Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
Section 506
California Building Code (Title 24, Part 2) · 2019 edition · updated 2026-09-12 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
506.1 General.¶
The floor area of a building shall be determined based on the type of construction, occupancy classification, whether there is an automatic sprinkler system installed throughout the building and the amount of building frontage on public way or open space.
506.1.1 Unlimited area buildings. Unlimited area buildings shall be designed in accordance with Section 507.
506.1.2 Special provisions. The special provisions of Section 510 permit the use of special conditions that are exempt from, or modify, the specific requirements of this chapter regarding the allowable areas of buildings based on the occupancy classification and type of construction, provided the special condition complies with the provisions specified in Section 510.
506.1.3 Basements. Basements need not be included in the total allowable floor area of a building provided the total area of such basements does not exceed the area permitted for a one-story above grