIAL
** FOR THE FOLLOWING**
** FIRE-RESISTANCE**
PERIODS (inches)
MINIMUM THICKNESS OF
INSULATING MATERIAL
** FOR THE FOLLOWING**
** FIRE-RESISTANCE**
PERIODS (inches)
MINIMUM THICKNESS OF
INSULATING MATERIAL
** FOR THE FOLLOWING**
** FIRE-RESISTANCE**
PERIODS (inches)
MINIMUM THICKNESS OF
INSULATING MATERIAL
** FOR THE FOLLOWING**
** FIRE-RESISTANCE**
PERIODS (inches)
STRUCTURAL
PARTS TO BE
** PROTECTED**
ITEM
NUMBER
INSULATING MATERIAL USED **4 **
hours
3
hours
**2 **
hours
**1 **
hour
1. Steel columns
and all of primary
trusses
1-6.5 Perlite or vermiculite gypsum plaster over one layer of1/2" plain full-length gypsum
lath applied tight to column flanges. Lath tied with doubled 0.049" (No. 18 B.W. gage)
wire ties spaced 23" on center and scratch coat wrapped with 1" hexagonal mesh
0.035" (No. 20 B.W. gage) wire fabric. For three-coat work, the plaster mix for the sec-
ond coat shall not exceed 100 pounds of gypsum to 21/2 cubic feet of aggregate.
2
1. Steel columns
and all of primary
trusses
1-7.1 Multiple layers of1/2" gypsum wallboardc adhesivelyd secured to column flanges and
successive layers. Wallboard applied without horizontal joints. Corner edges of each
layer staggered. Wallboard layer below outer layer secured to column with doubled
0.049" (No. 18 B.W. gage) steel wire ties spaced 15" on center. Exposed corners taped
and treated.
2 1
1. Steel columns
and all of primary
trusses
1-7.2 Three layers of5/8" Type X gypsum wallboard.cFirst and second layer held in place by
1/8" diameter by 13/8" long ring shank nails with5/16" diameter heads spaced 24" on cen-
ter at corners. Middle layer also secured with metal straps at mid-height and 18" from
each end, and by metal corner bead at each corner held by the metal straps. Third layer
attached to corner bead with 1" long gypsum wallboard screws spaced 12" on center.
17/8
1. Steel columns
and all of primary
trusses
1-7.3 Three layers of5/8" Type X gypsum wallboard,c each layer screw attached to 15/8" steel
studs 0.018" thick (No. 25 carbon sheet steel gage) at each corner of column. Middle
layer also secured with 0.049" (No. 18 B.W. gage) double-strand steel wire ties, 24" on
center. Screws are No. 6 by 1" spaced 24" on center for inner layer, No. 6 by 15/8"
spaced 12" on center for middle layer and No. 8 by 21/4" spaced 12" on center for outer
layer.
17/8
1. Steel columns
and all of primary
trusses
1-8.1 Wood-fibered gypsum plaster mixed 1:1 by weight gypsum-to-sand aggregate applied
over metal lath. Lath lapped 1" and tied 6" on center at all end, edges and spacers with
0.049" (No. 18 B.W. gage) steel tie wires. Lath applied over1/2" spacers made of3/4"
furring channel with 2" legs bent around each corner. Spacers located 1" from top and
bottom of member and not greater than 40" on center and wire tied with a single strand
of 0.049" (No. 18 B.W. gage) steel tie wires. Corner bead tied to the lath at 6" on center
along each corner to provide plaster thickness.
15/8
1. Steel columns
and all of primary
trusses
1-9.1 Minimum W8x35 wide flange steel column (w/d 0.75) with each web cavity filled
even with the flange tip with normal weight carbonate or siliceous aggregate concrete
(3,000 psi minimum compressive strength with 145 pcf ± 3 pcf unit weight). Reinforce
the concrete in each web cavity with a minimum No. 4 deformed reinforcing bar
installed vertically and centered in the cavity, and secured to the column web with a
minimum No. 2 horizontal deformed reinforcing bar welded to the web every 18" on
center vertically. As an alternative to the No. 4 rebar,3/4" diameter by 3" long headed
studs, spaced at 12" on center vertically, shall be welded on each side of the web mid-
way between the column flanges.
See
Note
n
2. Webs or flanges
of steel beams and
girders
(continued)
2-1.1 Carbonate, lightweight and sand-lightweight aggregate concrete (not including sand-
stone, granite and siliceous gravel) with 3" or finer metal mesh placed 1" from the fin-
ished surface anchored to the top flange and providing not less than 0.025 square inch
of steel area per foot in each direction.
2 11/2 1 1
2. Webs or flanges
of steel beams and
girders
(continued)
2-1.2 Siliceous aggregate concrete and concrete excluded in Item 2-1.1 with 3" or finer metal
mesh placed 1" from the finished surface anchored to the top flange and providing not
less than 0.025 square inch of steel area per foot in each direction.
21/2 2 11/2 1
2. Webs or flanges
of steel beams and
girders
(continued)
2-2.1 Cement plaster on metal lath attached to3/4" cold-rolled channels with 0.04" (No. 18
B.W. gage) wire ties spaced 3" to 6" on center. Plaster mixed 1:21/2 by volume, cement
to sand.
21/2
b
7/8

(continued)

FIRE AND SMOKE PROTECTION FEATURES

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(1)—continued MINIMUM PROTECTION OF STRUCTURAL PARTS BASED ON TIME PERIODS FOR VARIOUS NONCOMBUSTIBLE INSULATING MATERIALSm
STRUCTURAL
PARTS TO BE
** PROTECTED**
ITEM
NUMBER
INSULATING MATERIAL USED MINIMUM THICKNESS OF
INSULATING MATERIAL
** FOR THE FOLLOWING**
** FIRE-RESISTANCE**
PERIODS (inches)
MINIMUM THICKNESS OF
INSULATING MATERIAL
** FOR THE FOLLOWING**
** FIRE-RESISTANCE**
PERIODS (inches)
MINIMUM THICKNESS OF
INSULATING MATERIAL
** FOR THE FOLLOWING**
** FIRE-RESISTANCE**
PERIODS (inches)
MINIMUM THICKNESS OF
INSULATING MATERIAL
** FOR THE FOLLOWING**
** FIRE-RESISTANCE**
PERIODS (inches)
STRUCTURAL
PARTS TO BE
** PROTECTED**
ITEM
NUMBER
INSULATING MATERIAL USED **4 **
hours
3
hours
**2 **
hours
**1 **
hour
2. Webs or
flanges of steel
beams and
girders
2-3.1 Vermiculite gypsum plaster on a metal lath cage, wire tied to 0.165" diameter (No. 8
B.W. gage) steel wire hangers wrapped around beam and spaced 16" on center. Metal
lath ties spaced approximately 5" on center at cage sides and bottom.
7/8
2. Webs or
flanges of steel
beams and
girders
2-4.1 Two layers of5/8" Type X gypsum wallboardc are attached to U-shaped brackets spaced
24" on center. 0.018" thick (No. 25 carbon sheet steel gage) 15/8" deep by 1" galvanized
steel runner channels are first installed parallel to and on each side of the top beam
flange to provide a1/2" clearance to the flange. The channel runners are attached to steel
deck or concrete floor construction with approved fasteners spaced 12" on center. U-
shaped brackets are formed from members identical to the channel runners. At the bent
portion of the U-shaped bracket, the flanges of the channel are cut out so that 15/8" deep
corner channels can be inserted without attachment parallel to each side of the lower
flange.
As an alternative, 0.021" thick (No. 24 carbon sheet steel gage) 1" × 2" runner and cor-
ner angles shall be used in lieu of channels, and the web cutouts in the U-shaped brack-
ets shall not be required. Each angle is attached to the bracket with1/2"-long No. 8 self-
drilling screws. The vertical legs of the U-shaped bracket are attached to the runners
with one 1/2" long No. 8 self-drilling screw. The completed steel framing provides a 21/8"
and 11/2" space between the inner layer of wallboard and the sides and bottom of the
steel beam, respectively. The inner layer of wallboard is attached to the top runners and
bottom corner channels or corner angles with 11/4"-long No. 6 self-drilling screws
spaced 16" on center. The outer layer of wallboard is applied with 13/4"-long No. 6 self-
drilling screws spaced 8" on center. The bottom corners are reinforced with metal corner
beads.
11/4
2. Webs or
flanges of steel
beams and
girders
2-4.2 Three layers of5/8" Type X gypsum wallboardc attached to a steel suspension system as
described immediately above utilizing the 0.018" thick (No. 25 carbon sheet steel gage)
1" × 2" lower corner angles. The framing is located so that a 21/8" and 2" space is pro-
vided between the inner layer of wallboard and the sides and bottom of the beam,
respectively. The first two layers of wallboard are attached as described immediately
above. A layer of 0.035" thick (No. 20 B.W. gage) 1" hexagonal galvanized wire mesh
is applied under the soffit of the middle layer and up the sides approximately 2". The
mesh is held in position with the No. 6 15/8"-long screws installed in the vertical leg of
the bottom corner angles. The outer layer of wallboard is attached with No. 6 21/4"-long
screws spaced 8" on center. One screw is installed at the mid-depth of the bracket in
each layer. Bottom corners are finished as described above.
17/8
3. Bonded pre-
tensioned rein-
forcement in
prestressed
concretee
3-1.1 Carbonate, lightweight, sand-lightweight and siliceousf aggregate concrete
Beams or girders
Solidh
4g 3g
2
21/2
11/2
11/2
1

(continued)

246 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(1)—continued MINIMUM PROTECTION OF STRUCTURAL PARTS BASED ON TIME PERIODS FOR VARIOUS NONCOMBUSTIBLE INSULATING MATERIALSm
STRUCTURAL
PARTS TO BE
** PROTECTED**
ITEM
NUMBER
INSULATING MATERIAL USED MINIMUM THICKNESS OF
INSULATING MATERIAL
** FOR THE FOLLOWING**
** FIRE-RESISTANCE**
PERIODS (inches)
MINIMUM THICKNESS OF
INSULATING MATERIAL
** FOR THE FOLLOWING**
** FIRE-RESISTANCE**
PERIODS (inches)
MINIMUM THICKNESS OF
INSULATING MATERIAL
** FOR THE FOLLOWING**
** FIRE-RESISTANCE**
PERIODS (inches)
MINIMUM THICKNESS OF
INSULATING MATERIAL
** FOR THE FOLLOWING**
** FIRE-RESISTANCE**
PERIODS (inches)
STRUCTURAL
PARTS TO BE
** PROTECTED**
ITEM
NUMBER
INSULATING MATERIAL USED **4 **
hours
3
hours
**2 **
hours
**1 **
hour
4. Bonded or
unbonded post-
tensioned ten-
dons in pre-
stressed
concretee, i
4-1.1 Carbonate, lightweight, sand-lightweight and siliceousf aggregate concrete
Unrestrained members:
Solid slabsh
Beams and girdersj
8" wide
greater than 12" wide

3
2
41/2
21/2
11/2
21/2
2

13/4
11/2
4. Bonded or
unbonded post-
tensioned ten-
dons in pre-
stressed
concretee, i
4-1.2 Carbonate, lightweight, sand-lightweight and siliceous aggregate
Restrained members:k
Solid slabsh
Beams and girdersj
8" wide
greater than 12" wide
11/4
21/2
2
1
2
13/4
3/4
13/4
11/2


5. Reinforcing
steel in rein-
forced concrete
columns, beams
girders and
trusses
5-1.1 Carbonate, lightweight and sand-lightweight aggregate concrete, members 12" or
larger, square or round. (Size limit does not apply to beams and girders monolithic
with floors.)
Siliceous aggregate concrete, members 12" or larger, square or round. (Size limit
does not apply to beams and girders monolithic with floors.)
11/2
2
11/2
11/2
11/2
11/2
11/2
11/2
6. Reinforcing
steel in rein-
forced concrete
joistsl
6-1.1
6-1.2
Carbonate, lightweight and sand-lightweight aggregate concrete
Siliceous aggregate concrete
11/4
13/4
11/4
11/2
1
1
3/4
3/4
7. Reinforcing
and tie rods in
floor and roof
slabsl
7-1.1
7-1.2
Carbonate, lightweight and sand-lightweight aggregate concrete
Siliceous aggregate concrete
1
11/4
1
1
3/4
1
3/4
3/4

For SI: 1 inch = 25.4 mm, 1 square inch = 645.2 mm 2, 1 cubic foot = 0.0283 m 3, 1 pound per cubic foot = 16.02 kg/m 3 . a. Reentrant parts of protected members to be filled solidly. b. Two layers of equal thickness with a 3 /4-inch airspace between. c. For all of the construction with gypsum wallboard described in Table 721.1(1), gypsum base for veneer plaster of the same size, thickness and core type shall

2, 1 cubic foot = 0.0283 m 3, 1 pound per cubic foot = 16.02 kg/m 3 . a. Reentrant parts of protected members to be filled solidly. b. Two layers of equal thickness with a 3 /4-inch airspace between. c. For all of the construction with gypsum wallboard described in Table 721.1(1), gypsum base for veneer plaster of the same size, thickness and core type shall

be permitted to be substituted for gypsum wallboard, provided that attachment is identical to that specified for the wallboard and the joints on the face layer are reinforced, and the entire surface is covered with not less than 1 /16-inch gypsum veneer plaster. d. An approved adhesive qualified under ASTM E119 or UL 263. e. Where lightweight or sand-lightweight concrete having an oven-dry weight of 110 pounds per cubic foot or less is used, the tabulated minimum cover shall be

permitted to be reduced 25 percent, except that the reduced cover shall be not less than 3 /4 inch in slabs or 1 1 /2 inches in beams or girders. f. For solid slabs of siliceous aggregate concrete, increase tendon cover 20 percent. g. Adequate provisions against spalling shall be provided by U-shaped or hooped stirrups spaced not to exceed the depth of the member with a clear cover of 1 inch. h. Prestressed slabs shall have a thickness not less than that required in Table 721.1(3) for the respective fire-resistance time period. i. Fire coverage and end anchorages shall be as follows: Cover to the prestressing steel at the anchor shall be 1 /2 inch greater than that required away from the

anchor. Minimum cover to steel-bearing plate shall be 1 inch in beams and 3 /4 inch in slabs. j. For beam widths between 8 inches and 12 inches, cover thickness shall be permitted to be determined by interpolation. k. Interior spans of continuous slabs, beams and girders shall be permitted to be considered restrained. l. For use with concrete slabs having a comparable fire endurance where members are framed into the structure in such a manner as to provide equivalent

performance to that of monolithic concrete construction. m.Generic fire-resistance ratings (those not designated as PROPRIETARY* in the listing) in GA 600 shall be accepted as if herein listed. n. Additional insulating material is not required on the exposed outside face of the column flange to achieve a 1-hour fire-resistance rating.

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(2)

RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONS a, o, p

MATERIAL ITEM
NUMBER
CONSTRUCTION MINIMUM FINISHED
THICKNESS FACE-TO-
FACEb (inches)
MATERIAL ITEM
NUMBER
CONSTRUCTION **4 **
hours
3
hours
**2 **
hours
**1 **
hour
1. Brick of clay
or shale
1-1.1 Solid brick of clay or shalec. 6 4.9 3.8 2.7
1. Brick of clay
or shale
1-1.2 Hollow brick, not filled. 5.0 4.3 3.4 2.3
1. Brick of clay
or shale
1-1.3 Hollow brick unit wall, grout or filled with perlite vermiculite or expanded shale
aggregate.
6.6 5.5 4.4 3.0
1. Brick of clay
or shale
1-2.1 4" nominal thick units not less than 75 percent solid backed with a hat-shaped metal
furring channel3/4" thick formed from 0.021" sheet metal attached to the brick wall on
24" centers with approved fasteners, and1/2" Type X gypsum wallboard attached to the
metal furring strips with 1"-long Type S screws spaced 8" on center.
5d
2. Combination
of clay brick and
load-bearing hol-
low clay tile
2-1.1 4" solid brick and 4" tile (not less than 40 percent solid). 8
2. Combination
of clay brick and
load-bearing hol-
low clay tile
2-1.2
4" solid brick and 8" tile (not less than 40 percent solid).
12
3. Concrete
masonry units
3-1.1f, g
Expanded slag or pumice.
4.7 4.0 3.2 2.1
3. Concrete
masonry units
3-1.2f, g Expanded clay, shale or slate. 5.1 4.4 3.6 2.6
3. Concrete
masonry units
3-1.3f
Limestone, cinders or air-cooled slag.
5.9 5.0 4.0 2.7
3. Concrete
masonry units
3-1.4f, g Calcareous or siliceous gravel. 6.2 5.3 4.2 2.8
4. Solid con-
creteh, i
4-1.1 Siliceous aggregate concrete. 7.0 6.2 5.0 3.5
4. Solid con-
creteh, i
4-1.1 Carbonate aggregate concrete. 6.6 5.7 4.6 3.2
4. Solid con-
creteh, i
4-1.1 Sand-lightweight concrete. 5.4 4.6 3.8 2.7
4. Solid con-
creteh, i
4-1.1 Lightweight concrete. 5.1 4.4 3.6 2.5
5. Glazed or
unglazed facing
tile, nonload-
bearing
5-1.1 One 2" unit cored 15 percent maximum and one 4" unit cored 25 percent maximum with
3/4" mortar-filled collar joint. Unit positions reversed in alternate courses.
63/8
5. Glazed or
unglazed facing
tile, nonload-
bearing
5-1.2 One 2" unit cored 15 percent maximum and one 4" unit cored 40 percent maximum with
3/4" mortar-filled collar joint. Unit positions side with3/4" gypsum plaster. Two wythes
tied together every fourth course with No. 22 gage corrugated metal ties.
63/4
5. Glazed or
unglazed facing
tile, nonload-
bearing
5-1.3 One unit with three cells in wall thickness, cored 29 percent maximum. 6
5. Glazed or
unglazed facing
tile, nonload-
bearing
5-1.4 One 2" unit cored 22 percent maximum and one 4" unit cored 41 percent maximum with
1/4" mortar-filled collar joint. Two wythes tied together every third course with 0.030"
(No. 22 galvanized sheet steel gage) corrugated metal ties.
6
5. Glazed or
unglazed facing
tile, nonload-
bearing
5-1.5 One 4" unit cored 25 percent maximum with3/4" gypsum plaster on one side. 43/4
5. Glazed or
unglazed facing
tile, nonload-
bearing
5-1.6 One 4" unit with two cells in wall thickness, cored 22 percent maximum. 4
5. Glazed or
unglazed facing
tile, nonload-
bearing
5-1.7 One 4" unit cored 30 percent maximum with3/4" vermiculite gypsum plaster on one side. 41/2
5. Glazed or
unglazed facing
tile, nonload-
bearing
5-1.8 One 4" unit cored 39 percent maximum with3/4" gypsum plaster on one side. 41/2

(continued)

248 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(2)—continued RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONS a, o, p

MATERIAL ITEM
NUMBER
CONSTRUCTION MINIMUM FINISHED
THICKNESS FACE-TO-
FACEb (inches)
MATERIAL ITEM
NUMBER
CONSTRUCTION **4 **
hours
3
hours
**2 **
hours
**1 **
hour
6. Solid gypsum
plaster
6-1.1 3/4" by 0.055" (No. 16 carbon sheet steel gage) vertical cold-rolled channels, 16" on
center with 2.6-pound flat metal lath applied to one face and tied with 0.049" (No. 18
B.W. gage) wire at 6" spacing. Gypsum plaster each side mixed 1:2 by weight, gypsum
to sand aggregate.
2d
6. Solid gypsum
plaster
6-1.2 3/4" by 0.05" (No. 16 carbon sheet steel gage) cold-rolled channels 16" on center with
metal lath applied to one face and tied with 0.049" (No. 18 B.W. gage) wire at 6"
spacing. Perlite or vermiculite gypsum plaster each side. For three-coat work, the
plaster mix for the second coat shall not exceed 100 pounds of gypsum to 21/2 cubic feet
of aggregate for the 1-hour system.
21/2
d
2d
6. Solid gypsum
plaster
6-1.3 3/4" by 0.055" (No. 16 carbon sheet steel gage) vertical cold-rolled channels, 16" on
center with3/8" gypsum lath applied to one face and attached with sheet metal clips.
Gypsum plaster each side mixed 1:2 by weight, gypsum to sand aggregate.
2d
6. Solid gypsum
plaster
6-2.1 Studless with1/2" full-length plain gypsum lath and gypsum plaster each side. Plaster
mixed 1:1 for scratch coat and 1:2 for brown coat, by weight, gypsum to sand
aggregate.
2d
6. Solid gypsum
plaster
6-2.2 Studless with1/2" full-length plain gypsum lath and perlite or vermiculite gypsum
plaster each side.
21/2
d
2d
6. Solid gypsum
plaster
6-2.3 Studless partition with3/8" rib metal lath installed vertically adjacent edges tied 6" on
center with No. 18 gage wire ties, gypsum plaster each side mixed 1:2 by weight,
gypsum to sand aggregate.
2d
7. Solid perlite
and Portland
cement
7-1.1 Perlite mixed in the ratio of 3 cubic feet to 100 pounds of Portland cement and machine
applied to stud side of 11/2" mesh by 0.058-inch (No. 17 B.W. gage) paper-backed
woven wire fabric lath wire-tied to 4"-deep steel trussed wirej studs 16" on center. Wire
ties of 0.049" (No. 18 B.W. gage) galvanized steel wire 6" on center vertically.
31/8
d
8. Solid neat
wood fibered
gypsum plaster
8-1.1 3/4" by 0.055-inch (No. 16 carbon sheet steel gage) cold-rolled channels, 12" on center
with 2.5-pound flat metal lath applied to one face and tied with 0.049" (No. 18 B.W.
gage) wire at 6" spacing. Neat gypsum plaster applied each side.
2d
9. Solid wall-
board partition
9-1.1 One full-length layer1/2" Type X gypsum wallboarde laminated to each side of 1" full-
length V-edge gypsum coreboard with approved laminating compound. Vertical joints
of face layer and coreboard staggered not less than 3".
2d
10. Hollow (stud-
less) gypsum
wallboard parti-
tion
10-1.1 One full-length layer of5/8" Type X gypsum wallboarde attached to both sides of wood
or metal top and bottom runners laminated to each side of 1"× 6" full-length gypsum
coreboard ribs spaced 2" on center with approved laminating compound. Ribs centered
at vertical joints of face plies and joints staggered 24" in opposing faces. Ribs may be
recessed 6" from the top and bottom.
21/4
d
10. Hollow (stud-
less) gypsum
wallboard parti-
tion
10-1.2 1" regular gypsum V-edge full-length backing board attached to both sides of wood or
metal top and bottom runners with nails or 15/8" drywall screws at 24" on center.
Minimum width of runners 15/8". Face layer of1/2" regular full-length gypsum
wallboard laminated to outer faces of backing board with approved laminating
compound.
45/8
d

(continued)

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(2) —continued RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONS a, o, p

MATERIAL ITEM
NUMBER
CONSTRUCTION MINIMUM FINISHED
THICKNESS FACE-TO-
FACEb (inches)
MATERIAL ITEM
** NUMBER**
CONSTRUCTION **4 **
hours
3
hours
**2 **
hours
**1 **
hour
11. Noncombusti-
ble studs-interior
partition with
plaster each side
11-1.1 31/4" × 0.044" (No. 18 carbon sheet steel gage) steel studs spaced 24" on center.5/8"
gypsum plaster on metal lath each side mixed 1:2 by weight, gypsum to sand aggregate.
43/4
d
11. Noncombusti-
ble studs-interior
partition with
plaster each side
11-1.2 33 /8" × 0.055" (No. 16 carbon sheet steel gage) approved nailablek studs spaced 24" on
center.5/8" neat gypsum wood-fibered plaster each side over3/8" rib metal lath nailed to
studs with 6d common nails, 8" on center. Nails driven 11/4" and bent over.
55/8
11. Noncombusti-
ble studs-interior
partition with
plaster each side
11-1.3 4" × 0.044" (No. 18 carbon sheet steel gage) channel-shaped steel studs at 16" on center.
On each side approved resilient clips pressed onto stud flange at 16" vertical spacing,1/4"
pencil rods snapped into or wire tied onto outer loop of clips, metal lath wire-tied to
pencil rods at 6" intervals, 1" perlite gypsum plaster, each side.
75/8
d
11. Noncombusti-
ble studs-interior
partition with
plaster each side
11-1.4 21/2" × 0.044" (No. 18 carbon sheet steel gage) steel studs spaced 16" on center. Wood
fibered gypsum plaster mixed 1:1 by weight gypsum to sand aggregate applied on3/4-
pound metal lath wire tied to studs, each side.3/4" plaster applied over each face,
including finish coat.
41/4
d
12. Wood studs-
interior partition
with plaster each
side
12-1.1l, m 2" × 4" wood studs 16" on center with5/8" gypsum plaster on metal lath. Lath attached
by 4d common nails bent over or No. 14 gage by 11/4" by3/4" crown width staples
spaced 6" on center. Plaster mixed 1:11/2 for scratch coat and 1:3 for brown coat, by
weight, gypsum to sand aggregate.
51/8
12. Wood studs-
interior partition
with plaster each
side
12-1.2l 2" × 4" wood studs 16" on center with metal lath and7/8" neat wood-fibered gypsum
plaster each side. Lath attached by 6d common nails, 7" on center. Nails driven 11/4" and
bent over.
51/2
d
12. Wood studs-
interior partition
with plaster each
side
12-1.3l 2" × 4" wood studs 16" on center with3/8" perforated or plain gypsum lath and1/2"
gypsum plaster each side. Lath nailed with 11/8" by No. 13 gage by19/64" head
plasterboard blued nails, 4" on center. Plaster mixed 1:2 by weight, gypsum to sand
aggregate.
51/4
12. Wood studs-
interior partition
with plaster each
side
12-1.4l 2" × 4" wood studs 16" on center with3/8" Type X gypsum lath and1/2" gypsum plaster
each side. Lath nailed with 11/8" by No. 13 gage by 19/64" head plasterboard blued nails,
5" on center. Plaster mixed 1:2 by weight, gypsum to sand aggregate.
51/4
13. Noncombusti-
ble studs-interior
partition with gyp-
sum wallboard
each side
13-1.1 0.018" (No. 25 carbon sheet steel gage) channel-shaped studs 24" on center with one
full-length layer of5/8" Type X gypsum wallboarde applied vertically attached with 1"-
long No. 6 drywall screws to each stud. Screws are 8" on center around the perimeter
and 12" on center on the intermediate stud. Where applied horizontally, the Type X
gypsum wallboard shall be attached to 35/8" studs and the horizontal joints shall be
staggered with those on the opposite side. Screws for the horizontal application shall be
8" on center at vertical edges and 12" on center at intermediate studs.
27/8
d
13. Noncombusti-
ble studs-interior
partition with gyp-
sum wallboard
each side
13-1.2 0.018" (No. 25 carbon sheet steel gage) channel-shaped studs 25" on center with two
full-length layers of1/2" Type X gypsum wallboarde applied vertically each side. First
layer attached with 1"-long, No. 6 drywall screws, 8" on center around the perimeter
and 12" on center on the intermediate stud. Second layer applied with vertical joints
offset one stud space from first layer using 15/8" long, No. 6 drywall screws spaced 9" on
center along vertical joints, 12" on center at intermediate studs and 24" on center along
top and bottom runners.
35/8
d
13. Noncombusti-
ble studs-interior
partition with gyp-
sum wallboard
each side
13-1.3 0.055" (No. 16 carbon sheet steel gage) approved nailable metal studse24" on center
with full-length5/8" Type X gypsum wallboarde applied vertically and nailed 7" on
center with 6d cement-coated common nails. Approved metal fastener grips used with
nails at vertical butt joints along studs.
47/8

(continued)

250 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(2)—continued RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONS a, o, p

MATERIAL ITEM
NUMBER
CONSTRUCTION MINIMUM FINISHED
THICKNESS FACE-TO-FACEb
(inches)
MATERIAL ITEM
** NUMBER**
CONSTRUCTION **4 **
hours
3
hours
**2 **
hours
**1 **
hour
14. Wood
studs-interior
partition with
gypsum
wallboard each
side
14-1.1h, m 2" × 4" wood studs 16" on center with two layers of3/8" regular gypsum
wallboarde each side, 4d coolern or wallboardn nails at 8" on center first layer, 5d
coolern or wallboardn nails at 8" on center second layer with laminating compound
between layers, joints staggered. First layer applied full length vertically, second
layer applied horizontally or vertically.
5
14. Wood
studs-interior
partition with
gypsum
wallboard each
side
14-1.2l, m 2" × 4" wood studs 16" on center with two layers1/2" regular gypsum wallboarde
applied vertically or horizontally each sidek, joints staggered. Nail base layer with
5d coolern or wallboardn nails at 8" on center face layer with 8d coolern or wallboardn
nails at 8" on center.
51/2
14. Wood
studs-interior
partition with
gypsum
wallboard each
side
14-1.3l, m 2" × 4" wood studs 24" on center with5/8" Type X gypsum wallboarde applied
vertically or horizontally nailed with 6d coolern or wallboardn nails at 7" on center
with end joints on nailing members. Stagger joints each side.
43/4
14. Wood
studs-interior
partition with
gypsum
wallboard each
side
14-1.4l 2" × 4" fire-retardant-treated wood studs spaced 24" on center with one layer of
5/8" Type X gypsum wallboarde applied with face paper grain (long dimension)
parallel to studs. Wallboard attached with 6d coolern or wallboardn nails at 7" on
center.
43/4
d
14. Wood
studs-interior
partition with
gypsum
wallboard each
side
14-1.5l, m 2" × 4" wood studs 16" on center with two layers5/8" Type X gypsum wallboarde
each side. Base layers applied vertically and nailed with 6d coolern or wallboardn
nails at 9" on center. Face layer applied vertically or horizontally and nailed with 8d
coolern or wallboardn nails at 7" on center. For nail-adhesive application, base layers
are nailed 6" on center. Face layers applied with coating of approved wallboard
adhesive and nailed 12" on center.
6
14. Wood
studs-interior
partition with
gypsum
wallboard each
side
14-1.6l 2" × 3" fire-retardant-treated wood studs spaced 24" on center with one layer of
5/8" Type X gypsum wallboarde applied with face paper grain (long dimension) at
right angles to studs. Wallboard attached with 6d cement-coated box nails spaced 7"
on center.
35/8
d
15. Exterior or
interior walls
(continued)
15-1.1l, m Exterior surface with3/4" drop siding over1/2" gypsum sheathing on 2" × 4" wood
studs at 16" on center, interior surface treatment as required for 1-hour-rated exterior
or interior 2" × 4" wood stud partitions. Gypsum sheathing nailed with 13/4" by No.
11 gage by7/16" head galvanized nails at 8" on center. Siding nailed with 7d
galvanized smooth box nails.
Varies
15. Exterior or
interior walls
(continued)
15-1.2l, m 2" × 4" wood studs 16" on center with metal lath and3/4" cement plaster on each
side. Lath attached with 6d common nails 7" on center driven to 1" minimum
penetration and bent over. Plaster mix 1:4 for scratch coat and 1:5 for brown coat,
by volume, cement to sand.
53/8
15. Exterior or
interior walls
(continued)
15-1.3l, m 2" × 4" wood studs 16" on center with7/8" cement plaster (measured from the face of
studs) on the exterior surface with interior surface treatment as required for interior
wood stud partitions in this table. Plaster mix 1:4 for scratch coat and 1:5 for brown
coat, by volume, cement to sand.
Varies
15. Exterior or
interior walls
(continued)
15-1.4 35/8" No. 16 gage noncombustible studs 16" on center with7/8" cement plaster
(measured from the face of the studs) on the exterior surface with interior surface
treatment as required for interior, nonbearing, noncombustible stud partitions in this
table. Plaster mix 1:4 for scratch coat and 1:5 for brown coat, by volume, cement to
sand.
Variesd

(continued)

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(2)—continued RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONS a, o, p

MATERIAL ITEM
NUMBER
CONSTRUCTION MINIMUM FINISHED
THICKNESS FACE-TO-
FACEb (inches)
MATERIAL ITEM
** NUMBER**
CONSTRUCTION **4 **
hours
3
hours
**2 **
hours
**1 **
hour
15. Exterior or
interior walls
(continued)
15-1.5m 21/4" × 33/4" clay face brick with cored holes over1/2" gypsum sheathing on exterior
surface of 2" × 4" wood studs at 16" on center and two layers5/8" Type X gypsum
wallboarde on interior surface. Sheathing placed horizontally or vertically with vertical
joints over studs nailed 6" on center with 13/4" × No. 11 gage by7/16" head galvanized
nails. Inner layer of wallboard placed horizontally or vertically and nailed 8" on center
with 6d coolern or wallboardn nails. Outer layer of wallboard placed horizontally or
vertically and nailed 8" on center with 8d coolern or wallboardn nails. Joints staggered
with vertical joints over studs. Outer layer joints taped and finished with compound. Nail
heads covered with joint compound. 0.035 inch (No. 20 galvanized sheet gage)
corrugated galvanized steel wall ties3/4" by 65/8" attached to each stud with two 8d
coolern or wallboardn nails every sixth course of bricks.
10
15. Exterior or
interior walls
(continued)
15-1.6l, m 2" × 6" fire-retardant-treated wood studs 16" on center. Interior face has two layers of
5/8" Type X gypsum with the base layer placed vertically and attached with 6d box
nails 12" on center. The face layer is placed horizontally and attached with 8d box nails
8" on center at joints and 12" on center elsewhere. The exterior face has a base layer of
5/8" Type X gypsum sheathing placed vertically with 6d box nails 8" on center at joints
and 12" on center elsewhere. An approved building paper is next applied, followed by
self-furred exterior lath attached with 21/2", No. 12 gage galvanized roofing nails with a
3/8" diameter head and spaced 6" on center along each stud. Cement plaster consisting
of a1/2" brown coat is then applied. The scratch coat is mixed in the proportion of 1:3
by weight, cement to sand with 10 pounds of hydrated lime and 3 pounds of approved
additives or admixtures per sack of cement. The brown coat is mixed in the proportion
of 1:4 by weight, cement to sand with the same amounts of hydrated lime and approved
additives or admixtures used in the scratch coat.
81/4
15. Exterior or
interior walls
(continued)
15-1.7l, m 2" × 6" wood studs 16" on center. The exterior face has a layer of5/8" Type X gypsum
sheathing placed vertically with 6d box nails 8" on center at joints and 12" on center
elsewhere. An approved building paper is next applied, followed by 1" by No. 18 gage
self-furred exterior lath attached with 8d by 21/2" long galvanized roofing nails spaced 6"
on center along each stud. Cement plaster consisting of a1/2" scratch coat, a bonding
agent and a1/2" brown coat and a finish coat is then applied. The scratch coat is mixed in
the proportion of 1:3 by weight, cement to sand with 10 pounds of hydrated lime and 3
pounds of approved additives or admixtures per sack of cement. The brown coat is mixed
in the proportion of 1:4 by weight, cement to sand with the same amounts of hydrated
lime and approved additives or admixtures used in the scratch coat. The interior is
covered with3/8" gypsum lath with 1" hexagonal mesh of 0.035 inch (No. 20 B.W. gage)
woven wire lath furred out5/16" and 1" perlite or vermiculite gypsum plaster. Lath nailed
with 11/8" by No. 13 gage by19/64" head plasterboard glued nails spaced 5" on center.
Mesh attached by 13/4" by No. 12 gage by3/8" head nails with3/8" furrings, spaced 8" on
center. The plaster mix shall not exceed 100 pounds of gypsum to 21/2 cubic feet of
aggregate.
83/8

(continued)

252 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(2)—continued RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONS a, o, p

MATERIAL ITEM
NUMBER
CONSTRUCTION MINIMUM FINISHED
THICKNESS FACE-TO-
FACEb (inches)
MATERIAL ITEM
** NUMBER**
CONSTRUCTION **4 **
hours
3
hours
**2 **
hours
**1 **
hour
15. Exterior or
interior walls
(continued)
15-1.8l, m 2" × 6" wood studs 16" on center. The exterior face has a layer of5/8" Type X gypsum
sheathing placed vertically with 6d box nails 8" on center at joints and 12" on center
elsewhere. An approved building paper is next applied, followed by 11/2" by No. 17 gage
self-furred exterior lath attached with 8d by 21/2" long galvanized roofing nails spaced 6"
on center along each stud. Cement plaster consisting of a1/2" scratch coat, and a1/2"
brown coat is then applied. The plaster may be placed by machine. The scratch coat is
mixed in the proportion of 1:4 by weight, plastic cement to sand. The brown coat is
mixed in the proportion of 1:5 by weight, plastic cement to sand. The interior is covered
with3/8" gypsum lath with 1" hexagonal mesh of No. 20 gage woven wire lath furred out
5/16" and 1" perlite or vermiculite gypsum plaster. Lath nailed with 11/8" by No. 13 gage
by19/64" head plasterboard glued nails spaced 5" on center. Mesh attached by 13/4" by No.
12 gage by3/8" head nails with3/8" furrings, spaced 8" on center. The plaster mix shall
not exceed 100 pounds of gypsum to 21/2 cubic feet of aggregate.
83/8
15. Exterior or
interior walls
(continued)
15-1.9 4" No. 18 gage, nonload-bearing metal studs, 16" on center, with 1" Portland cement
lime plaster (measured from the back side of the3/4-pound expanded metal lath) on the
exterior surface. Interior surface to be covered with 1" of gypsum plaster on3/4-pound
expanded metal lath proportioned by weight-1:2 for scratch coat, 1:3 for brown, gypsum
to sand. Lath on one side of the partition fastened to1/4" diameter pencil rods supported
by No. 20 gage metal clips, located 16" on center vertically, on each stud. 3" thick min-
eral fiber insulating batts friction fitted between the studs.
61/2
d
15. Exterior or
interior walls
(continued)
15-1.10 Steel studs 0.060" thick, 4" deep or 6" at 16" or 24" centers, with1/2" Glass Fiber Rein-
forced Concrete (GFRC) on the exterior surface. GFRC is attached with flex anchors at
24" on center, with 5" leg welded to studs with two1/2"-long flare-bevel welds, and 4"
foot attached to the GFRC skin with5/8" thick GFRC bonding pads that extend 21/2"
beyond the flex anchor foot on both sides. Interior surface to have two layers of1/2" Type
X gypsum wallboard.e The first layer of wallboard to be attached with 1"-long Type S
buglehead screws spaced 24" on center and the second layer is attached with 15/8"-long
Type S screws spaced at 12" on center. Cavity is to be filled with 5" of 4 pcf (nominal)
mineral fiber batts. GFRC has 11/2" returns packed with mineral fiber and caulked on the
exterior.
61/2
15. Exterior or
interior walls
(continued)
15-1.11 Steel studs 0.060" thick, 4" deep or 6" at 16" or 24" centers, respectively, with1/2" Glass
Fiber Reinforced Concrete (GFRC) on the exterior surface. GFRC is attached with flex
anchors at 24" on center, with 5" leg welded to studs with two1/2"-long flare-bevel
welds, and 4" foot attached to the GFRC skin with5/8" -thick GFRC bonding pads that
extend 21/2" beyond the flex anchor foot on both sides. Interior surface to have one layer
of5/8" Type X gypsum wallboarde, attached with 11/4"-long Type S buglehead screws
spaced 12" on center. Cavity is to be filled with 5" of 4 pcf (nominal) mineral fiber batts.
GFRC has 11/2" returns packed with mineral fiber and caulked on the exterior.
61/8
15. Exterior or
interior walls
(continued)
15-1.12q 2" × 6" wood studs at 16" with double top plates, single bottom plate; interior and exte-
rior sides covered with5/8" Type X gypsum wallboard, 4 wide, applied horizontally or
vertically with vertical joints over studs, and fastened with 21/4" Type S drywall screws,
spaced 12" on center. Cavity to be filled with 51/2" mineral wool insulation.
63/4

(continued)

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(2)—continued RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONS a, o, p
MATERIAL ITEM
** NUMBER**
CONSTRUCTION MINIMUM FINISHED
THICKNESS FACE-TO-
FACEb (inches)
MINIMUM FINISHED
THICKNESS FACE-TO-
FACEb (inches)
MINIMUM FINISHED
THICKNESS FACE-TO-
FACEb (inches)
MINIMUM FINISHED
THICKNESS FACE-TO-
FACEb (inches)
MATERIAL ITEM
** NUMBER**
CONSTRUCTION **4 **
hours
3
hours
**2 **
hours
**1 **
hour
15. Exterior or
interior walls
(continued)
15-1.13q 2" × 6" wood studs at 16" with double top plates, single bottom plate; interior and exterior
sides covered with5/8" Type X gypsum wallboard, 4 wide, applied vertically with all joints
over framing or blocking and fastened with 21/4" Type S drywall screws, spaced 12" on
center. R-19 mineral fiber insulation installed in stud cavity.
63/4
15. Exterior or
interior walls
(continued)
15-1.14q 2" × 6" wood studs at 16" with double top plates, single bottom plate; interior and exterior
sides covered with5/8" Type X gypsum wallboard, 4 wide, applied horizontally or verti-
cally with vertical joints over studs, and fastened with 21/4" Type S drywall screws, spaced
7" on center.
63/4
15. Exterior or
interior walls
(continued)
15-1.15q 2" × 4" wood studs at 16" with double top plates, single bottom plate; interior and exterior
sides covered with5/8" Type X gypsum wallboard and sheathing, respectively, 4 wide,
applied horizontally or vertically with vertical joints over studs, and fastened with 21/4"
Type S drywall screws, spaced 12" on center. Cavity to be filled with 31/2" mineral wool
insulation.
43/4
15. Exterior or
interior walls
(continued)
15-1.16q 2" x 6" wood studs at 24" centers with double top plates, single bottom plate; interior and
exterior side covered with two layers of 5/8" Type X gypsum wallboard, 4' wide, applied
horizontally with vertical joints over studs. Base layer fastened with 21/4" Type S drywall
screws, spaced 24" on center and face layer fastened with Type S drywall screws, spaced
8" on center, wallboard joints covered with paper tape and joint compound, fastener heads
covered with joint compound. Cavity to be filled with 51/2" mineral wool insulation.
8
15. Exterior or
interior walls
(continued)
15-2.1d 35/8" No. 16 gage steel studs at 24" on center or 2" × 4" wood studs at 24" on center. Metal
lath attached to the exterior side of studs with minimum 1" long No. 6 drywall screws at 6"
on center and covered with minimum3/4" thick Portland cement plaster. Thin veneer brick
units of clay or shale complying with ASTM C1088, Grade TBS or better, installed in run-
ning bond in accordance with Section 1405.10. Combined total thickness of the Portland
cement plaster, mortar and thin veneer brick units shall be not less than 13/4". Interior side
covered with one layer of5/8" thick Type X gypsum wallboard attached to studs with 1"
long No. 6 drywall screws at 12" on center.
6
15. Exterior or
interior walls
(continued)
15-2.2 d 35/8" No. 16 gage steel studs at 24" on center or 2" × 4" wood studs at 24" on center. Metal
lath attached to the exterior side of studs with minimum 1" long No. 6 drywall screws at 6"
on center and covered with minimum3/4" thick Portland cement plaster. Thin veneer brick
units of clay or shale complying with ASTM C1088, Grade TBS or better, installed in run-
ning bond in accordance with Section 1405.10. Combined total thickness of the Portland
cement plaster, mortar and thin veneer brick units shall be not less than 2". Interior side
covered with two layers of5/8" thick Type X gypsum wallboard. Bottom layer attached to
studs with 1" long No. 6 drywall screws at 24" on center. Top layer attached to studs with
15/8" long No. 6 drywall screws at 12" on center.
67/8
15. Exterior or
interior walls
(continued)
15-2.3 d 35/8" No. 16 gage steel studs at 16" on center or 2"× 4" wood studs at 16" on center. Where
metal lath is used, attach to the exterior side of studs with minimum 1" long No. 6 drywall
screws at 6" on center. Brick units of clay or shale not less than 25/8" thick complying with
ASTM C216 installed in accordance with Section 1405.6 with a minimum 1" airspace.
Interior side covered with one layer of5/8" thick Type X gypsum wallboard attached to
studs with 1" long No. 6 drywall screws at 12" on center.
77/8

(continued)

254 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(2)—continued RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONS a, o, p

MATERIAL ITEM
NUMBER
CONSTRUCTION MINIMUM FINISHED
THICKNESS FACE-TO-
FACEb (inches)
MATERIAL ITEM
NUMBER
CONSTRUCTION **4 **
hours
3
hours
**2 **
hours
**1 **
hour
15. Exterior or
interior walls
15-2.4d 35/8" No. 16 gage steel studs at 16" on center or 2" × 4" wood studs at 16" on center.
Where metal lath is used, attach to the exterior side of studs with minimum 1" long No.
6 drywall screws at 6" on center. Brick units of clay or shale not less than 25/8" thick
complying with ASTM C216 installed in accordance with Section 1405.6 with a
minimum 1" airspace. Interior side covered with two layers of5/8" thick Type X gypsum
wallboard. Bottom layer attached to studs with 1" long No. 6 drywall screws at 24" on
center. Top layer attached to studs with 15/8" long No. 6 drywall screws at 12" on center.
81/2
16. Exterior walls
rated for fire
resistance from
the inside only in
accordance with
Section 705.5.
16-1.1q 2" × 4" wood studs at 16" centers with double top plates, single bottom plate; interior
side covered with5/8" Type X gypsum wallboard, 4" wide, applied horizontally
unblocked, and fastened with 21/4" Type S drywall screws, spaced 12" on center,
wallboard joints covered with paper tape and joint compound, fastener heads covered
with joint compound. Exterior covered with3/8" wood structural panels, applied
vertically, horizontal joints blocked and fastened with 6d common nails (bright) — 12"
on center in the field, and 6" on center panel edges. Cavity to be filled with 31/2" mineral
wool insulation. Rating established for exposure from interior side only.
41/2
16. Exterior walls
rated for fire
resistance from
the inside only in
accordance with
Section 705.5.
16-1.2q 2" × 6" wood studs at 16" centers with double top plates, single bottom plate; interior
side covered with5/8" Type X gypsum wallboard, 4" wide, applied horizontally or
vertically with vertical joints over studs and fastened with 21/4" Type S drywall screws,
spaced 12" on center, wallboard joints covered with paper tape and joint compound,
fastener heads covered with joint compound, exterior side covered with7/16" wood
structural panels fastened with 6d common nails (bright) spaced 12" on center in the
field and 6" on center along the panel edges. Cavity to be filled with 51/2" mineral wool
insulation. Rating established from the gypsum-covered side only.
69/16
16. Exterior walls
rated for fire
resistance from
the inside only in
accordance with
Section 705.5.
16-1.3q 2" × 6" wood studs at 16" centers with double top plates, single bottom plates; interior
side covered with5/8" Type X gypsum wallboard, 4" wide, applied vertically with all
joints over framing or blocking and fastened with 21/4" Type S drywall screws spaced 7"
on center. Joints to be covered with tape and joint compound. Exterior covered with3/8"
wood structural panels, applied vertically with edges over framing or blocking and
fastened with 6d common nails (bright) at 12" on center in the field and 6" on center on
panel edges. R-19 mineral fiber insulation installed in stud cavity. Rating established
from the gypsum-covered side only.
61/2

For SI: 1 inch = 25.4 mm, 1 square inch = 645.2 mm 2, 1 cubic foot = 0.0283 m 3 . a. Staples with equivalent holding power and penetration shall be permitted to be used as alternate fasteners to nails for attachment to wood framing. b. Thickness shown for brick and clay tile is nominal thicknesses unless plastered, in which case thicknesses are net. Thickness shown for concrete masonry and

clay masonry is equivalent thickness defined in Section 722.3.1 for concrete masonry and Section 722.4.1.1 for clay masonry. Where all cells are solid grouted or filled with silicone-treated perlite loose-fill insulation; vermiculite loose-fill insulation; or expanded clay, shale or slate lightweight aggregate, the equivalent thickness shall be the thickness of the block or brick using specified dimensions as defined in Chapter 21. Equivalent thickness shall include the thickness of applied plaster and lath or gypsum wallboard, where specified. c. For units in which the net cross-sectional area of cored brick in any plane parallel to the surface containing the cores is not less than 75 percent of the gross

cross-sectional area measured in the same plane. d. Shall be used for nonbearing purposes only. e. For all of the construction with gypsum wallboard described in this table, gypsum base for veneer plaster of the same size, thickness and core type shall be

permitted to be substituted for gypsum wallboard, provided that attachment is identical to that specified for the wallboard, and the joints on the face layer are reinforced and the entire surface is covered with not less than 1 /16-inch gypsum veneer plaster. f. The fire-resistance time period for concrete masonry units meeting the equivalent thicknesses required for a 2-hour fire-resistance rating in Item 3, and having

a thickness of not less than 7 5 /8 inches is 4 hours where cores that are not grouted are filled with silicone-treated perlite loose-fill insulation; vermiculite loosefill insulation; or expanded clay, shale or slate lightweight aggregate, sand or slag having a maximum particle size of 3 /8 inch. g. The fire-resistance rating of concrete masonry units composed of a combination of aggregate types or where plaster is applied directly to the concrete

masonry shall be determined in accordance with ACI 216.1/TMS 0216. Lightweight aggregates shall have a maximum combined density of 65 pounds per cubic foot.

(continued)

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(2)—continued RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONS a, o,

h. See Note b. The equivalent thickness shall be permitted to include the thickness of cement plaster or 1.5 times the thickness of gypsum plaster applied in

accordance with the requirements of Chapter 25. i. Concrete walls shall be reinforced with horizontal and vertical temperature reinforcement as required by Chapter 19. j. Studs are welded truss wire studs with 0.18 inch (No. 7 B.W. gage) flange wire and 0.18 inch (No. 7 B.W. gage) truss wires. k. Nailable metal studs consist of two channel studs spot welded back to back with a crimped web forming a nailing groove. l. Wood structural panels shall be permitted to be installed between the fire protection and the wood studs on either the interior or exterior side of the wood

frame assemblies in this table, provided that the length of the fasteners used to attach the fire protection is increased by an amount not less than the thickness of the wood structural panel. m.For studs with a slenderness ratio, le/d, greater than 33, the design stress shall be reduced to 78 percent of allowable F c . For studs with a slenderness ratio,

le/d, not exceeding 33, the design stress shall be reduced to 78 percent of the adjusted stress F c calculated for studs having a slenderness ratio le/d of 33. n. For properties of cooler or wallboard nails, see ASTM C514, ASTM C547 or ASTM F1667. o. Generic fire-resistance ratings (those not designated as PROPRIETARY* in the listing) in the GA 600 shall be accepted as if herein listed. p. NCMA TEK 5-8A shall be permitted for the design of fire walls. q. The design stress of studs shall be equal to not more than 100 percent of the allowable F' c calculated in accordance with Section 2306.

TABLE 721.1(3)

MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS a, q

FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION THICKNESS OF FLOOR
OR ROOF SLAB
(inches)
MINIMUM THICKNESS
OF CEILING
(inches)
FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION **4 **
hours
**3 **
hours
**2 **
hours
**1 **
hour
**4 **
hours
**3 **
hours
**2 **
hours
1
** hour**
1. Siliceous aggre-
gate concrete
1-1.1 Slab (ceiling not required). Minimum cover over
nonprestressed reinforcement shall be not less than3/4" b.
7.0 6.2 5.0 3.5
2. Carbonate
aggregate concrete
2-1.1 2-1.1 6.6 5.7 4.6 3.2
3. Sand-light-
weight concrete
3-1.1 3-1.1 5.4 4.6 3.8 2.7
4. Lightweight
concrete
4-1.1 4-1.1 5.1 4.4 3.6 2.5
5. Reinforced
concrete
5-1.1 Slab with suspended ceiling of vermiculite gypsum plaster
over metal lath attached to3/4" cold-rolled channels spaced
12" on center. Ceiling located 6" minimum below joists.
3 2 1 3/4
5. Reinforced
concrete
5-2.1 3/8" Type X gypsum wallboardc attached to 0.018 inch (No.
25 carbon sheet steel gage) by7/8" deep by 25/8" hat-shaped
galvanized steel channels with 1"-long No. 6 screws. The
channels are spaced 24" on center, span 35" and are
supported along their length at 35" intervals by 0.033" (No.
21 galvanized sheet gage) galvanized steel flat strap
hangers having formed edges that engage the lips of the
channel. The strap hangers are attached to the side of the
concrete joists with5/32" by 11/4" long power-driven
fasteners. The wallboard is installed with the long
dimension perpendicular to the channels. End joints occur
on channels and supplementary channels are installed
parallel to the main channels, 12" each side, at end joint
occurrences. The finished ceiling is located approximately
12" below the soffit of the floor slab.
21/2 5/8

(continued)

256 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(3)—continued MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS a, q

FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION THICKNESS OF FLOOR
OR ROOF SLAB
(inches)
MINIMUM THICKNESS
OF CEILING
(inches)
FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION **4 **
hours
**3 **
hours
**2 **
hours
**1 **
hour
**4 **
hours
**3 **
hours
**2 **
hours
1
** hour**
6. Steel joists con-
structed with a
poured reinforced
concrete slab on
metal lath forms or
steel form unitsd, e
6-1.1 Gypsum plaster on metal lath attached to the bottom cord
with single No. 16 gage or doubled No. 18 gage wire ties
spaced 6" on center. Plaster mixed 1:2 for scratch coat, 1:3
for brown coat, by weight, gypsum-to-sand aggregate for 2-
hour system. For 3-hour system plaster is neat.
21/2 21/4 3/4 5/8
6. Steel joists con-
structed with a
poured reinforced
concrete slab on
metal lath forms or
steel form unitsd, e
6-2.1 Vermiculite gypsum plaster on metal lath attached to the
bottom chord with single No.16 gage or doubled 0.049-
inch (No. 18 B.W. gage) wire ties 6" on center.
2 5/8
6. Steel joists con-
structed with a
poured reinforced
concrete slab on
metal lath forms or
steel form unitsd, e
6-3.1 Cement plaster over metal lath attached to the bottom chord
of joists with single No. 16 gage or doubled 0.049" (No. 18
B.W. gage) wire ties spaced 6" on center. Plaster mixed 1:2
for scratch coat, 1:3 for brown coat for 1-hour system and
1:1 for scratch coat, 1:11/2 for brown coat for 2-hour sys-
tem, by weight, cement to sand.
2 5/8
f
6. Steel joists con-
structed with a
poured reinforced
concrete slab on
metal lath forms or
steel form unitsd, e
6-4.1 Ceiling of5/8" Type X wallboardc attached to7/8" deep by
25/8" by 0.021 inch (No. 25 carbon sheet steel gage) hat-
shaped furring channels 12" on center with 1" long No. 6
wallboard screws at 8" on center. Channels wire tied to bot-
tom chord of joists with doubled 0.049 inch (No. 18 B.W.
gage) wire or suspended below joists on wire hangers.g
21/2 5/8
6. Steel joists con-
structed with a
poured reinforced
concrete slab on
metal lath forms or
steel form unitsd, e
6-5.1 Wood-fibered gypsum plaster mixed 1:1 by weight gypsum
to sand aggregate applied over metal lath. Lath tied 6" on
center to3/4" channels spaced 131/2" on center. Channels
secured to joists at each intersection with two strands of
0.049 inch (No. 18 B.W. gage) galvanized wire.
21/2 3/4
7. Reinforced con-
crete slabs and joists
with hollow clay tile
fillers laid end to
end in rows 21/2" or
more apart; rein-
forcement placed
between rows and
concrete cast around
and over tile.
7-1.1 5/8" gypsum plaster on bottom of floor or roof construction. 8h 5/8
7. Reinforced con-
crete slabs and joists
with hollow clay tile
fillers laid end to
end in rows 21/2" or
more apart; rein-
forcement placed
between rows and
concrete cast around
and over tile.
7-1.2 None 51/2
i
8. Steel joists con-
structed with a rein-
forced concrete slab
on top poured on a
1/2" deep steel deck.e
8-1.1 Vermiculite gypsum plaster on metal lath attached to3/4"
cold-rolled channels with 0.049" (No. 18 B.W. gage) wire
ties spaced 6" on center.
21/2
j
3/4

(continued)

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(3)—continued MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMSa, q
FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION THICKNESS OF FLOOR OR
ROOF SLAB
(inches)
THICKNESS OF FLOOR OR
ROOF SLAB
(inches)
THICKNESS OF FLOOR OR
ROOF SLAB
(inches)
THICKNESS OF FLOOR OR
ROOF SLAB
(inches)
MINIMUM THICKNESS OF
CEILING
** (inches)**
MINIMUM THICKNESS OF
CEILING
** (inches)**
MINIMUM THICKNESS OF
CEILING
** (inches)**
MINIMUM THICKNESS OF
CEILING
** (inches)**
FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION **4 **
hours
**3 **
hours
**2 **
hours
**1 **
hour
**4 **
hours
**3 **
hours
**2 **
hours
**1 **
hour
9. 3" deep cellular
steel deck with
concrete slab on
top. Slab thickness
measured to top.
9-1.1 Suspended ceiling of vermiculite gypsum plaster base coat
and vermiculite acoustical plaster on metal lath attached at
6" intervals to3/4" cold-rolled channels spaced 12" on
center and secured to 11/2" cold-rolled channels spaced 36"
on center with 0.065" (No. 16 B.W. gage) wire. 11/2"
channels supported by No. 8 gage wire hangers at 36" on
center. Beams within envelope and with a 21/2" airspace
between beam soffit and lath have a 4-hour rating.
21/2 11/8
k
10. 11/2"-deep steel
roof deck on steel
framing. Insulation
board, 30 pcf
density, composed
of wood fibers
with cement
binders of
thickness shown
bonded to deck
with unified
asphalt adhesive.
Covered with a
Class A or B roof
covering.
10-1.1 Ceiling of gypsum plaster on metal lath. Lath attached to
3/4" furring channels with 0.049" (No. 18 B.W. gage) wire
ties spaced 6" on center.3/4" channel saddle tied to 2"
channels with doubled 0.065" (No. 16 B.W. gage) wire
ties. 2" channels spaced 36" on center suspended 2" below
steel framing and saddle-tied with 0.165" (No. 8 B.W.
gage) wire. Plaster mixed 1:2 by weight, gypsum-to-sand
aggregate.
17/8 1 3/4
l
3/4
l
11. 11/2"-deep steel
roof deck on steel-
framing wood fiber
insulation board,
17.5 pcf density on
top applied over a
15-lb asphalt-
saturated felt.
Class A or B roof
covering.
11-1.1 Ceiling of gypsum plaster on metal lath. Lath attached to
3/4" furring channels with 0.049" (No. 18 B.W. gage) wire
ties spaced 6" on center.3/4" channels saddle tied to 2"
channels with doubled 0.065" (No. 16 B.W. gage) wire
ties. 2" channels spaced 36" on center suspended 2" below
steel framing and saddle tied with 0.165" (No. 8 B.W.
gage) wire. Plaster mixed 1:2 for scratch coat and 1:3 for
brown coat, by weight, gypsum-to-sand aggregate for 1-
hour system. For 2-hour system, plaster mix is 1:2 by
weight, gypsum-to-sand aggregate.
11/2 1 7/8
g
3/4
l

(continued)

258 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(3)—continued MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS a, q

FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION THICKNESS OF FLOOR
OR ROOF SLAB
(inches)
MINIMUM THICKNESS
OF CEILING
(inches)
FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION **4 **
hours
**3 **
hours
**2 **
hours
**1 **
hour
**4 **
hours
**3 **
hours
**2 **
hours
**1 **
hour
12. 11/2" deep steel
roof deck on steel-
framing insulation
of rigid board con-
sisting of expanded
perlite and fibers
impregnated with
integral asphalt
waterproofing; den-
sity 9 to 12 pcf
secured to metal
roof deck by1/2"
wide ribbons of
waterproof, cold-
process liquid adhe-
sive spaced 6"
apart. Steel joist or
light steel construc-
tion with metal roof
deck, insulation,
and Class A or B
built-up roof cover-
ing.e
12-1.1 Gypsum-vermiculite plaster on metal lath wire tied at 6"
intervals to3/4" furring channels spaced 12" on center and
wire tied to 2" runner channels spaced 32" on center.
Runners wire tied to bottom chord of steel joists.
1 7/8
13. Double wood
floor over wood
joists spaced 16" on
center.m, n
13-1.1 Gypsum plaster over3/8" Type X gypsum lath. Lath
initially applied with not less than four 11/8" by No. 13 gage
by19/64" head plasterboard blued nails per bearing.
Continuous stripping over lath along all joist lines.
Stripping consists of 3" wide strips of metal lath attached
by 11/2" by No. 11 gage by1/2" head roofing nails spaced 6"
on center. Alternate stripping consists of 3" wide 0.049"
diameter wire stripping weighing 1 pound per square yard
and attached by No.16 gage by 11/2" by3/4" crown width
staples, spaced 4" on center. Where alternate stripping is
used, the lath nailing shall consist of two nails at each end
and one nail at each intermediate bearing. Plaster mixed
1:2 by weight, gypsum-to-sand aggregate.
7/8
13. Double wood
floor over wood
joists spaced 16" on
center.m, n
13-1.2 Cement or gypsum plaster on metal lath. Lath fastened
with 11/2" by No. 11 gage by7/16" head barbed shank
roofing nails spaced 5" on center. Plaster mixed 1:2 for
scratch coat and 1:3 for brown coat, by weight, cement to
sand aggregate.
5/8
13. Double wood
floor over wood
joists spaced 16" on
center.m, n
13-1.3 Perlite or vermiculite gypsum plaster on metal lath secured
to joists with 11/2" by No. 11 gage by7/16" head barbed
shank roofing nails spaced 5" on center.
5/8
13. Double wood
floor over wood
joists spaced 16" on
center.m, n
13-1.4 1/2" Type X gypsum wallboardc nailed to joists with 5d
coolero or wallboardo nails at 6" on center. End joints of
wallboard centered on joists.
1/2

(continued)

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(3)—continued MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS a, q

FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION THICKNESS OF FLOOR
OR ROOF SLAB
(inches)
MINIMUM THICKNESS
OF CEILING
(inches)
FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION **4 **
hours
**3 **
hours
**2 **
hours
**1 **
hour
**4 **
hours
**3 **
hours
**2 **
hours
1
** hour**
14. Plywood
stressed skin panels
consisting of5/8" -
thick interior C-D
(exterior glue) top
stressed skin on 2" ×
6" nominal (mini-
mum) stringers.
Adjacent panel
edges joined with 8d
common wire nails
spaced 6" on center.
Stringers spaced 12"
maximum on center.
14-1.1 1/2" -thick wood fiberboard weighing 15 to 18 pounds per
cubic foot installed with long dimension parallel to string-
ers or3/8" C-D (exterior glue) plywood glued and/or nailed
to stringers. Nailing to be with 5d coolero or wallboardo
nails at 12" on center. Second layer of1/2" Type X gypsum
wallboardc applied with long dimension perpendicular to
joists and attached with 8d cooleroor wallboardo nails at 6"
on center at end joints and 8" on center elsewhere. Wall-
board joints staggered with respect to fiberboard joints.
1
15. Vermiculite con-
crete slab propor-
tioned 1:4 (Portland
cement to vermicu-
lite aggregate) on a
11/2" -deep steel
deck supported on
individually pro-
tected steel framing.
Maximum span of
deck 6-10" where
deck is less than
0.019 inch (No. 26
carbon steel sheet
gage) or greater.
Slab reinforced with
4" × 8" 0.109/0.083"
(No.12/14B.W. gage)
welded wire mesh.
15-1.1 None 3j
16. Perlite concrete
slab proportioned
1:6 (Portland cement
to perlite aggregate)
on a 11/4" -deep steel
deck supported on
individually pro-
tected steel framing.
Slab reinforced with
4" × 8" 0.109/0.083"
(No.12/14B.W. gage)
welded wire mesh.
16-1.1 None 31/2
j

(continued)

260 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(3)—continued MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS a, q

FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION THICKNESS OF FLOOR
OR ROOF SLAB
(inches)
MINIMUM THICKNESS OF
CEILING
(inches)
FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION **4 **
hours
**3 **
hours
**2 **
hours
**1 **
hour
**4 **
hours
**3 **
hours
**2 **
hours
1
** hour**
17. Perlite concrete
slab proportioned
1:6 (Portland cement
to perlite aggregate)
on a9/16"-deep steel
deck supported by
steel joists 4 on
center. Class A or B
roof covering on top.
17-1.1 Perlite gypsum plaster on metal lath wire tied to3/4" furring
channels attached with 0.065" (No. 16 B.W. gage) wire ties
to lower chord of joists.
2p 2p 7/8 3/4
18. Perlite concrete
slab proportioned
1:6 (Portland cement
to perlite aggregate)
on 11/4" -deep steel
deck supported on
individually
protected steel
framing. Maximum
span of deck 6-10"
where deck is less
than 0.019" (No. 26
carbon sheet steel
gage) and 8-0"
where deck is 0.019"
(No. 26 carbon sheet
steel gage) or
greater. Slab
reinforced with
0.042" (No. 19 B.W.
gage) hexagonal
wire mesh. Class A
or B roof covering
on top.
18-1.1 None 21/4
p
21/4
p
19. Floor and beam
construction
consisting of 3" -
deep cellular steel
floor unit mounted
on steel members
with 1:4 (proportion
of Portland cement
to perlite aggregate)
perlite-concrete
floor slab on top.
19-1.1 Suspended envelope ceiling of perlite gypsum plaster on
metal lath attached to3/4" cold-rolled channels, secured to
11/2" cold-rolled channels spaced 42" on center supported
by 0.203 inch (No. 6 B.W. gage) wire 36" on center. Beams
in envelope with 3" minimum airspace between beam soffit
and lath have a 4-hour rating.
2p 1l

(continued)

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

lding Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(3)—continued MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS a, q

FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION THICKNESS OF FLOOR OR
ROOF SLAB
(inches)
MINIMUM THICKNESS
OF CEILING
(inches)
FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION **4 **
hours
**3 **
hours
**2 **
hours
1
hour
**4 **
hours
**3 **
hours
**2 **
hours
**1 **
hour
20. Perlite concrete proportioned 1:6
(Portland cement to perlite aggregate)
poured to1/8" thickness above top of
corrugations of 15/16" -deep
galvanized steel deck maximum span
8-0" for 0.024" (No. 24 galvanized
sheet gage) or 60" for 0.019" (No.
26 galvanized sheet gage) with deck
supported by individually protected
steel framing. Approved polystyrene
foam plastic insulation board having a
flame spread not exceeding 75 (1" to
4" thickness) with vent holes that
approximate 3 percent of the board
surface area placed on top of perlite
slurry. A 2 by 4 insulation board
contains six 23/4" diameter holes.
Board covered with 21/4" minimum
perlite concrete slab. Slab reinforced
with mesh consisting of 0.042" (No.
19 B.W. gage) galvanized steel wire
twisted together to form 2" hexagons
with straight 0.065" (No. 16 B.W.
gage) galvanized steel wire woven
into mesh and spaced 3". Alternate
slab reinforcement shall be permitted
to consist of 4" × 8", 0.109/0.238"
(No. 12/4 B.W. gage), or 2" × 2",
0.083/0.083" (No. 14/14 B.W. gage)
welded wire fabric. Class A or B roof
covering on top.
20-1.1 None Varies
21. Wood joists, wood I-joists, floor
trusses and flat or pitched roof trusses
spaced a maximum 24" o.c. with1/2"
wood structural panels with exterior
glue applied at right angles to top of
joist or top chord of trusses with 8d
nails. The wood structural panel
thickness shall be not less than
nominal1/2" nor less than required by
Chapter 23.
21-1.1 Base layer5/8" Type X gypsum wallboard
applied at right angles to joist or truss 24"
o.c. with 11/4" Type S or Type W drywall
screws 24" o.c. Face layer5/8" Type X
gypsum wallboard or veneer base applied
at right angles to joist or truss through
base layer with 17/8" Type S or Type W
drywall screws 12" o.c. at joints and
intermediate joist or truss. Face layer
Type G drywall screws placed 2" back on
either side of face layer end joints, 12"
o.c.
Varies 11/4

(continued)

262 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(3)—continued MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS a, q

FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION THICKNESS OF FLOOR OR
ROOF SLAB
(inches)
MINIMUM THICKNESS OF
CEILING
(inches)
FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION **4 **
hours
**3 **
hours
**2 **
hours
1
** hour**
**4 **
hours
**3 **
hours
**2 **
hours
1
** hour**
22. Steel joists, floor trusses and flat
or pitched roof trusses spaced a
maximum 24" o.c. with1/2" wood
structural panels with exterior glue
applied at right angles to top of joist
or top chord of trusses with No. 8
screws. The wood structural panel
thickness shall be not less than nom-
inal1/2" nor less than required by
Chapter 23.
22-1.1 Base layer5/8" Type X gypsum board
applied at right angles to steel framing 24"
on center with 1" Type S drywall screws
spaced 24" on center. Face layer5/8" Type
X gypsum board applied at right angles to
steel framing attached through base layer
with 15/8" Type S drywall screws 12" on
center at end joints and intermediate joints
and 11/2" Type G drywall screws 12 inches
on center placed 2" back on either side of
face layer end joints. Joints of the face
layer are offset 24" from the joints of the
base layer.
Varies 11/4
23. Wood I-joist (minimum joist
depth 91/4" with a minimum flange
depth of 15/16" and a minimum
flange cross-sectional area of 2.25
square inches) at 24" o.c. spacing
with a minimum 1 × 4 (3/4" × 3.5"
actual) ledger strip applied parallel
to and covering the bottom of the
bottom flange of each member,
tacked in place. 2" mineral wool
insulation, 3.5 pcf (nominal)
installed adjacent to the bottom
flange of the I-joist and supported by
the 1 × 4 ledger strip.
23-1.1 1/2" deep single leg resilient channel 16" on
center (channels doubled at wallboard end
joints), placed perpendicular to the furring
strip and joist and attached to each joist by
17/8" Type S drywall screws.5/8" Type C
gypsum wallboard applied perpendicular
to the channel with end joints staggered
not less than 4 and fastened with 11/8"
Type S drywall screws spaced 7" on cen-
ter. Wallboard joints to be taped and cov-
ered with joint compound.
Varies 5/8
24. Wood I-joist (minimum I-joist
depth 91/4" with a minimum flange
depth of 11/2" and a minimum flange
cross-sectional area of 5.25 square
inches; minimum web thickness of
3/8") @ 24" o.c., 11/2" mineral wool
insulation (2.5 pcf-nominal) resting
on hat-shaped furring channels.
24-1.1 Minimum 0.026" thick hat-shaped channel
16" o.c. (channels doubled at wallboard
end joints), placed perpendicular to the
joist and attached to each joist by 11/4"
Type S drywall screws.5/8" Type C gyp-
sum wallboard applied perpendicular to
the channel with end joints staggered and
fastened with 11/8" Type S drywall screws
spaced 12" o.c. in the field and 8" o.c. at
the wallboard ends. Wallboard joints to be
taped and covered with joint compound.
Varies 5/8
25. Wood I-joist (minimum I-joist
depth 91/4" with a minimum flange
depth of 11/2" and a minimum flange
cross-sectional area of 5.25 square
inches; minimum web thickness of
7/16") @ 24" o.c., 11/2" mineral wool
insulation (2.5 pcf-nominal) resting
on resilient channels.
25-1.1 Minimum 0.019" thick resilient channel
16" o.c. (channels doubled at wallboard
end joints), placed perpendicular to the
joist and attached to each joist by 15/8"
Type S drywall screws.5/8" Type C gyp-
sum wallboard applied perpendicular to
the channel with end joints staggered and
fastened with 1" Type S drywall screws
spaced 12" o.c. in the field and 8" o.c. at
the wallboard ends. Wallboard joints to be
taped and covered with joint compound.
Varies 5/8

(continued)

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(3)—continued MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS a, q

FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION THICKNESS OF FLOOR OR
ROOF SLAB
(inches)
MINIMUM THICKNESS OF
CEILING
(inches)
FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION **4 **
hours
**3 **
hours
**2 **
hours
1
** hour**
**4 **
hours
**3 **
hours
**2 **
hours
1
** hour**
26. Wood I-joist (minimum I-joist
depth 91/4" with a minimum flange
thickness of 11/2" and a minimum
flange cross-sectional area of 2.25
square inches; minimum web thick-
ness of3/8") @ 24" o.c.
26-1.1 Two layers of1/2" Type X gypsum
wallboard applied with the long
dimension perpendicular to the I-joists
with end joints staggered. The base layer
is fastened with 15/8" Type S drywall
screws spaced 12" o.c. and the face layer
is fastened with 2" Type S drywall screws
spaced 12" o.c. in the field and 8" o.c. on
the edges. Face layer end joints shall not
occur on the same I-joist as base layer
end joints and edge joints shall be offset
24" from base layer joints. Face layer to
also be attached to base layer with 11/2"
Type G drywall screws spaced 8" o.c.
placed 6" from face layer end joints. Face
layer wallboard joints to be taped and
covered with joint compound.
Varies 1
27. Wood I-joist (minimum I-joist
depth 91/2" with a minimum flange
depth of 15/16" and a minimum
flange cross-sectional area of 1.95
square inches; minimum web thick-
ness of3/8") @ 24" o.c.
27-1.1 Minimum 0.019" thick resilient channel
16" o.c. (channels doubled at wallboard
end joints), placed perpendicular to the
joist and attached to each joist by 11/4"
Type S drywall screws. Two layers of1/2"
Type X gypsum wallboard applied with
the long dimension perpendicular to the
resilient channels with end joints
staggered. The base layer is fastened
with 11/4" Type S drywall screws spaced
12" o.c. and the face layer is fastened
with 15/8" Type S drywall screws spaced
12" o.c. Face layer end joints shall not
occur on the same I-joist as base layer
end joints and edge joints shall be offset
24" from base layer joints. Face layer to
also be attached to base layer with 11/2"
Type G drywall screws spaced 8" o.c.
placed 6" from face layer end joints.
Face layer wallboard joints to be taped
and covered with joint compound.
Varies 1

(continued)

264 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(3)—continued MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS a, q

FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION THICKNESS OF FLOOR OR
ROOF SLAB (inches)
MINIMUM THICKNESS OF
CEILING (inches)
FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION **4 **
hours
**3 **
hours
**2 **
hours
1
** hour**
**4 **
hours
**3 **
hours
**2 **
hours
1
** hour**
28. Wood I-joist (minimum I-joist
depth 91/4" with a minimum flange
depth of 11/2" and a minimum flange
cross-sectional area of 2.25 square
inches; minimum web thickness of
3/8") @ 24" o.c. Unfaced fiberglass
insulation or mineral wool insulation
is installed between the I-joists
supported on the upper surface of the
flange by stay wires spaced 12" o.c.
28-1.1 Base layer of5/8" Type C gypsum
wallboard attached directly to I-joists
with 15/8" Type S drywall screws
spaced 12" o.c. with ends staggered.
Minimum 0.0179" thick hat-shaped7/8-
inch furring channel 16" o.c. (channels
doubled at wallboard end joints),
placed perpendicular to the joist and
attached to each joist by 15/8" Type S
drywall screws after the base layer of
gypsum wallboard has been applied.
The middle and face layers of5/8" Type
C gypsum wallboard applied
perpendicular to the channel with end
joints staggered. The middle layer is
fastened with 1" Type S drywall screws
spaced 12" o.c. The face layer is
applied parallel to the middle layer but
with the edge joints offset 24" from
those of the middle layer and fastened
with 15/8" Type S drywall screws 8" o.c.
The joints shall be taped and covered
with joint compound.
Varies 23/4
29. Channel-shaped 18 gage steel
joists (minimum depth 8") spaced a
maximum 24" o.c. supporting
tongue-and-groove wood structural
panels (nominal minimum3/4" thick)
applied perpendicular to framing
members. Structural panels attached
with 15/8" Type S-12 screws spaced
12" o.c.
29-1.1 Base layer5/8" Type X gypsum board
applied perpendicular to bottom of
framing members with 11/8" Type S-12
screws spaced 12" o.c. Second layer5/8"
Type X gypsum board attached
perpendicular to framing members with
15/8" Type S-12 screws spaced 12" o.c.
Second layer joints offset 24" from base
layer. Third layer5/8" Type X gypsum
board attached perpendicular to framing
members with 23/8" Type S-12 screws
spaced 12" o.c. Third layer joints offset
12" from second layer joints. Hat-
shaped7/8-inch rigid furring channels
applied at right angles to framing
members over third layer with two 23/8"
Type S-12 screws at each framing
member. Face layer5/8" Type X gypsum
board applied at right angles to furring
channels with 11/8" Type S screws
spaced 12" o.c.
Varies 33/8

(continued)

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 721.1(3)—continued MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS a, q

FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION THICKNESS OF FLOOR OR
ROOF SLAB (inches)
MINIMUM THICKNESS OF
CEILING (inches)
FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION **4 **
hours
**3 **
hours
**2 **
hours
1
** hour**
**4 **
hours
**3 **
hours
**2 **
hours
1
** hour**
30. Wood I-joist (minimum I-joist
depth 91/2" with a minimum flange
depth of 11/2" and a minimum flange
cross-sectional area of 2.25 square
inches; minimum web thickness of
3/8") @ 24" o.c. Fiberglass insulation
placed between I-joists supported by
the resilient channels.
30-1.1 Minimum 0.019" thick resilient channel
16" o.c. (channels doubled at wallboard
end joints), placed perpendicular to the
joists and attached to each joist by 11/4"
Type S drywall screws. Two layers of
1/2" Type X gypsum wallboard applied
with the long dimension perpendicular
to the resilient channels with end joints
staggered. The base layer is fastened
with 11/4" Type S drywall screws spaced
12" o.c. and the face layer is fastened
with 15/8" Type S drywall screws spaced
12" o.c. Face layer end joints shall not
occur on the same I-joist as base layer
end joints and edge joints shall be offset
24" from base layer joints. Face layer to
be attached to base layer with 11/2" Type
G drywall screws spaced 8" o.c. placed
6" from face layer end joints. Face layer
wallboard joints to be taped and cov-
ered with joint compound.
Varies 1

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 0.454 kg, 1 cubic foot = 0.0283 m 3,

1 pound per square inch = 6.895 kPa, 1 pound per linear foot = 1.4882 kg/m. a. Staples with equivalent holding power and penetration shall be permitted to be used as alternate fasteners to nails for attachment to wood framing. b. Where the slab is in an unrestrained condition, minimum reinforcement cover shall be not less than 1 5 /8 inches for 4 hours (siliceous aggregate only);

1 1 /4 inches for 4 and 3 hours; 1 inch for 2 hours (siliceous aggregate only); and 3 /4 inch for all other restrained and unrestrained conditions. c. For all of the construction with gypsum wallboard described in this table, gypsum base for veneer plaster of the same size, thickness and core type shall be

permitted to be substituted for gypsum wallboard, provided that attachment is identical to that specified for the wallboard, and the joints on the face layer are reinforced and the entire surface is covered with not less than 1 /16-inch gypsum veneer plaster. d. Slab thickness over steel joists measured at the joists for metal lath form and at the top of the form for steel form units. e. (a) The maximum allowable stress level for H-Series joists shall not exceed 22,000 psi. (b) The allowable stress for K-Series joists shall not exceed 26,000 psi, the nominal depth of such joist shall be not less than 10 inches and the nominal joist weight shall be not less than 5 pounds per linear foot. f. Cement plaster with 15 pounds of hydrated lime and 3 pounds of approved additives or admixtures per bag of cement. g. Gypsum wallboard ceilings attached to steel framing shall be permitted to be suspended with 1 1 /2-inch cold-formed carrying channels spaced 48 inches on

center, that are suspended with No. 8 SWG galvanized wire hangers spaced 48 inches on center. Cross-furring channels are tied to the carrying channels with No. 18 SWG galvanized wire hangers spaced 48 inches on center. Cross-furring channels are tied to the carrying channels with No. 18 SWG galvanized wire (double strand) and spaced as required for direct attachment to the framing. This alternative is applicable to those steel framing assemblies recognized under Note q. h. Six-inch hollow clay tile with 2-inch concrete slab above. i. Four-inch hollow clay tile with 1 1 /2-inch concrete slab above. j. Thickness measured to bottom of steel form units. k. Five-eighths inch of vermiculite gypsum plaster plus 1 /2 inch of approved vermiculite acoustical plastic. l. Furring channels spaced 12 inches on center. m.Double wood floor shall be permitted to be either of the following:

(a) Subfloor of 1-inch nominal boarding, a layer of asbestos paper weighing not less than 14 pounds per 100 square feet and a layer of 1-inch nominal

tongue-and-groove finished flooring. (b) Subfloor of 1-inch nominal tongue-and-groove boarding or 15 /32-inch wood structural panels with exterior glue and a layer of 1-inch nominal tongue-and groove finished flooring or 19 /32-inch wood structural panel finish flooring or a layer of Type I Grade M-1 particleboard not less than 5 /8-inch thick. n. The ceiling shall be permitted to be omitted over unusable space, and flooring shall be permitted to be omitted where unusable space occurs above. o. For properties of cooler or wallboard nails, see ASTM C514, ASTM C547 or ASTM F1667. p. Thickness measured on top of steel deck unit. q. Generic fire-resistance ratings (those not designated as PROPRIETARY* in the listing) in the GA 600 shall be accepted as if herein listed.

266 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

722.2.1.2 Multiwythe walls.

For walls that consist of two wythes of different types of concrete, the fire-resistance ratings shall be permitted to be determined from Figure 722.2.1.2.

722.2.1.2.1 Two or more wythes. The fire-resistance rating for wall panels consisting of two or more wythes shall be permitted to be determined by the formula:

FIRE AND SMOKE PROTECTION FEATURES

board or plaster applied to one or both sides shall be permitted to be calculated in accordance with the provisions of this section.

R = ( R 10.59 + R 20.59 +...+ Rn 0.59)1.7 (Equation 7-4)

where:

R = The fire endurance of the assembly, minutes.

R 1, R 2, and Rn = The fire endurances of the individual wythes, minutes. Values of Rn 0.59 for use in

Equation 7-4 are given in Table 722.2.1.2(1). Calculated fire-resistance ratings are shown in Table 722.2.1.2(2).

722.2.1.2.2 Foam plastic insulation.

The fire-resistance ratings of precast concrete wall panels consisting of a layer of foam plastic insulation sandwiched between two wythes of concrete shall be permitted to be determined by use of Equation 7-4. Foam plastic insulation with a total thickness of less than 1 inch (25 mm) shall be disregarded. The Rn value for thickness of foam plastic insulation of 1 inch (25 mm) or greater, for use in the calculation, is 5 minutes; therefore Rn 0.59 = 2.5.

722.2.1.3 Joints between precast wall panels.

Joints between precast concrete wall panels that are not insulated as required by this section shall be considered as openings in walls. Uninsulated joints shall be included in determining the percentage of openings permitted by Table 705.8. Where openings are not permitted or are required by this code to be protected, the provisions of this section shall be used to determine the amount of joint insulation required. Insulated joints shall not be considered openings for purposes of determining compliance with the allowable percentage of openings in Table 705.8.

722.2.1.3.1 Ceramic fiber joint protection.

Figure 722.2.1.3.1 shows thicknesses of ceramic fiber blankets to be used to insulate joints between precast concrete wall panels for various panel thicknesses and for joint widths of 3 /8 inch (9.5 mm) and 1 inch (25 mm) for fire-resistance ratings of 1 hour to 4 hours. For joint widths between 3 /8 inch (9.5 mm) and 1 inch (25 mm), the thickness of ceramic fiber blanket is allowed to be determined by direct interpolation. Other tested and labeled materials are acceptable in place of ceramic fiber blankets.

722.2.1.4 Walls with gypsum wallboard or plaster finishes.

finishes. The fire-resistance rating of cast-in-place or precast concrete walls with finishes of gypsum wall

722.2.1.4.1 Nonfire-exposed side. Where the finish of gypsum wallboard or plaster is applied to the side of the wall not exposed to fire, the contribution of the finish to the total fire-resistance rating shall be determined as follows: The thickness of the finish shall first be corrected by multiplying the actual thickness of the finish by the applicable factor determined from Table 722.2.1.4(1) based on the type of aggregate in the concrete. The corrected thickness of finish shall then be added to the actual or equivalent thickness of concrete and fire-resistance rating of the concrete and finish determined from Tables 722.2.1.1 and 722.2.1.2(1) and Figure 722.2.1.2.

722.2.1.4.2 Fire-exposed side.

Where gypsum wallboard or plaster is applied to the fire-exposed side of the wall, the contribution of the finish to the total fire-resistance rating shall be determined as follows: The time assigned to the finish as established by Table 722.2.1.4(2) shall be added to the fire-resistance rating determined from Tables 722.2.1.1 and 722.2.1.2(1) and Figure 722.2.1.2 for the concrete alone, or to the rating determined in Section 722.2.1.4.1 for the concrete and finish on the nonfire-exposed side.

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 722.2.1.4(1)

MULTIPLYING FACTOR FOR FINISHES ON NONFIRE-EXPOSED SIDE OF WALL

TYPE OF FINISH APPLIED
TO CONCRETE OR CONCRETE
MASONRY WALL
TYPE OF AGGREGATE USED IN CONCRETE OR CONCRETE MASONRY
TYPE OF FINISH APPLIED
TO CONCRETE OR CONCRETE
MASONRY WALL
Concrete: siliceous
or carbonate
Concrete Masonry:
siliceous or carbonate;
solid clay brick
Concrete: sand-lightweight
Concrete Masonry: clay tile;
hollow clay brick; concrete
masonry units of expanded
shale and < 20% sand
Concrete: lightweight Concrete
Masonry: concrete masonry
units of expanded shale,
expanded clay, expanded slag,
or pumice < 20% sand
Concrete Masonry:
concrete masonry
units of expanded
slag, expanded clay,
or pumice
Portland cement-sand plaster 1.00 0.75a 0.75a 0.50a
Gypsum-sand plaster 1.25 1.00 1.00 1.00
Gypsum-vermiculite or perlite plaster 1.75 1.50 1.25 1.25
Gypsum wallboard 3.00 2.25 2.25 2.25

For SI: 1 inch = 25.4 mm. a. For Portland cement-sand plaster 5 /8 inch or less in thickness and applied directly to the concrete or concrete masonry on the nonfire-exposed side of the wall,

the multiplying factor shall be 1.00.

TABLE 722.2.1.4(2)

TIME ASSIGNED TO FINISH MATERIALS

ON FIRE-EXPOSED SIDE OF WALL

FINISH DESCRIPTION TIME (minutes)
Gypsum wallboard
3/8 inch

1/2 inch
5/8 inch
2 layers of3/8 inch
1 layer of3/8 inch, 1 layer of1/2 inch
2 layers of1/2 inch
10
15
20
25
35
40
Type X gypsum wallboard

1/2 inch
5/8 inch
25
40
Portland cement-sand plaster applied directly
to concrete masonry
See Note a
Portland cement-sand plaster on metal lath
3/4 inch
7/8 inch
1 inch
20
25
30
Gypsum sand plaster on3/8-inch gypsum lath
1/2 inch
5/8 inch
3/4 inch
35
40
50
Gypsum sand plaster on metal lath
3/4 inch
7/8 inch
1 inch
50
60
80

For SI: 1 inch = 25.4 mm. a. The actual thickness of Portland cement-sand plaster, provided that it is 5 /8

inch or less in thickness, shall be permitted to be included in determining the equivalent thickness of the masonry for use in Table 722.3.2.

722.2.1.4.3 Nonsymmetrical assemblies.

For a wall without finish on one side or having different types or thicknesses of finish on each side, the calculation procedures of Sections 722.2.1.4.1 and 722.2.1.4.2 shall be performed twice, assuming either side of the wall to be the fire-exposed side. The fire-resistance

CONCRETE TYPE FIRE-RESISTANCE RATING (hours)
CONCRETE TYPE 1 11/2 2 3 4
Siliceous 3.5 4.3 5 6.2 7
Carbonate 3.2 4 4.6 5.7 6.6
Sand-lightweight 2.7 3.3 3.8 4.6 5.4
Lightweight 2.5 3.1 3.6 4.4 5.1

For SI: 1 inch = 25.4 mm.

rating of the wall shall not exceed the lower of the two values.

Exception: For an exterior wall with a fire separation distance greater than 5 feet (1524 mm) the fire shall be assumed to occur on the interior side only.

722.2.1.4.4 Minimum concrete fire-resistance rat-ing.

ing. Where finishes applied to one or both sides of a concrete wall contribute to the fire-resistance rating, the concrete alone shall provide not less than onehalf of the total required fire-resistance rating. Additionally, the contribution to the fire resistance of the finish on the nonfire-exposed side of a load-bearing wall shall not exceed one-half the contribution of the concrete alone. 722.2.1.4.5 Concrete finishes. Finishes on concrete walls that are assumed to contribute to the total fireresistance rating of the wall shall comply with the installation requirements of Section 722.3.2.5.

722.2.2 Concrete floor and roof slabs.

Reinforced and prestressed floors and roofs shall comply with Section 722.2.2.1. Multicourse floors and roofs shall comply with Sections 722.2.2.2 and 722.2.2.3, respectively.

722.2.2.1 Reinforced and prestressed floors and roofs. The minimum thicknesses of reinforced and prestressed concrete floor or roof slabs for fire-resistance ratings of 1 hour to 4 hours are shown in Table 722.2.2.1.

Exception: Minimum thickness shall not be required for floors and ramps within parking garages constructed in accordance with Sections 406.5 and 406.6.

TABLE 722.2.2.1

MINIMUM SLAB THICKNESS (inches)

268 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 722.2.1.2(1) VALUES OF Rn 0.59 FOR USE IN EQUATION 7-4
TYPE OF MATERIAL THICKNESS OF MATERIAL (inches) THICKNESS OF MATERIAL (inches) THICKNESS OF MATERIAL (inches) THICKNESS OF MATERIAL (inches) THICKNESS OF MATERIAL (inches) THICKNESS OF MATERIAL (inches) THICKNESS OF MATERIAL (inches) THICKNESS OF MATERIAL (inches) THICKNESS OF MATERIAL (inches) THICKNESS OF MATERIAL (inches) THICKNESS OF MATERIAL (inches) THICKNESS OF MATERIAL (inches)
TYPE OF MATERIAL 11/2 2 21/2 3 31/2 4 41/2 5 51/2 6 61/2 7
Siliceous aggregate concrete 5.3 6.5 8.1 9.5 11.3 13.0 14.9 16.9 18.8 20.7 22.8 25.1
Carbonate aggregate concrete 5.5 7.1 8.9 10.4 12.0 14.0 16.2 18.1 20.3 21.9 24.7 27.2c
Sand-lightweight concrete 6.5 8.2 10.5 12.8 15.5 18.1 20.7 23.3 26.0c Note c Note c Note c
Lightweight concrete 6.6 8.8 11.2 13.7 16.5 19.1 21.9 24.7 27.8c Note c Note c Note c
Insulating concretea 9.3 13.3 16.6 18.3 23.1 26.5c Note c Note c Note c Note c Note c Note c
Airspaceb

For SI: 1 inch = 25.4 mm, 1 pound per cubic foot = 16.02 kg/m 3 . a. Dry unit weight of 35 pcf or less and consisting of cellular, perlite or vermiculite concrete. b. The Rn 0.59 value for one 1/2" to 31/2" airspace is 3.3. The Rn 0.59 value for two 1/2" to 31/2" airspaces is 6.7.

c. The fire-resistance rating for this thickness exceeds 4 hours.

TABLE 722.2.1.2(2)

FIRE-RESISTANCE RATINGS BASED ON R 0.59

a. Based on Equation 7-4.

Ra, MINUTES R0.59
60 11.20
120 16.85
180 21.41
240 25.37

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

722.2.2.1.1 Hollow-core prestressed slabs.

For hollow-core prestressed concrete slabs in which the cores are of constant cross section throughout the length, the equivalent thickness shall be permitted to be obtained by dividing the net cross-sectional area of the slab including grout in the joints, by its width.

722.2.2.1.2 Slabs with sloping soffits. The thickness of slabs with sloping soffits (see Figure 722.2.2.1.2) shall be determined at a distance 2 t or 6 inches (152 mm), whichever is less, from the point of minimum thickness, where t is the minimum thickness.

722.2.2.2 Multicourse floors.

The fire-resistance ratings of floors that consist of a base slab of concrete with a topping (overlay) of a different type of concrete shall comply with Figure 722.2.2.2.

722.2.2.1.3 Slabs with ribbed soffits. The thickness of slabs with ribbed or undulating soffits (see Figure 722.2.2.1.3) shall be determined by one of the following expressions, whichever is applicable: For s - 4 t, the thickness to be used shall be t For s ≤ 2 t, the thickness to be used shall be te For 4 t - s - 2 t, the thickness to be used shall be

4 t t + - 1 te - t --- s -

(Equation 7-5)

722.2.2.3 Multicourse roofs.

The fire-resistance ratings of roofs that consist of a base slab of concrete with a topping (overlay) of an insulating concrete or with an insulating board and built-up roofing shall comply with Figures 722.2.2.3(1) and 722.2.2.3(2).

722.2.2.3.1 Heat transfer. For the transfer of heat, three-ply built-up roofing contributes 10 minutes to the fire-resistance rating. The fire-resistance rating for concrete assemblies such as those shown in Figure 722.2.2.3(1) shall be increased by 10 minutes. This increase is not applicable to those shown in Figure 722.2.2.3(2).

722.2.2.4 Joints in precast slabs.

Joints between adjacent precast concrete slabs need not be considered in calculating the slab thickness provided that a concrete topping not less than 1 inch (25 mm) thick is used. Where concrete topping is not used, joints must be grouted to a depth of not less than one-third the slab thickness at the joint, but not less than 1 inch (25 mm), or the joints must be made fire resistant by other approved methods.

722.2.3 Concrete cover over reinforcement. The minimum thickness of concrete cover over reinforcement in concrete slabs, reinforced beams and prestressed beams shall comply with this section.

where: s = Spacing of ribs or undulations. t = Minimum thickness. te = Equivalent thickness of the slab calculated as

the net area of the slab divided by the width, in which the maximum thickness used in the calculation shall not exceed 2 t .

270 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

722.2.3.1 Slab cover.

The minimum thickness of concrete cover to the positive moment reinforcement shall comply with Table 722.2.3(1) for reinforced concrete and Table 722.2.3(2) for prestressed concrete. These tables are applicable for solid or hollow-core one-way or two-way slabs with flat undersurfaces. These tables are applicable to slabs that are either cast in place or precast. For precast prestressed concrete not covered elsewhere, the procedures contained in PCI MNL 124 shall be acceptable.

722.2.3.2 Reinforced beam cover.

The minimum thickness of concrete cover to the positive moment reinforcement (bottom steel) for reinforced concrete beams is shown in Table 722.2.3(3) for fire-resistance ratings of 1 hour to 4 hours.

722.2.3.3 Prestressed beam cover. The minimum thickness of concrete cover to the positive moment prestressing tendons (bottom steel) for restrained and unrestrained prestressed concrete beams and stemmed units shall comply with the values shown in Tables 722.2.3(4) and 722.2.3(5) for fire-resistance ratings of 1 hour to 4 hours. Values in Table 722.2.3(4) apply to beams 8 inches (203 mm) or greater in width. Values in Table 722.2.3(5) apply to beams or stems of any width, provided that the cross-section area is not less than 40 square inches (25 806 mm 2 ). In case of differences

between the values determined from Table 722.2.3(4) or 722.2.3(5), it is permitted to use the smaller value. The concrete cover shall be calculated in accordance with Section 722.2.3.3.1. The minimum concrete cover for nonprestressed reinforcement in prestressed concrete beams shall comply with Section 722.2.3.2.

722.2.3.3.1 Calculating concrete cover.

The concrete cover for an individual tendon is the minimum thickness of concrete between the surface of the tendon and the fire-exposed surface of the beam, except that for ungrouted ducts, the assumed cover thickness is the minimum thickness of concrete between the surface of the duct and the fire-exposed surface of the beam. For beams in which two or more tendons are used, the cover is assumed to be the average of the minimum cover of the individual tendons. For corner tendons (tendons equal distance from the bottom and side), the minimum cover used in the calculation shall be one-half the actual value. For stemmed members with two or more prestressing tendons located along the vertical centerline of the stem, the average cover shall be the distance from the bottom of the member to the centroid of the tendons. The actual cover for any individual tendon shall be not less than one-half the smaller value shown in Tables 722.2.3(4) and 722.2.3(5), or 1 inch (25 mm), whichever is greater.

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

COVER THICKNESS TABLE 722.2.3(1) FOR REINFORCED CONCRETE FLOOR OR ROOF SLABS (inches)
CONCRETE AGGREGATE TYPE FIRE-RESISTANCE RATING (hours) FIRE-RESISTANCE RATING (hours) FIRE-RESISTANCE RATING (hours) FIRE-RESISTANCE RATING (hours) FIRE-RESISTANCE RATING (hours) FIRE-RESISTANCE RATING (hours) FIRE-RESISTANCE RATING (hours) FIRE-RESISTANCE RATING (hours) FIRE-RESISTANCE RATING (hours) FIRE-RESISTANCE RATING (hours)
CONCRETE AGGREGATE TYPE Restrained Restrained Restrained Restrained Restrained Unrestrained Unrestrained Unrestrained Unrestrained Unrestrained
CONCRETE AGGREGATE TYPE 1 11/2 2 3 4 1 11/2 2 3 4
Siliceous 3/4 3/4 3/4 3/4 3/4 3/4 3/4 1 11/4 15/8
Carbonate 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 11/4 11/4
Sand-lightweight or lightweight 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 11/4 11/4

For SI: 1 inch = 25.4 mm.

TABLE 722.2.3(2)

COVER THICKNESS FOR PRESTRESSED CONCRETE FLOOR OR ROOF SLABS (inches)

CONCRETE AGGREGATE TYPE FIRE-RESISTANCE RATING (hours)
CONCRETE AGGREGATE TYPE Restrained Restrained Restrained Restrained Restrained Unrestrained Unrestrained Unrestrained Unrestrained Unrestrained
CONCRETE AGGREGATE TYPE 1 11/2 2 3 4 1 11/2 2 3 4
Siliceous 3/4 3/4 3/4 3/4 3/4 11/8 11/2 13/4 23/8 23/4
Carbonate 3/4 3/4 3/4 3/4 3/4 1 13/8 15/8 21/8 21/4
Sand-lightweight or lightweight 3/4 3/4 3/4 3/4 3/4 1 13/8 11/2 2 21/4

For SI: 1 inch = 25.4 mm.

TABLE 722.2.3(3)

MINIMUM COVER FOR MAIN REINFORCING BARS OF REINFORCED CONCRETE BEAMS c

(APPLICABLE TO ALL TYPES OF STRUCTURAL CONCRETE)
RESTRAINED OR
UNRESTRAINEDa
BEAM
WIDTHb(inches)
FIRE-RESISTANCE RATING (hours) FIRE-RESISTANCE RATING (hours) FIRE-RESISTANCE RATING (hours) FIRE-RESISTANCE RATING (hours) FIRE-RESISTANCE RATING (hours)
RESTRAINED OR
UNRESTRAINEDa
BEAM
WIDTHb(inches)
1 11/2 2 3 4
Restrained 5
7
10
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
1a
3/4
3/4
11/4
a
3/4
3/4
Unrestrained 5
7
10
3/4
3/4
3/4
1
3/4
3/4
11/4
3/4
3/4

13/4
1

3
13/4

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. a. Tabulated values for restrained assemblies apply to beams spaced more than 4 feet on center. For restrained beams spaced 4 feet or less on center, minimum

cover of 3 /4 inch is adequate for ratings of 4 hours or less. b. For beam widths between the tabulated values, the minimum cover thickness can be determined by direct interpolation. c. The cover for an individual reinforcing bar is the minimum thickness of concrete between the surface of the bar and the fire-exposed surface of the beam. For

beams in which several bars are used, the cover for corner bars used in the calculation shall be reduced to one-half of the actual value. The cover for an individual bar must be not less than one-half of the value given in Table 722.2.3(3) nor less than 3 /4 inch.

TABLE 722.2.3(4)

MINIMUM COVER FOR PRESTRESSED CONCRETE BEAMS 8 INCHES OR GREATER IN WIDTH b

RESTRAINED OR
UNRESTRAINEDa
CONCRETE
AGGREGATE TYPE
BEAM WIDTH
(inches)
FIRE-RESISTANCE RATING (hours)
RESTRAINED OR
UNRESTRAINEDa
CONCRETE
AGGREGATE TYPE
BEAM WIDTH
(inches)
1 11/2 2 3 4
Restrained Carbonate or siliceous
Carbonate or siliceous
Sand lightweight
Sand lightweight
8
12
8
12
11/2
11/2
11/2
11/2
11/2
11/2
11/2
11/2
11/2
11/2
11/2
11/2
13/4
a
11/2
11/2
11/2
21/2
a
17/8
a
2a
15/8
a
Unrestrained Carbonate or siliceous
Carbonate or siliceous
Sand lightweight
Sand lightweight
8
12
8
12
11/2
11/2
11/2
11/2
13/4
11/2
11/2
11/2
21/2
17/8
a
2
15/8
5c
21/2
31/4
2

3

21/2

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. a. Tabulated values for restrained assemblies apply to beams spaced more than 4 feet on center. For restrained beams spaced 4 feet or less on center, minimum

cover of 3 /4 inch is adequate for 4-hour ratings or less. b. For beam widths between 8 inches and 12 inches, minimum cover thickness can be determined by direct interpolation. c. Not practical for 8-inch-wide beam but shown for purposes of interpolation.

272 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 722.2.3(5)

MINIMUM COVER FOR PRESTRESSED CONCRETE BEAMS OF ALL WIDTHS

RESTRAINED OR
UNRESTRAINEDa
CONCRETE AGGREGATE TYPE BEAM AREAb
A (square inches)
FIRE-RESISTANCE RATING (hours)
RESTRAINED OR
UNRESTRAINEDa
CONCRETE AGGREGATE TYPE BEAM AREAb
A (square inches)
1 11/2 2 3 4
Restrained All 40 A 150
11/2 11/2 2 21/2
Restrained Carbonate or
siliceous
150 < A 300 11/2 11/2 11/2 13/4 21/2
Restrained Carbonate or
siliceous
300 < A 11/2 11/2 11/2 11/2 2
Restrained Sand lightweight 150 < A
11/2 11/2 11/2 11/2 2
Unrestrained All 40 A 150
2 21/2
Unrestrained Carbonate or
siliceous
150 < A 300 11/2 13/4 21/2
Unrestrained Carbonate or
siliceous
300 < A 11/2 11/2 2 3c 4c
Unrestrained Sand lightweight 150 < A 11/2 11/2 2 3c 4c

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square inch = 645.2 mm 2 . a. Tabulated values for restrained assemblies apply to beams spaced more than 4 feet on center. For restrained beams spaced 4 feet or less on center, minimum

cover of 3 /4 inch is adequate for 4-hour ratings or less. b. The cross-sectional area of a stem is permitted to include a portion of the area in the flange, provided that the width of the flange used in the calculation does

not exceed three times the average width of the stem. c. U-shaped or hooped stirrups spaced not to exceed the depth of the member and having a minimum cover of 1 inch shall be provided.

722.2.4 Concrete columns.

Concrete columns shall comply with this section.

722.2.4.1 Minimum size. The minimum overall dimensions of reinforced concrete columns for fireresistance ratings of 1 hour to 4 hours for exposure to fire on all sides shall comply with this section.

722.2.4.1.1 Concrete strength less than or equal to 12,000 psi. For columns made with concrete having a specified compressive strength, f c, of less than or equal to 12,000 psi (82.7 MPa), the minimum dimension shall comply with Table 722.2.4.

722.2.4.1.2 Concrete strength greater than 12,000 psi.

psi. For columns made with concrete having a specified compressive strength, f c, greater than 12,000 psi (82.7 MPa), for fire-resistance ratings of 1 hour to 4 hours the minimum dimension shall be 24 inches (610 mm).

TABLE 722.2.4 MINIMUM DIMENSION OF CONCRETE COLUMNS (inches)

than 1 inch (25 mm) times the number of hours of required fire resistance or 2 inches (51 mm), whichever is less.

722.2.4.3 Tie and spiral reinforcement. For concrete columns made with concrete having a specified compressive strength, f ′c, greater than 12,000 psi (82.7 MPa), tie and spiral reinforcement shall comply with the following:

  1. The free ends of rectangular ties shall terminate with a 135-degree (2.4 rad) standard tie hook.

  2. The free ends of circular ties shall terminate with a 90-degree (1.6 rad) standard tie hook.

  3. The free ends of spirals, including at lap splices, shall terminate with a 90-degree (1.6 rad) standard tie hook.

The hook extension at the free end of ties and spirals shall be the larger of six bar diameters and the extension required by Section 7.1.3 of ACI 318. Hooks shall project into the core of the column.

722.2.4.4 Columns built into walls.

The minimum dimensions of Table 722.2.4 do not apply to a reinforced concrete column that is built into a concrete or masonry wall provided that all of the following are met:

  1. The fire-resistance rating for the wall is equal to or greater than the required rating of the column.

  2. The main longitudinal reinforcing in the column has cover not less than that required by Section 722.2.4.2.

  3. Openings in the wall are protected in accordance with Section 716.

Where openings in the wall are not protected as required by Section 716, the minimum dimension of columns required to have a fire-resistance rating of 3 hours or less shall be 8 inches (203 mm), and 10 inches

TYPES OF CONCRETE FIRE-RESISTANCE RATING (hours)
TYPES OF CONCRETE 1 11/2 2a 3a 4b
Siliceous 8 9 10 12 14
Carbonate 8 9 10 11 12
Sand-lightweight 8 81/2 9 101/2 12

For SI: 1 inch = 25 mm. a. The minimum dimension is permitted to be reduced to 8 inches for

rectangular columns with two parallel sides not less than 36 inches in length. b. The minimum dimension is permitted to be reduced to 10 inches for

rectangular columns with two parallel sides not less than 36 inches in length.

722.2.4.2 Minimum cover for R/C columns.

The minimum thickness of concrete cover to the main longitudinal reinforcement in columns, regardless of the type of aggregate used in the concrete and the specified compressive strength of concrete, f c, shall be not less

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

(254 mm) for columns required to have a fire-resistance rating of 4 hours, regardless of the type of aggregate used in the concrete.

722.2.4.5 Precast cover units for steel columns.

See Section 722.5.1.4.

722.3 Concrete masonry.

The provisions of this section contain procedures by which the fire-resistance ratings of concrete masonry are established by calculations.

722.3.1 Equivalent thickness. The equivalent thickness of concrete masonry construction shall be determined in accordance with the provisions of this section.

722.3.1.1 Concrete masonry unit plus finishes. The equivalent thickness of concrete masonry assemblies, Tea, shall be computed as the sum of the equivalent thickness of the concrete masonry unit, Te, as determined by Section 722.3.1.2, 722.3.1.3 or 722.3.1.4, plus the equivalent thickness of finishes, Tef, determined in accordance with Section 722.3.2:

Tea = Te + Tef (Equation 7-6)

722.3.1.2 Ungrouted or partially grouted construc- tion. Te shall be the value obtained for the concrete masonry unit determined in accordance with ASTM C140.

722.3.1.3 Solid grouted construction. The equivalent thickness, Te, of solid grouted concrete masonry units is the actual thickness of the unit.

722.3.1.4 Airspaces and cells filled with loose-fill material. The equivalent thickness of completely filled hollow concrete masonry is the actual thickness of the unit where loose-fill materials are: sand, pea gravel, crushed stone, or slag that meet ASTM C33 requirements; pumice, scoria, expanded shale, expanded clay, expanded slate, expanded slag, expanded fly ash, or cinders that comply with ASTM C331; or perlite or vermiculite meeting the requirements of ASTM C549 and ASTM C516, respectively.

722.3.2 Concrete masonry walls. The fire-resistance rating of walls and partitions constructed of concrete

masonry units shall be determined from Table 722.3.2. The rating shall be based on the equivalent thickness of the masonry and type of aggregate used.

722.3.2.1 Finish on nonfire-exposed side. Where plaster or gypsum wallboard is applied to the side of the wall not exposed to fire, the contribution of the finish to the total fire-resistance rating shall be determined as follows: The thickness of gypsum wallboard or plaster shall be corrected by multiplying the actual thickness of the finish by applicable factor determined from Table 722.2.1.4(1). This corrected thickness of finish shall be added to the equivalent thickness of masonry and the fire-resistance rating of the masonry and finish determined from Table 722.3.2.

722.3.2.2 Finish on fire-exposed side. Where plaster or gypsum wallboard is applied to the fire-exposed side of the wall, the contribution of the finish to the total fire-resistance rating shall be determined as follows: The time assigned to the finish as established by Table 722.2.1.4(2) shall be added to the fire-resistance rating determined in Section 722.3.2 for the masonry alone, or in Section 722.3.2.1 for the masonry and finish on the nonfire-exposed side.

board is applied to the fire-exposed side of the wall, the contribution of the finish to the total fire-resistance rating shall be determined as follows: The time assigned to the finish as established by Table 722.2.1.4(2) shall be added to the fire-resistance rating determined in Section 722.3.2 for the masonry alone, or in Section 722.3.2.1 for the masonry and finish on the nonfire-exposed side.

722.3.2.3 Nonsymmetrical assemblies. For a wall without finish on one side or having different types or thicknesses of finish on each side, the calculation procedures of this section shall be performed twice, assuming either side of the wall to be the fire-exposed side. The fire-resistance rating of the wall shall not exceed the lower of the two values calculated.

Exception: For exterior walls with a fire separation distance greater than 5 feet (1524 mm), the fire shall be assumed to occur on the interior side only.

722.3.2.4 Minimum concrete masonry fire-resis- tance rating. Where the finish applied to a concrete masonry wall contributes to its fire-resistance rating, the masonry alone shall provide not less than one-half the total required fire-resistance rating.

TABLE 722.3.2 MINIMUM EQUIVALENT THICKNESS (inches) OF BEARING OR NONBEARING CONCRETE MASONRY WALLS a, b, c, d

TYPE OF AGGREGATE FIRE-RESISTANCE RATING (hours)
TYPE OF AGGREGATE 1/2 3/4 1 11/4 11/2 13/4 2 21/4 21/2 23/4 3 31/4 31/2 33/4 4
Pumice or expanded slag 1.5 1.9 2.1 2.5 2.7 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.5 4.7
Expanded shale, clay or slate 1.8 2.2 2.6 2.9 3.3 3.4 3.6 3.8 4.0 4.2 4.4 4.6 4.8 4.9 5.1
Limestone, cinders or unexpanded slag 1.9 2.3 2.7 3.1 3.4 3.7 4.0 4.3 4.5 4.8 5.0 5.2 5.5 5.7 5.9
Calcareous or siliceous gravel 2.0 2.4 2.8 3.2 3.6 3.9 4.2 4.5 4.8 5.0 5.3 5.5 5.8 6.0 6.2

For SI: 1 inch = 25.4 mm. a. Values between those shown in the table can be determined by direct interpolation. b. Where combustible members are framed into the wall, the thickness of solid material between the end of each member and the opposite face of the wall, or

between members set in from opposite sides, shall be not less than 93 percent of the thickness shown in the table. c. Requirements of ASTM C55, ASTM C73, ASTM C90 or ASTM C744 shall apply. d. Minimum required equivalent thickness corresponding to the hourly fire-resistance rating for units with a combination of aggregate shall be determined by

linear interpolation based on the percent by volume of each aggregate used in manufacture.

274 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

722.3.2.5 Attachment of finishes. Installation of finishes shall be as follows:

  1. Gypsum wallboard and gypsum lath applied to concrete masonry or concrete walls shall be secured to wood or steel furring members spaced not more than 16 inches (406 mm) on center (o.c.).

  2. Gypsum wallboard shall be installed with the long dimension parallel to the furring members and shall have all joints finished.

  3. Other aspects of the installation of finishes shall comply with the applicable provisions of Chapters 7 and 25.

722.3.3 Multiwythe masonry walls. The fire-resistance rating of wall assemblies constructed of multiple wythes of masonry materials shall be permitted to be based on the fire-resistance rating period of each wythe and the continuous airspace between each wythe in accordance with the following formula:

RA = ( R 10.59 + R 20.59 + ... + Rn 0.59 + A 1 + A 2 + ... + An )1.7

(Equation 7-7)

where:

RA = Fire-resistance rating of the assembly (hours).

R1, R2, ..., Rn = Fire-resistance rating of wythes for 1, 2,

n (hours), respectively.

A1, A2, ...., An = 0.30, factor for each continuous airspace

for 1, 2, ... n, respectively, having a depth of 1 /2 inch (12.7 mm) or more between wythes.

722.3.4 Concrete masonry lintels. Fire-resistance ratings for concrete masonry lintels shall be determined based on the nominal thickness of the lintel and the minimum thickness of concrete masonry or concrete, or any combination thereof, covering the main reinforcing bars, as determined in accordance with Table 722.3.4, or by approved alternate methods.

TABLE 722.3.4 MINIMUM COVER OF LONGITUDINAL REINFORCEMENT IN FIRE-RESISTANCE-RATED REINFORCED CONCRETE MASONRY LINTELS (inches)

FIRE AND SMOKE PROTECTION FEATURES

TABLE 722.3.5
MINIMUM DIMENSION OF CONCRETE
MASONRY COLUMNS (inches)
FIRE-RESISTANCE RATING (hours)
1 2
3
4
8 inches 10 inches
12 inches
14 inches

For SI: 1 inch = 25.4 mm.

722.4 Clay brick and tile masonry.

The provisions of this section contain procedures by which the fire-resistance ratings of clay brick and tile masonry are established by calculations.

722.4.1 Masonry walls. The fire-resistance rating of masonry walls shall be based on the equivalent thickness as calculated in accordance with this section. The calculation shall take into account finishes applied to the wall and airspaces between wythes in multiwythe construction.

722.4.1.1 Equivalent thickness. The fire-resistance ratings of walls or partitions constructed of solid or hollow clay masonry units shall be determined from Table 722.4.1(1) or 722.4.1(2). The equivalent thickness of the clay masonry unit shall be determined by Equation 7-8 where using Table 722.4.1(1). The fire-resistance rating determined from Table 722.4.1(1) shall be permitted to be used in the calculated fire-resistance rating procedure in Section 722.4.2.

Te = Vn / LH (Equation 7-8)

where: Te = The equivalent thickness of the clay masonry unit

(inches). Vn = The net volume of the clay masonry unit (inch 3 ). L = The specified length of the clay masonry unit

(inches).

H = The specified height of the clay masonry unit

(inches).

722.4.1.1.1 Hollow clay units. The equivalent thickness, Te, shall be the value obtained for hollow clay units as determined in accordance with Equation 7-8. The net volume, Vn, of the units shall be determined using the gross volume and percentage of void area determined in accordance with ASTM C67.

722.4.1.1.2 Solid grouted clay units. The equivalent thickness of solid grouted clay masonry units shall be taken as the actual thickness of the units.

722.4.1.1.3 Units with filled cores. The equivalent thickness of the hollow clay masonry units is the actual thickness of the unit where completely filled with loose-fill materials of: sand, pea gravel, crushed stone, or slag that meet ASTM C33 requirements; pumice, scoria, expanded shale, expanded clay, expanded slate, expanded slag, expanded fly ash, or cinders in compliance with ASTM C331; or perlite or vermiculite meeting the requirements of ASTM C549 and ASTM C516, respectively.

NOMINAL WIDTH
OF LINTEL (inches)
FIRE-RESISTANCE RATING (hours)
NOMINAL WIDTH
OF LINTEL (inches)
1 2 3 4
6 11/2 2
8 11/2 11/2 13/4 3
10 or greater 11/2 11/2 11/2 13/4

For SI: 1 inch = 25.4 mm.

722.3.5 Concrete masonry columns. The fire-resistance rating of concrete masonry columns shall be determined based on the least plan dimension of the column in accordance with Table 722.3.5 or by approved alternate methods.

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 722.4.1(1) FIRE-RESISTANCE PERIODS OF CLAY MASONRY WALLS

MATERIAL TYPE MINIMUM REQUIRED EQUIVALENT THICKNESS FOR FIRE RESISTANCEa, b, c
(inches)
MATERIAL TYPE 1 hour 2 hours 3 hours 4 hours
Solid brick of clay or shaled 2.7 3.8 4.9 6.0
Hollow brick or tile of clay or shale, unfilled 2.3 3.4 4.3 5.0
Hollow brick or tile of clay or shale, grouted or filled with materials
specified in Section 722.4.1.1.3
3.0 4.4 5.5 6.6

For SI: 1 inch = 25.4 mm. a. Equivalent thickness as determined from Section 722.4.1.1. b. Calculated fire resistance between the hourly increments listed shall be determined by linear interpolation. c. Where combustible members are framed in the wall, the thickness of solid material between the end of each member and the opposite face of the wall, or

between members set in from opposite sides, shall be not less than 93 percent of the thickness shown. d. For units in which the net cross-sectional area of cored brick in any plane parallel to the surface containing the cores is not less than 75 percent of the gross

cross-sectional area measured in the same plane.

TABLE 722.4.1(2) FIRE-RESISTANCE RATINGS FOR BEARING STEEL FRAME BRICK VENEER WALLS OR PARTITIONS

WALL OR PARTITION ASSEMBLY PLASTER SIDE
EXPOSED
(hours)
BRICK FACED
SIDE EXPOSED
(hours)
Outside facing of steel studs:
1/2" wood fiberboard sheathing next to studs,3/4" airspace formed with 3/4" × 15/8" wood strips placed over the
fiberboard and secured to the studs; metal or wire lath nailed to such strips, 33/4" brick veneer held in place by
filling3/4" airspace between the brick and lath with mortar. Inside facing of studs:3/4" unsanded gypsum plaster
on metal or wire lath attached to
5/16" wood strips secured to edges of the studs.
1.5 4
Outside facing of steel studs:
1" insulation board sheathing attached to studs, 1" airspace, and 33/4" brick veneer attached to steel frame with
metal ties every 5th course. Inside facing of studs:7/8" sanded gypsum plaster (1:2 mix) applied on metal or wire
lath attached directly to the studs.
1.5 4
Same as previous assembly except use7/8" vermiculite-gypsum plaster or 1" sanded gypsum plaster (1:2 mix)
applied to metal or wire.
2 4
Outside facing of steel studs:
1/2" gypsum sheathing board, attached to studs, and 33/4" brick veneer attached to steel frame with metal ties every 5th
course. Inside facing of studs:1/2" sanded gypsum plaster (1:2 mix) applied to1/2" perforated gypsum lath securely
attached to studs and having strips of metal lath 3 inches wide applied to all horizontal joints of gypsum lath.
2 4

For SI: 1 inch = 25.4 mm.

TABLE 722.4.1(3)
VALUES OF R 0.59
n
Rn 0.59 R (hours)
1 1.0
2 1.50
3 1.91
4 2.27

TABLE 722.4.1(4) COEFFICIENTS FOR PLASTER, pl a

THICKNESS OF PLASTER (inch) ONE SIDE TWO SIDES
1/2 0.3 0.6
5/8 0.37 0.75
3/4 0.45 0.90

For SI: 1 inch = 25.4 mm. a. Values listed in the table are for 1:3 sanded gypsum plaster.

NOMINAL
LINTEL WIDTH
(inches)
MINIMUM LONGITUDINAL REINFORCEMENT
COVER FOR FIRE RESISTANCE (inches)
NOMINAL
LINTEL WIDTH
(inches)
1 hour 2 hours 3 hours 4 hours
6 11/2 2 NP NP
8 11/2 11/2 13/4 3
10 or more 11/2 11/2 11/2 13/4

TABLE 722.4.1(5) REINFORCED MASONRY LINTELS

For SI: 1 inch = 25.4 mm. NP = Not Permitted.

TABLE 722.4.1(6)
REINFORCED CLAY MASONRY
** COLUMNS** ** COLUMNS**
COLUMN SIZE
FIRE-RESISTANCE RATING
(hours)
1 2 3 4
Minimum column dimension (inches)
8
10 12 14
For SI: 1 inch = 25.4 mm.

276 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

722.4.1.2 Plaster finishes. Where plaster is applied to the wall, the total fire-resistance rating shall be determined by the formula:

R = ( Rn 0.59 + pl ) 1.7 (Equation 7-9)

where: R = The fire-resistance rating of the assembly (hours). Rn = The fire-resistance rating of the individual wall

R = ( Rn

(hours). pl = Coefficient for thickness of plaster. Values for Rn 0.59 for use in Equation 7-9 are given in

Values for Rn 0.59 for use in Equation 7-9 are given in

Table 722.4.1(3). Coefficients for thickness of plaster shall be selected from Table 722.4.1(4) based on the actual thickness of plaster applied to the wall or partition and whether one or two sides of the wall are plastered.

722.4.1.3 Multiwythe walls with airspace. Where a continuous airspace separates multiple wythes of the wall or partition, the total fire-resistance rating shall be determined by the formula:

R = ( R 10.59 + R 20.59 + ...+ Rn 0.59 + as ) 1.7 (Equation 7-10)

where:

R = The fire-resistance rating of the assembly (hours).

R 1, R 2 and Rn = The fire-resistance rating of the

individual wythes (hours).

as = Coefficient for continuous airspace.

FIRE AND SMOKE PROTECTION FEATURES

722.4.2.1 Multiwythe walls of different material. For walls that consist of two or more wythes of different materials (concrete or concrete masonry units) in combination with clay masonry units, the fire-resistance rating of the different materials shall be permitted to be determined from Table 722.2.1.1 for concrete; Table 722.3.2 for concrete masonry units or Table 722.4.1(1) or 722.4.1(2) for clay and tile masonry units.

722.4.3 Reinforced clay masonry lintels. Fire-resistance ratings for clay masonry lintels shall be determined based on the nominal width of the lintel and the minimum covering for the longitudinal reinforcement in accordance with Table 722.4.1(5).

722.4.4 Reinforced clay masonry columns. The fireresistance ratings shall be determined based on the last plan dimension of the column in accordance with Table 722.4.1(6). The minimum cover for longitudinal reinforcement shall be 2 inches (51 mm).

722.5 Steel assemblies.

The provisions of this section contain procedures by which the fire-resistance ratings of steel assemblies are established by calculations.

722.5.1 Structural steel columns. The fire-resistance ratings of structural steel columns shall be based on the size of the element and the type of protection provided in accordance with this section.

722.5.1.1 General. These procedures establish a basis for determining the fire resistance of column assemblies as a function of the thickness of fire-resistant material and, the weight, W, and heated perimeter, D, of structural steel columns. As used in these sections, W is the average weight of a structural steel column in pounds per linear foot. The heated perimeter, D, is the inside perimeter of the fire-resistant material in inches as illustrated in Figure 722.5.1(1).

722.5.1.1.1 Nonload-bearing protection. The application of these procedures shall be limited to column assemblies in which the fire-resistant material is not designed to carry any of the load acting on the column.

722.5.1.1.2 Embedments. In the absence of substantiating fire-endurance test results, ducts, conduit, piping, and similar mechanical, electrical, and plumbing installations shall not be embedded in any required fire-resistant materials.

Values for Rn 0.59 for use in Equation 7-10 are given

in Table 722.4.1(3). The coefficient for each continuous airspace of 1 /2 inch to 3 1 /2 inches (12.7 to 89 mm) separating two individual wythes shall be 0.3.

722.4.1.4 Nonsymmetrical assemblies. For a wall without finish on one side or having different types or thicknesses of finish on each side, the calculation procedures of this section shall be performed twice, assuming either side to be the fire-exposed side of the wall. The fire resistance of the wall shall not exceed the lower of the two values determined.

Exception: For exterior walls with a fire separation distance greater than 5 feet (1524 mm), the fire shall be assumed to occur on the interior side only.

722.4.2 Multiwythe walls. The fire-resistance rating for walls or partitions consisting of two or more dissimilar wythes shall be permitted to be determined by the formula:

R = ( R 10.59 + R 20.59 + ...+ Rn 0.59) 1.7 (Equation 7-11)

where:

R = The fire-resistance rating of the assembly (hours).

R1, R2 and Rn = The fire-resistance rating of the individual wythes (hours).

Values for Rn 0.59 for use in Equation 7-11 are given in

Table 722.4.1(3).

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

278 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

accordance with the definitions given in this section.

722.5.1.2 Gypsum wallboard protection. The fire resistance of structural steel columns with weight-toheated-perimeter ratios ( W/D ) less than or equal to 3.65 and that are protected with Type X gypsum wallboard shall be permitted to be determined from the following expression:

2

(Equation 7-12)

tected with sprayed fire-resistant materials, as illustrated in Figure 722.5.1(5), shall be permitted to be determined from the following expression:

R = [ C 1( W/D ) + C 2] h (Equation 7-13)

where:

R = Fire resistance (minutes).

h = Thickness of sprayed fire-resistant material

(inches).

D = Heated perimeter of the structural steel column

(inches). C 1 and C 2 = Material-dependent constants. W = Weight of structural steel columns (pounds per

linear foot).

The fire resistance of structural steel columns protected with intumescent or mastic fire-resistant coatings shall be determined on the basis of fire-resistance tests in accordance with Section 703.2.

722.5.1.3.1 Material-dependent constants. The material-dependent constants, C 1 and C 2, shall be determined for specific fire-resistant materials on the basis of standard fire endurance tests in accordance with Section 703.2. Unless evidence is submitted to the building official substantiating a broader application, this expression shall be limited to determining the fire resistance of structural steel columns with weight-to-heated-perimeter ratios ( W/D ) between the largest and smallest columns for which standard fireresistance test results are available.

where:

R = Fire resistance (minutes).

h = Total thickness of gypsum wallboard (inches).

D = Heated perimeter of the structural steel column

(inches).

W' = Total weight of the structural steel column and

gypsum wallboard protection (pounds per linear foot).

W' = W + 50 hD /144.

722.5.1.2.1 Attachment. The gypsum board or gypsum panel products shall be supported as illustrated in either Figure 722.5.1(2) for fire-resistance ratings of 4 hours or less, or Figure 722.5.1(3) for fire-resistance ratings of 3 hours or less.

722.5.1.2.2 Gypsum wallboard equivalent to con- crete. The determination of the fire resistance of structural steel columns from Figure 722.5.1(4) is permitted for various thicknesses of gypsum wallboard as a function of the weight-to-heated-perimeter ratio ( W/D ) of the column. For structural steel

280 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

722.5.1.3.2 Identification. Sprayed fire-resistant materials shall be identified by density and thickness required for a given fire-resistance rating.

722.5.1.4 Concrete-protected columns. The fire resistance of structural steel columns protected with concrete, as illustrated in Figure 722.5.1(6)(a) and (b), shall be permitted to be determined from the following expression:

R = Ro (1 + 0.03 m ) (Equation 7-14)

where:

Ro = 10 ( W/D ) 0.7 + 17 ( h 1.6 / kc 0.2) ×

[1 + 26 { H/pccch ( L + h) } 0.8 ] As used in these expressions:

R = Fire endurance at equilibrium moisture conditions (minutes).

Ro = Fire endurance at zero moisture content

(minutes).

m = Equilibrium moisture content of the concrete by

volume (percent).

W = Average weight of the structural steel column

(pounds per linear foot).

D = Heated perimeter of the structural steel column

(inches).

h = Thickness of the concrete cover (inches).

kc = Ambient temperature thermal conductivity of the

concrete (Btu/hr ft °F).

H = Ambient temperature thermal capacity of the

steel column = 0.11W (Btu/ ft °F).

pc = Concrete density (pounds per cubic foot). cc = Ambient temperature specific heat of concrete

(Btu/lb °F).

L = Interior dimension of one side of a square

concrete box protection (inches).

722.5.1.4.1 Reentrant space filled. For wide-flange structural steel columns completely encased in concrete with all reentrant spaces filled [Figure 722.5.1(6)(c)], the thermal capacity of the concrete within the reentrant spaces shall be permitted to be added to the thermal capacity of the steel column, as follows:

H = 0.11 W + ( pccc /144) ( bfd - As )

(Equation 7-15)

where:

bf = Flange width of the structural steel column

(inches).

d = Depth of the structural steel column (inches).

As = Cross-sectional area of the steel column

(square inches).

722.5.1.4.2 Concrete properties unknown. If specific data on the properties of concrete are not available, the values given in Table 722.5.1(2) are permitted.

FIRE AND SMOKE PROTECTION FEATURES

722.5.1.4.3 Minimum concrete cover. For structural steel column encased in concrete with all reentrant spaces filled, Figure 722.5.1(6)(c) and Tables 722.5.1(7) and 722.5.1(8) indicate the thickness of concrete cover required for various fireresistance ratings for typical wide-flange sections. The thicknesses of concrete indicated in these tables apply to structural steel columns larger than those listed.

722.5.1.4.4 Minimum precast concrete cover. For structural steel columns protected with precast concrete column covers as shown in Figure 722.5.1(6)(a), Tables 722.5.1(9) and 722.5.1(10) indicate the thickness of the column covers required for various fire-resistance ratings for typical wideflange shapes. The thicknesses of concrete given in these tables apply to structural steel columns larger than those listed.

722.5.1.4.5 Masonry protection. The fire resistance of structural steel columns protected with concrete masonry units or clay masonry units as illustrated in Figure 722.5.1(7) shall be permitted to be determined from the following expression:

R = 0.17 ( W/D ) 0.7 + [0.285 ( Te 1.6/ K 0.2)]

[1.0 + 42.7 {( As/dm Te )/(0.25 p + Te )} 0.8 ]

(Equation 7-16)

where:

R = Fire-resistance rating of column assembly

(hours).

W = Average weight of structural steel column

(pounds per foot).

D = Heated perimeter of structural steel column

(inches) [see Figure 722.5.1(7)]. Te = Equivalent thickness of concrete or clay

masonry unit (inches) (see Table 722.3.2, Note a or Section 722.4.1).

K = Thermal conductivity of concrete or clay

masonry unit (Btu/hr · ft · °F) [see Table 722.5.1(3)].

As = Cross-sectional area of structural steel column

(square inches).

dm = Density of the concrete or clay masonry unit

(pounds per cubic foot).

p = Inner perimeter of concrete or clay masonry

protection (inches) [see Figure 722.5.1(7)].

722.5.1.4.6 Equivalent concrete masonry thick- ness. For structural steel columns protected with concrete masonry, Table 722.5.1(5) gives the equivalent thickness of concrete masonry required for various fire-resistance ratings for typical column shapes. For structural steel columns protected with clay masonry, Table 722.5.1(6) gives the equivalent thickness of concrete masonry required for various fire-resistance ratings for typical column shapes.

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

722.5.2 Structural steel beams and girders. The fireresistance ratings of structural steel beams and girders shall be based on the size of the element and the type of protection provided in accordance with this section.

722.5.2.1 Determination of fire resistance. These procedures establish a basis for determining resistance of structural steel beams and girders that differ in size from that specified in approved fire-resistance-rated assemblies as a function of the thickness of fire-resistant material and the weight (W) and heated perimeter ( D ) of the beam or girder. As used in these sections, W is the average weight of a structural steel element in pounds per linear foot (plf). The heated perimeter, D, is the inside perimeter of the fire-resistant material in inches as illustrated in Figure 722.5.2.

722.5.2.1.1 Weight-to-heated perimeter. The weight-to-heated-perimeter ratios ( W/D ), for both contour and box fire-resistant protection profiles, for the wide flange shapes most often used as beams or girders are given in Table 722.5.1(4). For different shapes, the weight-to-heated-perimeter ratios ( W/D ) shall be determined in accordance with the definitions given in this section.

722.5.2.1.2 Beam and girder substitutions. Except as provided for in Section 722.5.2.2, structural steel beams in approved fire-resistance-rated assemblies shall be considered to be the minimum permissible size. Other beam or girder shapes shall be permitted to be substituted provided that the weight-to-heatedperimeter ratio ( W/D ) of the substitute beam is equal to or greater than that of the beam specified in the approved assembly.

722.5.2.2 Sprayed fire-resistant materials. The provisions in this section apply to structural steel beams and girders protected with sprayed fire-resistant materials. Larger or smaller beam and girder shapes shall be permitted to be substituted for beams specified in approved unrestrained or restrained fire-resistancerated assemblies, provided that the thickness of the fireresistant material is adjusted in accordance with the following expression:

h 2 = h 1 [( W 1 / D 1) + 0.60] / [( W 2 / D 2) + 0.60]

(Equation 7-17)

where:

h = Thickness of sprayed fire-resistant material in

inches.

W = Weight of the structural steel beam or girder in

pounds per linear foot.

D = Heated perimeter of the structural steel beam in

inches.

Subscript 1 refers to the beam and fire-resistant material thickness in the approved assembly.

Subscript 2 refers to the substitute beam or girder and the required thickness of fire-resistant material.

The fire resistance of structural steel beams and girders protected with intumescent or mastic fire-resistant coatings shall be determined on the basis of fireresistance tests in accordance with Section 703.2.

722.5.2.2.1 Minimum thickness. The use of Equation 7-17 is subject to the following conditions:

  1. The weight-to-heated-perimeter ratio for the substitute beam or girder ( W2/D2 ) shall be not less than 0.37.

  2. The thickness of fire protection materials calculated for the substitute beam or girder ( T1 ) shall be not less than 3 /8 inch (9.5 mm).

  3. The unrestrained or restrained beam rating shall be not less than 1 hour.

  4. Where used to adjust the material thickness for a restrained beam, the use of this procedure is limited to structural steel sections classified as compact in accordance with AISC 360.

722.5.2.3 Structural steel trusses. The fire resistance of structural steel trusses protected with fire-resistant materials sprayed to each of the individual truss elements shall be permitted to be determined in accordance with this section. The thickness of the fireresistant material shall be determined in accordance with Section 722.5.1.3. The weight-to-heated-perimeter ratio ( W/D ) of truss elements that can be simultaneously exposed to fire on all sides shall be determined on the same basis as columns, as specified in Section 722.5.1.1. The weight-to-heated-perimeter ratio ( W/D ) of truss elements that directly support floor or roof assembly shall be determined on the same basis as beams and girders, as specified in Section 722.5.2.1.

The fire resistance of structural steel trusses protected with intumescent or mastic fire-resistant coatings shall be determined on the basis of fire-resistance tests in accordance with Section 703.2.

722.6 Wood assemblies.

The provisions of this section contain procedures by which the fire-resistance ratings of wood assemblies are established by calculations.

722.6.1 General. This section contains procedures for calculating the fire-resistance ratings of walls, floor/ceiling and roof/ceiling assemblies based in part on the standard method of testing referenced in Section 703.2.

282 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

722.6.1.1 Maximum fire-resistance rating. Fire-resistance ratings calculated for assemblies using the methods in Section 722.6 shall be limited to not more than 1 hour.

722.6.1.2 Dissimilar membranes. Where dissimilar membranes are used on a wall assembly that requires consideration of fire exposure from both sides, the calculation shall be made from the least fire-resistant (weaker) side.

722.6.2 Walls, floors and roofs. These procedures apply to both load-bearing and nonload-bearing assemblies.

722.6.2.1 Fire-resistance rating of wood frame assemblies. The fire-resistance rating of a wood frame assembly is equal to the sum of the time assigned to the membrane on the fire-exposed side, the time assigned to the framing members and the time assigned for additional contribution by other protective measures such as insulation. The membrane on the unexposed side shall not be included in determining the fire resistance of the assembly.

722.6.2.2 Time assigned to membranes. Table 722.6.2(1) indicates the time assigned to membranes on the fire-exposed side.

722.6.2.3 Exterior walls. For an exterior wall with a fire separation distance greater than 10 feet (3048 mm), the wall is assigned a rating dependent on the interior membrane and the framing as described in Tables 722.6.2(1) and 722.6.2(2). The membrane on the outside of the nonfire-exposed side of exterior walls with a fire separation distance greater than 10 feet (3048 mm) shall consist of sheathing, sheathing paper and siding as described in Table 722.6.2(3).

722.6.2.4 Floors and roofs. In the case of a floor or roof, the standard test provides only for testing for fire exposure from below. Except as noted in Section 703.3, Item 5, floor or roof assemblies of wood framing shall have an upper membrane consisting of a subfloor and finished floor conforming to Table 722.6.2(4) or any other membrane that has a contribution to fire resistance of not less than 15 minutes in Table 722.6.2(1).

case of a floor or roof, the standard test provides only for testing for fire exposure from below. Except as noted in Section 703.3, Item 5, floor or roof assemblies of wood framing shall have an upper membrane consisting of a subfloor and finished floor conforming to Table 722.6.2(4) or any other membrane that has a contribution to fire resistance of not less than 15 minutes in Table 722.6.2(1).

722.6.2.5 Additional protection. Table 722.6.2(5) indicates the time increments to be added to the fire resistance where glass fiber, rockwool, slag mineral wool or cellulose insulation is incorporated in the assembly.

722.6.2.6 Fastening. Fastening of wood frame assemblies and the fastening of membranes to the wood framing members shall be done in accordance with Chapter 23.

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 722.5.1(1)

W/D RATIOS FOR STEEL COLUMNS
STRUCTURAL SHAPE CONTOUR PROFILE BOX
PROFILE
STRUCTURAL SHAPE CONTOUR PROFILE BOX
PROFILE
W14 × 233 2.55 3.65 W10 × 112 1.81 2.57
× 211 2.32 3.35 × 100 1.64 2.33
× 193 2.14 3.09 × 88 1.45 2.08
× 176 1.96 2.85 × 77 1.28 1.85
× 159 1.78 2.60 × 68 1.15 1.66
× 145 1.64 2.39 × 60 1.01 1.48
× 132 1.56 2.25 × 54 0.922 1.34
× 120 1.42 2.06 × 49 0.84 1.23
× 109 1.29 1.88 × 45 0.888 1.24
× 99 1.18 1.72 × 39 0.78 1.09
× 90 1.08 1.58 × 33 0.661 0.93
× 82 1.23 1.68
× 74 1.12 1.53 W8 × 67 1.37 1.94
× 68 1.04 1.41 × 58 1.20 1.71
× 61 0.928 1.28 × 48 1.00 1.44
× 53 0.915 1.21 × 40 0.849 1.23
× 48 0.835 1.10 × 35 0.749 1.08
× 43 0.752 0.99 × 31 0.665 0.97
× 28 0.688 0.96
W12 × 190 2.50 3.51 × 24 0.591 0.83
× 170 2.26 3.20 × 21 0.577 0.77
× 152 2.04 2.90 × 18 0.499 0.67
× 136 1.86 2.63
× 120 1.65 2.36 W6 ×25 0.696 1.00
× 106 1.47 2.11 × 20 0.563 0.82
× 96 1.34 1.93 × 16 0.584 0.78
× 87 1.22 1.76 × 15 0.431 0.63
× 79 1.11 1.61 × 12 0.448 0.60
× 72 1.02 1.48 × 9 0.338 0.46
× 65 0.925 1.35
× 58 0.925 1.31 W5 ×19 0.644 0.93
× 53 0.855 1.20 × 16 0.55 0.80
× 50 0.909 1.23
× 45 0.829 1.12 W4 ×13 0.556 0.79
× 40 0.734 1.00

For SI: 1 pound per linear foot per inch = 0.059 kg/m/mm.

TABLE 722.5.1(2) PROPERTIES OF CONCRETE
PROPERTY NORMAL-WEIGHT CONCRETE STRUCTURAL LIGHTWEIGHT CONCRETE
Thermal conductivity (_k_c) 0.95 Btu/hr**·** ft**·** °F 0.35 Btu/hr**·** ft**·** °F
Specific heat (_c_c) 0.20 Btu/lb °F 0.20 Btu/lb °F
Density (_P_c) 145 lb/ft3 110 lb/ft3
Equilibrium (free) moisture content (m) by volume 4% 5%

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 lb/ft 3 = 16.0185 kg/m 3, Btu/hr · ft · °F = 1.731 W/(m · K).

284 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 722.5.1(3) THERMAL CONDUCTIVITY OF CONCRETE OR CLAY MASONRY UNITS

DENSITY (d ) OF UNITS (lb/ft3)
m
THERMAL CONDUCTIVITY (K) OF UNITS (Btu/hr · ft · °F)
Concrete Masonry Units Concrete Masonry Units
80 0.207
85 0.228
90 0.252
95 0.278
100 0.308
105 0.340
110 0.376
115 0.416
120 0.459
125 0.508
130 0.561
135 0.620
140 0.685
145 0.758
150 0.837
Clay Masonry Units Clay Masonry Units
120 1.25
130 2.25

For SI: 1 pound per cubic foot = 16.0185 kg/m 3, Btu/hr · ft · °F = 1.731 W/(m · K).

TABLE 722.5.1(4) WEIGHT-TO-HEATED-PERIMETER RATIOS ( W/D ) FOR TYPICAL WIDE FLANGE BEAM AND GIRDER SHAPES

STRUCTURAL SHAPE CONTOUR PROFILE BOX PROFILE STRUCTURAL SHAPE CONTOUR PROFILE BOX PROFILE
W36 x 300 2.50 3.33 W24 x 68 0.942 1.21
x 280 2.35 3.12 x 62 0.934 1.14
x 260 2.18 2.92 x 55 0.828 1.02
x 245 2.08 2.76
x 230 1.95 2.61 W21 x 147 1.87 2.60
x 210 1.96 2.45 x 132 1.68 2.35
x 194 1.81 2.28 x 122 1.57 2.19
x 182 1.72 2.15 x 111 1.43 2.01
x 170 1.60 2.01 x 101 1.30 1.84
x 160 1.51 1.90 x 93 1.40 1.80
x 150 1.43 1.79 x 83 1.26 1.62
x 135 1.29 1.63 x 73 1.11 1.44
x 68 1.04 1.35

(continued)

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 722.5.1(4)—continued WEIGHT-TO-HEATED-PERIMETER RATIOS ( W/D ) FOR TYPICAL WIDE FLANGE BEAM AND GIRDER SHAPES

STRUCTURAL SHAPE CONTOUR PROFILE BOX PROFILE STRUCTURAL SHAPE CONTOUR PROFILE BOX PROFILE
W33 x 241 2.13 2.86 W21 x 62 0.952 1.23
x 221 1.97 2.64 x 57 0.952 1.17
x 201 1.79 2.42 x 50 0.838 1.04
x 152 1.53 1.94 x 44 0.746 0.92
x 141 1.43 1.80
x 130 1.32 1.67 W18 x 119 1.72 2.42
x 118 1.21 1.53 x 106 1.55 2.18
x 97 1.42 2.01
W30 x 211 2.01 2.74 x 86 1.27 1.80
x 191 1.85 2.50 x 76 1.13 1.60
x 173 1.66 2.28 x 71 1.22 1.59
x 132 1.47 1.85 x 65 1.13 1.47
x 124 1.39 1.75 x 60 1.04 1.36
x 116 1.30 1.65 x 55 0.963 1.26
x 108 1.21 1.54 x 50 0.88 1.15
x 99 1.12 1.42 x 46 0.878 1.09
x 40 0.768 0.96
W27 x 178 1.87 2.55 x 35 0.672 0.85
x 161 1.70 2.33
x 146 1.55 2.12 W16 x 100 1.59 2.25
x 114 1.39 1.76 x 89 1.43 2.03
x 102 1.24 1.59 x 77 1.25 1.78
x 94 1.15 1.47 x 67 1.09 1.56
x 84 1.03 1.33 x 57 1.09 1.43
x 50 0.962 1.26
x 45 0.870 1.15
W24 x 162 1.88 2.57 x 40 0.780 1.03
x 146 1.70 2.34 x 36 0.702 0.93
x 131 1.54 2.12 x 31 0.661 0.83
x 117 1.38 1.91 x 26 0.558 0.70
x 104 1.24 1.71
x 94 1.28 1.63 W14 x 132 1.89 3.00
x 84 1.15 1.47 x 120 1.71 2.75
x 76 1.05 1.34 x 109 1.57 2.52
W14 x 99 1.43 2.31 W10 x 30 0.806 1.12
x 90 1.31 2.11 x 26 0.708 0.98
x 82 1.45 2.12 x 22 0.606 0.84
x 74 1.32 1.93 x 19 0.607 0.78
x 68 1.22 1.78 x 17 0.543 0.70
x 61 1.10 1.61 x 15 0.484 0.63
x 53 1.06 1.48 x 12 0.392 0.51
x 48 0.970 1.35

(continued)

286 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 722.5.1(4)—continued WEIGHT-TO-HEATED-PERIMETER RATIOS ( W/D ) FOR TYPICAL WIDE FLANGE BEAM AND GIRDER SHAPES

STRUCTURAL SHAPE CONTOUR PROFILE BOX PROFILE STRUCTURAL SHAPE CONTOUR PROFILE BOX PROFILE
W14 x 43 0.874 1.22 W8 x 67 1.65 2.55
x 38 0.809 1.09 x 58 1.44 2.26
x 34 0.725 0.98 x 48 1.21 1.91
x 30 0.644 0.87 x 40 1.03 1.63
x 26 0.628 0.79 x 35 0.907 1.44
x 22 0.534 0.68 x 31 0.803 1.29
x 28 0.819 1.24
W12 x 87 1.47 2.34 x 24 0.704 1.07
x 79 1.34 2.14 x 21 0.675 0.96
x 72 1.23 1.97 x 18 0.583 0.84
x 65 1.11 1.79 x 15 0.551 0.74
x 58 1.10 1.69 x 13 0.483 0.65
x 53 1.02 1.55 x 10 0.375 0.51
x 50 1.06 1.54
x 45 0.974 1.40 W6 x 25 0.839 1.33
x 40 0.860 1.25 x 20 0.678 1.09
x 35 0.810 1.11 x 16 0.684 0.96
x 30 0.699 0.96 x 15 0.521 0.83
x 26 0.612 0.84 x 12 0.526 0.75
x 22 0.623 0.77 x 9 0.398 0.57
x 19 0.540 0.67
x 16 0.457 0.57 W5 x 19 0.776 1.24
x 14 0.405 0.50 x 16 0.664 1.07
W10 x 112 2.17 3.38 W4 x 13 0.670 1.05
x 100 1.97 3.07
x 88 1.74 2.75 2.75 2.75 2.75
x 77 1.54 2.45 2.45 2.45 2.45
x 68 1.38 2.20 2.20 2.20 2.20
x 60 1.22 1.97 1.97 1.97 1.97
x 54 1.11 1.79 1.79 1.79 1.79
x 49 1.01 1.64 1.64 1.64 1.64
x 45 1.06 1.59 1.59 1.59 1.59
x 39 0.94 1.40 1.40 1.40 1.40
x 33 0.77 1.20 1.20 1.20 1.20

For SI: 1 pound per linear foot per inch = 0.059 kg/m/mm.

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 722.5.1(5) FIRE RESISTANCE OF CONCRETE MASONRY PROTECTED STEEL COLUMNS

COLUMN SIZE CONCRETE
MASONRY
DENSITY
POUNDS PER
CUBIC FOOT
MINIMUM REQUIRED EQUIVALENT
THICKNESS FOR FIRE-RESISTANCE
RATING OF CONCRETE MASONRY
PROTECTION ASSEMBLY, T (inches)
e
COLUMN SIZE CONCRETE
MASONRY
DENSITY
POUNDS PER
CUBIC FOOT
MINIMUM REQUIRED EQUIVALENT
THICKNESS FOR FIRE-RESISTANCE
RATING OF CONCRETE MASONRY
PROTECTION ASSEMBLY, T (inches)
e
COLUMN SIZE CONCRETE
MASONRY
DENSITY
POUNDS PER
CUBIC FOOT
1 hour 2 hours 3 hours 4 hours 4 hours 4 hours 1 hour 2 hours 3 hours 4 hours
W14 × 82 80 0.74 1.61 2.36 3.04 W10 × 68 80 0.72 1.58 2.33 3.01
W14 × 82 100 0.89 1.85 2.67 3.40 3.40 100 0.87 1.83 2.65 3.38
W14 × 82 110 0.96 1.97 2.81 3.57 3.57 110 0.94 1.95 2.79 3.55
W14 × 82 120 1.03 2.08 2.95 3.73 3.73 120 1.01 2.06 2.94 3.72
W14 × 68 80 0.83 1.70 2.45 3.13 W10 × 54 80 0.88 1.76 2.53 3.21
W14 × 68 100 0.99 1.95 2.76 3.49 3.49 100 1.04 2.01 2.83 3.57
W14 × 68 110 1.06 2.06 2.91 3.66 3.66 110 1.11 2.12 2.98 3.73
W14 × 68 120 1.14 2.18 3.05 3.82 3.82 120 1.19 2.24 3.12 3.90
W14 × 53 80 0.91 1.81 2.58 3.27 W10 × 45 80 0.92 1.83 2.60 3.30
W14 × 53 100 1.07 2.05 2.88 3.62 3.62 100 1.08 2.07 2.90 3.64
W14 × 53 110 1.15 2.17 3.02 3.78 3.78 110 1.16 2.18 3.04 3.80
W14 × 53 120 1.22 2.28 3.16 3.94 3.94 120 1.23 2.29 3.18 3.96
W14 × 43 80 1.01 1.93 2.71 3.41 W10 × 33 80 1.06 2.00 2.79 3.49
W14 × 43 100 1.17 2.17 3.00 3.74 3.74 100 1.22 2.23 3.07 3.81
W14 × 43 110 1.25 2.28 3.14 3.90 3.90 110 1.30 2.34 3.20 3.96
W14 × 43 120 1.32 2.38 3.27 4.05 4.05 120 1.37 2.44 3.33 4.12
W12 × 72 80 0.81 1.66 2.41 3.09 W8 × 40 80 0.94 1.85 2.63 3.33
W12 × 72 100 0.91 1.88 2.70 3.43 3.43 100 1.10 2.10 2.93 3.67
W12 × 72 110 0.99 1.99 2.84 3.60 3.60 110 1.18 2.21 3.07 3.83
W12 × 72 120 1.06 2.10 2.98 3.76 3.76 120 1.25 2.32 3.20 3.99
W12 × 58 80 0.88 1.76 2.52 3.21 W8 × 31 80 1.06 2.00 2.78 3.49
W12 × 58 100 1.04 2.01 2.83 3.56 3.56 100 1.22 2.23 3.07 3.81
W12 × 58 110 1.11 2.12 2.97 3.73 3.73 110 1.29 2.33 3.20 3.97
W12 × 58 120 1.19 2.23 3.11 3.89 3.89 120 1.36 2.44 3.33 4.12
W12 × 50 80 0.91 1.81 2.58 3.27 W8 × 24 80 1.14 2.09 2.89 3.59
W12 × 50 100 1.07 2.05 2.88 3.62 3.62 100 1.29 2.31 3.16 3.90
W12 × 50 110 1.15 2.17 3.02 3.78 3.78 110 1.36 2.42 3.28 4.05
W12 × 50 120 1.22 2.28 3.16 3.94 3.94 120 1.43 2.52 3.41 4.20
W12 × 40 80 1.01 1.94 2.72 3.41 W8 × 18 80 1.22 2.20 3.01 3.72
W12 × 40 100 1.17 2.17 3.01 3.75 3.75 100 1.36 2.40 3.25 4.01
W12 × 40 110 1.25 2.28 3.14 3.90 3.90 110 1.42 2.50 3.37 4.14
W12 × 40 120 1.32 2.39 3.27 4.06 4.06 120 1.48 2.59 3.49 4.28
4 × 4 ×1/2 wall
thickness
80 0.93 1.90 2.71 3.43 4 double
extra strong
0.674 wall
thickness
80 0.80 1.75 2.56 3.28
4 × 4 ×1/2 wall
thickness
100 1.08 2.13 2.99 3.76 3.76 100 0.95 1.99 2.85 3.62
4 × 4 ×1/2 wall
thickness
110 1.16 2.24 3.13 3.91 3.91 110 1.02 2.10 2.99 3.78
4 × 4 ×1/2 wall
thickness
120 1.22 2.34 3.26 4.06 4.06 120 1.09 2.20 3.12 3.93
4 × 4 ×3/8 wall
thickness
80 1.05 2.03 2.84 3.57 4 extra strong
0.337 wall
thickness
80 1.12 2.11 2.93 3.65
4 × 4 ×3/8 wall
thickness
100 1.20 2.25 3.11 3.88 3.88 100 1.26 2.32 3.19 3.95
4 × 4 ×3/8 wall
thickness
110 1.27 2.35 3.24 4.02 4.02 110 1.33 2.42 3.31 4.09
4 × 4 ×3/8 wall
thickness
120 1.34 2.45 3.37 4.17 4.17 120 1.40 2.52 3.43 4.23

(continued)

288 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 722.5.1(5)—continued FIRE RESISTANCE OF CONCRETE MASONRY PROTECTED STEEL COLUMNS

COLUMN SIZE CONCRETE
MASONRY
DENSITY
POUNDS PER
CUBIC FOOT
MINIMUM REQUIRED EQUIVALENT
THICKNESS FOR FIRE-RESISTANCE
RATING OF CONCRETE MASONRY
PROTECTION ASSEMBLY, T (inches)
e
COLUMN SIZE CONCRETE
MASONRY
DENSITY
POUNDS PER
CUBIC FOOT
MINIMUM REQUIRED EQUIVALENT
THICKNESS FOR FIRE-RESISTANCE
RATING OF CONCRETE MASONRY
PROTECTION ASSEMBLY, T (inches)
e
COLUMN SIZE CONCRETE
MASONRY
DENSITY
POUNDS PER
CUBIC FOOT
1 hour 2 hours 3 hours 4 hours 4 hours 4 hours 1 hour 2 hours 3 hours 4 hours
4 × 4 ×1/4 wall
thickness
80 1.21 2.20 3.01 3.73 4 standard
0.237 wall
thickness
80 1.26 2.25 3.07 3.79
4 × 4 ×1/4 wall
thickness
100 1.35 2.40 3.26 4.02 4.02 100 1.40 2.45 3.31 4.07
4 × 4 ×1/4 wall
thickness
110 1.41 2.50 3.38 4.16 4.16 110 1.46 2.55 3.43 4.21
4 × 4 ×1/4 wall
thickness
120 1.48 2.59 3.50 4.30 4.30 120 1.53 2.64 3.54 4.34
6 × 6 ×1/2 wall
thickness
80 0.82 1.75 2.54 3.25 5 double extra
strong 0.750
wall thickness
80 0.70 1.61 2.40 3.12
6 × 6 ×1/2 wall
thickness
100 0.98 1.99 2.84 3.59 3.59 100 0.85 1.86 2.71 3.47
6 × 6 ×1/2 wall
thickness
110 1.05 2.10 2.98 3.75 3.75 110 0.91 1.97 2.85 3.63
6 × 6 ×1/2 wall
thickness
120 1.12 2.21 3.11 3.91 3.91 120 0.98 2.02 2.99 3.79
6 × 6 ×3/8 wall
thickness
80 0.96 1.91 2.71 3.42 5 extra strong
0.375 wall
thickness
80 1.04 2.01 2.83 3.54
6 × 6 ×3/8 wall
thickness
100 1.12 2.14 3.00 3.75 3.75 100 1.19 2.23 3.09 3.85
6 × 6 ×3/8 wall
thickness
110 1.19 2.25 3.13 3.90 3.90 110 1.26 2.34 3.22 4.00
6 × 6 ×3/8 wall
thickness
120 1.26 2.35 3.26 4.05 4.05 120 1.32 2.44 3.34 4.14
6 × 6 ×1/4 wall
thickness
80 1.14 2.11 2.92 3.63 5 standard
0.258 wall
thickness
80 1.20 2.19 3.00 3.72
6 × 6 ×1/4 wall
thickness
100 1.29 2.32 3.18 3.93 3.93 100 1.34 2.39 3.25 4.00
6 × 6 ×1/4 wall
thickness
110 1.36 2.43 3.30 4.08 4.08 110 1.41 2.49 3.37 4.14
6 × 6 ×1/4 wall
thickness
120 1.42 2.52 3.43 4.22 4.22 120 1.47 2.58 3.49 4.28
8 × 8 ×1/2 wall
thickness
80 0.77 1.66 2.44 3.13 6 double extra
strong 0.864
wall thickness
80 0.59 1.46 2.23 2.92
8 × 8 ×1/2 wall
thickness
100 0.92 1.91 2.75 3.49 3.49 100 0.73 1.71 2.54 3.29
8 × 8 ×1/2 wall
thickness
110 1.00 2.02 2.89 3.66 3.66 110 0.80 1.82 2.69 3.47
8 × 8 ×1/2 wall
thickness
120 1.07 2.14 3.03 3.82 3.82 120 0.86 1.93 2.83 3.63
8 × 8 ×3/8 wall
thickness
80 0.91 1.84 2.63 3.33 6 extra strong
0.432 wall
thickness
80 0.94 1.90 2.70 3.42
8 × 8 ×3/8 wall
thickness
100 1.07 2.08 2.92 3.67 3.67 100 1.10 2.13 2.98 3.74
8 × 8 ×3/8 wall
thickness
110 1.14 2.19 3.06 3.83 3.83 110 1.17 2.23 3.11 3.89
8 × 8 ×3/8 wall
thickness
120 1.21 2.29 3.19 3.98 3.98 120 1.24 2.34 3.24 4.04
8 × 8 ×1/4 wall
thickness
80 1.10 2.06 2.86 3.57 6 standard
0.280 wall
thickness
80 1.14 2.12 2.93 3.64
8 × 8 ×1/4 wall
thickness
100 1.25 2.28 3.13 3.87 3.87 100 1.29 2.33 3.19 3.94
8 × 8 ×1/4 wall
thickness
110 1.32 2.38 3.25 4.02 4.02 110 1.36 2.43 3.31 4.08
8 × 8 ×1/4 wall
thickness
120 1.39 2.48 3.38 4.17 4.17 120 1.42 2.53 3.43 4.22

For SI: 1 inch = 25.4 mm, 1 pound per cubic feet = 16.02 kg/m 3 . Note: Tabulated values assume 1-inch air gap between masonry and steel section.

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 722.5.1(6) FIRE RESISTANCE OF CLAY MASONRY PROTECTED STEEL COLUMNS

COLUMN SIZE CLAY
MASONRY
DENSITY,
POUNDS PER
CUBIC FOOT
MINIMUM REQUIRED EQUIVALENT
THICKNESS FOR FIRE-RESISTANCE
RATING OF CLAY MASONRY
PROTECTION ASSEMBLY, T (inches)
e
COLUMN SIZE CLAY
MASONRY
DENSITY,
POUNDS PER
CUBIC FOOT
MINIMUM REQUIRED EQUIVALENT
THICKNESS FOR FIRE-RESISTANCE
RATING OF CLAY MASONRY
PROTECTION ASSEMBLY, T (inches)
e
COLUMN SIZE CLAY
MASONRY
DENSITY,
POUNDS PER
CUBIC FOOT
1 hour 2 hours 3 hours 4 hours 4 hours 4 hours 1 hour 2 hours 3 hours 4 hours
W14 × 82 120 1.23 2.42 3.41 4.29 W10 × 68 120 1.27 2.46 3.26 4.35
W14 × 82 130 1.40 2.70 3.78 4.74 4.74 130 1.44 2.75 3.83 4.80
W14 × 68 120 1.34 2.54 3.54 4.43 W10 × 54 120 1.40 2.61 3.62 4.51
W14 × 68 130 1.51 2.82 3.91 4.87 4.87 130 1.58 2.89 3.98 4.95
W14 × 53 120 1.43 2.65 3.65 4.54 W10 × 45 120 1.44 2.66 3.67 4.57
W14 × 53 130 1.61 2.93 4.02 4.98 4.98 130 1.62 2.95 4.04 5.01
W14 × 43 120 1.54 2.76 3.77 4.66 W10 × 33 120 1.59 2.82 3.84 4.73
W14 × 43 130 1.72 3.04 4.13 5.09 5.09 130 1.77 3.10 4.20 5.13
W12 × 72 120 1.32 2.52 3.51 4.40 W8 × 40 120 1.47 2.70 3.71 4.61
W12 × 72 130 1.50 2.80 3.88 4.84 4.84 130 1.65 2.98 4.08 5.04
W12 × 58 120 1.40 2.61 3.61 4.50 W8 × 31 120 1.59 2.82 3.84 4.73
W12 × 58 130 1.57 2.89 3.98 4.94 4.94 130 1.77 3.10 4.20 5.17
W12 × 50 120 1.43 2.65 3.66 4.55 W8 × 24 120 1.66 2.90 3.92 4.82
W12 × 50 130 1.61 2.93 4.02 4.99 4.99 130 1.84 3.18 4.28 5.25
W12 × 40 120 1.54 2.77 3.78 4.67 W8 × 18 120 1.75 3.00 4.01 4.91
W12 × 40 130 1.72 3.05 4.14 5.10 5.10 130 1.93 3.27 4.37 5.34
STEEL TUBING STEEL TUBING STEEL TUBING STEEL TUBING STEEL TUBING STEEL TUBING STEEL PIPE STEEL PIPE STEEL PIPE STEEL PIPE STEEL PIPE STEEL PIPE
NOMINAL
TUBE SIZE
(inches)
CLAY
MASONRY
DENSITY,
POUNDS PER
CUBIC FOOT
MINIMUM REQUIRED EQUIVALENT
THICKNESS FOR FIRE-RESISTANCE
RATING OF CLAY MASONRY
PROTECTION ASSEMBLY,****_ T_e (inches)
MINIMUM REQUIRED EQUIVALENT
THICKNESS FOR FIRE-RESISTANCE
RATING OF CLAY MASONRY
PROTECTION ASSEMBLY,****_ T_e (inches)
MINIMUM REQUIRED EQUIVALENT
THICKNESS FOR FIRE-RESISTANCE
RATING OF CLAY MASONRY
PROTECTION ASSEMBLY,****_ T_e (inches)
MINIMUM REQUIRED EQUIVALENT
THICKNESS FOR FIRE-RESISTANCE
RATING OF CLAY MASONRY
PROTECTION ASSEMBLY,****_ T_e (inches)
NOMINAL PIPE
SIZE (inches)
CLAY
MASONRY
DENSITY,
POUNDS PER
CUBIC FOOT
MINIMUM REQUIRED EQUIVALENT
THICKNESS FOR FIRE-RESISTANCE
RATING OF CLAY MASONRY
PROTECTION ASSEMBLY,****_ T_e (inches)
MINIMUM REQUIRED EQUIVALENT
THICKNESS FOR FIRE-RESISTANCE
RATING OF CLAY MASONRY
PROTECTION ASSEMBLY,****_ T_e (inches)
MINIMUM REQUIRED EQUIVALENT
THICKNESS FOR FIRE-RESISTANCE
RATING OF CLAY MASONRY
PROTECTION ASSEMBLY,****_ T_e (inches)
MINIMUM REQUIRED EQUIVALENT
THICKNESS FOR FIRE-RESISTANCE
RATING OF CLAY MASONRY
PROTECTION ASSEMBLY,****_ T_e (inches)
NOMINAL
TUBE SIZE
(inches)
CLAY
MASONRY
DENSITY,
POUNDS PER
CUBIC FOOT
1 hour 2 hours 3 hours 4 hours 4 hours 4 hours 1 hour 2 hours 3 hours 4 hours
4 × 4 ×1/2 wall
thickness
120 1.44 2.72 3.76 4.68 4 double extra
strong 0.674
wall thickness
120 1.26 2.55 3.60 4.52
4 × 4 ×1/2 wall
thickness
130 1.62 3.00 4.12 5.11 5.11 130 1.42 2.82 3.96 4.95
4 × 4 ×3/8 wall
thickness
120 1.56 2.84 3.88 4.78 4 extra strong
0.337 wall
thickness
120 1.60 2.89 3.92 4.83
4 × 4 ×3/8 wall
thickness
130 1.74 3.12 4.23 5.21 5.21 130 1.77 3.16 4.28 5.25
4 × 4 ×1/4 wall
thickness
120 1.72 2.99 4.02 4.92 4 standard
0.237 wall
thickness
120 1.74 3.02 4.05 4.95
4 × 4 ×1/4 wall
thickness
130 1.89 3.26 4.37 5.34 5.34 130 1.92 3.29 4.40 5.37
6 × 6 ×1/2 wall
thickness
120 1.33 2.58 3.62 4.52 5 double extra
strong 0.750
wall thickness
120 1.17 2.44 3.48 4.40
6 × 6 ×1/2 wall
thickness
130 1.50 2.86 3.98 4.96 4.96 130 1.33 2.72 3.84 4.83
6 × 6 ×3/8 wall
thickness
120 1.48 2.74 3.76 4.67 5 extra strong
0.375
wall thickness
120 1.55 2.82 3.85 4.76
6 × 6 ×3/8 wall
thickness
130 1.65 3.01 4.13 5.10 5.10 130 1.72 3.09 4.21 5.18
6 × 6 ×1/4 wall
thickness
120 1.66 2.91 3.94 4.84 5 standard
0.258 wall
thickness
120 1.71 2.97 4.00 4.90
6 × 6 ×1/4 wall
thickness
130 1.83 3.19 4.30 5.27 5.27 130 1.88 3.24 4.35 5.32
8 × 8 ×1/2 wall
thickness
120 1.27 2.50 3.52 4.42 6 double extra
strong 0.864
wall thickness
120 1.04 2.28 3.32 4.23
8 × 8 ×1/2 wall
thickness
130 1.44 2.78 3.89 4.86 4.86 130 1.19 2.60 3.68 4.67
8 × 8 ×3/8 wall
thickness
120 1.43 2.67 3.69 4.59 6 extra strong
0.432 wall
thickness
120 1.45 2.71 3.75 4.65
8 × 8 ×3/8 wall
thickness
130 1.60 2.95 4.05 5.02 5.02 130 1.62 2.99 4.10 5.08
8 × 8 ×1/4 wall
thickness
120 1.62 2.87 3.89 4.78 6 standard
0.280 wall
thickness
120 1.65 2.91 3.94 4.84
8 × 8 ×1/4 wall
thickness
130 1.79 3.14 4.24 5.21 5.21 130 1.82 3.19 4.30 5.27

For SI: 1 inch = 25.4 mm, 1 pound per cubic foot = 16.02 kg/m 3 .

290 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

TABLE 722.5.1(7) MINIMUM COVER (inch) FOR STEEL COLUMNS ENCASED IN

FIRE AND SMOKE PROTECTION FEATURES

TABLE 722.5.1(8) MINIMUM COVER (inch) FOR STEEL COLUMNS ENCASED IN STRUCTURAL LIGHTWEIGHT CONCRETE a

[FIGURE 722.5.1(6)(c)]

STRUCTURAL SHAPE FIRE-RESISTANCE RATING (HOURS)
STRUCTURAL SHAPE 1 11/2 2 3 4
W14 × 233 1 1 1 1 11/2
× 193 × 193 × 193 × 193 11/2 11/2
× 74 × 74 × 74 × 74 × 74 2
× 61 × 61 × 61 × 61 × 61 21/2
× 43 × 43 × 43 11/2 2 2
W12 × 65 1 1 1 11/2 2
× 53 × 53 × 53 × 53 2 21/2
× 40 × 40 × 40 11/2 11/2 11/2
W10 × 112 1 1 1 11/2 2
× 88 × 88 × 88 × 88 × 88 × 88
× 60 × 60 × 60 × 60 2 21/2
× 33 × 33 × 33 11/2 11/2 11/2
W8 × 35 1 1 11/2 2 21/2
× 28 × 28 × 28 × 28 × 28 3
× 24 × 24 × 24 × 24 21/2 21/2
× 18 × 18 11/2 11/2 11/2 11/2

For SI: 1 inch = 25.4 mm. a. The tabulated thicknesses are based on the assumed properties of

structural lightweight concrete given in Table 722.5.1(2).

NORMAL-WEIGHT T CONCRETEa [FIGURE 722.5.1(6)(c)]
STRUCTURAL SHAPE FIRE-RESISTANCE RATING (hours) FIRE-RESISTANCE RATING (hours) FIRE-RESISTANCE RATING (hours) FIRE-RESISTANCE RATING (hours) FIRE-RESISTANCE RATING (hours)
STRUCTURAL SHAPE 1 11/2 2 3 4
W14 × 233 1 1 1 11/2 2
× 176 × 176 × 176 × 176 × 176 21/2
× 132 × 132 × 132 × 132 2 2
× 90 × 90 × 90 11/2 11/2 11/2
× 61 × 61 × 61 × 61 × 61 3
× 48 × 48 11/2 11/2 21/2 21/2
× 43 × 43 × 43 × 43 × 43 × 43
W12 × 152 1 1 1 2 21/2
× 96 × 96 × 96 × 96 × 96 × 96
× 65 × 65 11/2 11/2 11/2 3
× 50 × 50 × 50 × 50 21/2 21/2
× 40 × 40 × 40 × 40 × 40 × 40
W10 × 88 1 11/2 11/2 2 3
× 49 1 1 1 21/2 21/2
× 45 × 45 × 45 × 45 × 45 × 45
× 39 × 39 × 39 × 39 × 39 31/2
× 33 × 33 × 33 2 2 2
W8 × 67 1 1 11/2 21/2 3
× 58 × 58 × 58 × 58 × 58 × 58
× 48 × 48 11/2 11/2 11/2 31/2
× 31 × 31 × 31 2 3 3
× 21 × 21 × 21 × 21 × 21 × 21
× 18 × 18 × 18 × 18 × 18 4
W6 × 25 1 11/2 2 3 31/2
× 20 × 20 2 21/2 21/2 4
× 16 × 16 × 16 × 16 31/2 31/2
× 15 11/2 11/2 11/2 11/2 11/2
× 9 × 9 × 9 × 9 × 9 × 9

For SI: 1 inch = 25.4 mm. a. The tabulated thicknesses are based on the assumed properties of normal weight concrete given in Table 722.5.1(2).

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 722.5.1(9)
MINIMUM COVER (inch) FOR STEEL COLUMNS IN NORMAL-
WEIGHT PRECAST COVERSa [FIGURE 722.5.1(6)(a)]
TABLE 722.5.1(10)
MINIMUM COVER (inch) FOR STEEL COLUMNS IN
STRUCTURAL LIGHTWEIGHT PRECAST COVERSa

STRUCTURAL SHAPE
FIRE-RESISTANCE RATING (hours)
1
11/2
2
3
4
W14 × 233
11/2
11/2
11/2
21/2
3
× 211
31/2
× 176
2
× 145
3
× 109
2
21/2
× 99
4
× 61
31/2
× 43
41/2
W12 × 190
11/2
11/2
11/2
21/2
31/2
× 152
2
× 120
3
4
× 96
× 87
2
21/2
31/2
× 58
41/2
× 40
W10 × 112
11/2
11/2
2
3
31/2
× 88
4
× 77
2
21/2
× 54
31/2
× 33
41/2
W8 × 67
11/2
11/2
2
3
4
× 58
2
21/2
31/2
× 48
× 28
41/2
× 21
21/2
3
× 18
4
W6 × 25
11/2
2
21/2
31/2
41/2
× 20
21/2
3
× 16
4
× 12
2
× 9
5
[FIGURE 722.5.1(6)(a)]
STRUCTURAL SHAPE
FIRE-RESISTANCE RATING (hours)
1
11/2
2
3
4
W14 × 233
11/2
11/2
11/2
2
21/2
× 176
3
× 145
21/2
× 132
× 109
× 99
2
× 68
31/2
× 43
3
W12 × 190
11/2
11/2
11/2
2
21/2
× 152
× 136
3
× 106
21/2
× 96
31/2
× 87
× 65
2
× 40
3
W10 × 112
11/2
11/2
11/2
2
3
× 100
21/2
× 88
× 77
2
31/2
× 60
× 39
3
× 33
2
W8 × 67
11/2
11/2
11/2
21/2
3
× 48
2
3
31/2
× 35
× 28
2
× 18
21/2
4
W6 × 25
11/2
2
2
3
31/2
× 15
21/2
4
× 9
31/2

a. The tabulated thicknesses are based on the assumed properties of normal weight concrete given in Table 722.5.1(2).

For SI: 1 inch = 25.4 mm. a. The tabulated thicknesses are based on the assumed properties of

structural lightweight concrete given in Table 722.5.1(2).

292 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 722.6.2(1) TIME ASSIGNED TO WALLBOARD MEMBRANESa, b, c, d

DESCRIPTION OF FINISH TIMEe(minutes)
3/8-inch wood structural panel bonded with exterior glue 5
15/32-inch wood structural panel bonded with exterior glue 10
19/32-inch wood structural panel bonded with exterior glue 15
3/8-inch gypsum wallboard 10
1/2-inch gypsum wallboard 15
5/8-inch gypsum wallboard 30
1/2-inch Type X gypsum wallboard 25
5/8-inch Type X gypsum wallboard 40
Double3/8-inch gypsum wallboard 25
1/2-inch +3/8-inch gypsum wallboard 35
Double1/2-inch gypsum wallboard 40

For SI: 1 inch = 25.4 mm. a. These values apply only where membranes are installed on framing members that are spaced 16 inches o.c. or less. b. Gypsum wallboard installed over framing or furring shall be installed so that all edges are supported, except 5 /8-inch Type X gypsum wallboard shall be

permitted to be installed horizontally with the horizontal joints staggered 24 inches each side and unsupported but finished. c. On wood frame floor/ceiling or roof/ceiling assemblies, gypsum board shall be installed with the long dimension perpendicular to framing members and shall

have all joints finished. d. The membrane on the unexposed side shall not be included in determining the fire resistance of the assembly. Where dissimilar membranes are used on a wall

assembly, the calculation shall be made from the least fire-resistant (weaker) side. e. The time assigned is not a finished rating.

TABLE 722.6.2(2) TIME ASSIGNED FOR CONTRIBUTION OF WOOD FRAME a, b, c

DESCRIPTION TIME ASSIGNED TO FRAME (minutes)
Wood studs 16 inches o.c. 20
Wood floor and roof joists 16 inches o.c. 10

For SI: 1 inch = 25.4 mm. a. This table does not apply to studs or joists spaced more than 16 inches o.c. b. All studs shall be nominal 2 × 4 and all joists shall have a nominal thickness of not less than 2 inches. c. Allowable spans for joists shall be determined in accordance with Sections 2308.4.2.1, 2308.7.1 and 2308.7.2.

TABLE 722.6.2(3) MEMBRANE a ON EXTERIOR FACE OF WOOD STUD WALLS

SHEATHING PAPER EXTERIOR FINISH
5/8-inch T & G lumber
5/16-inch exterior glue wood structural panel
1/2-inch gypsum wallboard
5/8-inch gypsum wallboard
1/2-inch fiberboard
Sheathing paper Lumber siding
Wood shingles and shakes
1/4-inch fiber-cement lap, panel or shingle siding
1/4-inch wood structural panels-exterior type
1/4-inch hardboard
Metal siding
Stucco on metal lath
Masonry veneer
Vinyl siding
None 3/8-inch exterior-grade wood structural panels

For SI: 1 inch = 25.4 mm. a. Any combination of sheathing, paper and exterior finish is permitted.

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

FIRE AND SMOKE PROTECTION FEATURES

TABLE 722.6.2(4) FLOORING OR ROOFING OVER WOOD FRAMING a

ASSEMBLY STRUCTURAL
MEMBERS
SUBFLOOR OR ROOF DECK FINISHED FLOORING OR ROOFING
Floor Wood 15/32-inch wood structural panels or
11/16-inch T & G softwood
Hardwood or softwood flooring on building paper resilient flooring,
parquet floor felted-synthetic fiber floor coverings, carpeting, or ceramic
tile on1/4-inch-thick fiber-cement underlayment or3/8-inch-thick panel-
type underlay
Ceramic tile on 11/4-inch mortar bed
Roof Wood 15/32-inch wood structural panels or
11/16-inch T & G softwood
Finished roofing material with or without insulation

For SI: 1 inch = 25.4 mm. a. This table applies only to wood joist construction. It is not applicable to wood truss construction.

TABLE 722.6.2(5) TIME ASSIGNED FOR ADDITIONAL PROTECTION

DESCRIPTION OF ADDITIONAL PROTECTION FIRE RESISTANCE (minutes)
Add to the fire-resistance rating of wood stud walls if the spaces between the studs are completely filled with
glass fiber mineral wool batts weighing not less than 2 pounds per cubic foot (0.6 pound per square foot of wall
surface) or rockwool or slag material wool batts weighing not less than 3.3 pounds per cubic foot (1 pound per
square foot of wall surface), or cellulose insulation having a nominal density not less than 2.6 pounds per cubic
foot.
15

For SI: 1 pound/cubic foot = 16.0185 kg/m 3 .

294 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

CALIFORNIA BUILDING CODE – MATRIX ADOPTION TABLE

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Building Code (Title 24, Part 2)
California Building Code (Title 24, Part 2)
  1. Chapter 2 — DEFINITIONS AND ABBREVIATIONS
  2. Appendix G — FLOOD-RESISTANT
  3. Appendix L — EARTHQUAKE RECORDING
  4. Appendix M — TSUNAMI-GENERATED
  5. Chapter 1 — SCOPE AND ADMINISTRATION
  6. Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
  7. Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED
  8. Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
  9. Chapter 6 — TYPES OF CONSTRUCTION
  10. Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
  11. Chapter 7A — MATERIALS AND CONSTRUCTION
  12. Chapter 8 — INTERIOR FINISHES
  13. Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
  14. Chapter 10 — MEANS OF EGRESS
  15. Chapter 11A — HOUSING ACCESSIBILITY
  16. Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
  17. Chapter 12 — INTERIOR ENVIRONMENT
  18. Chapter 14 — EXTERIOR WALLS
  19. Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
  20. Chapter 16 — STRUCTURAL DESIGN
  21. Chapter 16A — STRUCTURAL DESIGN
  22. Chapter 17 — SPECIAL INSPECTIONS AND TESTS
  23. Chapter 18 — SOILS AND FOUNDATIONS
  24. Chapter 19 — CONCRETE
  25. Chapter 20 — ALUMINUM
  26. Chapter 21 — MASONRY
  27. Chapter 22 — STEEL
  28. Chapter 23 — WOOD
  29. Chapter 24 — GLASS AND GLAZING
  30. Chapter 25 — GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER
  31. Chapter 26 — PLASTIC
  32. Chapter 27 — ELECTRICAL
  33. Chapter 28 — MECHANICAL SYSTEMS
  34. Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
  35. Chapter 31 — SPECIAL CONSTRUCTION
  36. Chapter 31B — PUBLIC POOLS
  37. Chapter 31C — RADIATION
  38. Chapter 31D — FOOD ESTABLISHMENTS
  39. Chapter 31F — MARINE OIL TERMINALS
  40. Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
  41. Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
  42. Chapter 35 — REFERENCED STANDARDS
  43. Appendix A — EMPLOYEE QUALIFICATIONS
  44. Appendix B — BOARD OF APPEALS
  45. Appendix C — GROUP U – AGRICULTURAL BUILDINGS
  46. Appendix D — FIRE DISTRICTS
  47. Appendix F — RODENTPROOFING
  48. Appendix H — SIGNS
  49. Appendix I — PATIO COVERS
  50. Appendix J — GRADING
  51. Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES
  52. Appendix N — REPLICABLE BUILDINGS
  53. Appendix O — EMERGENCY HOUSING

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.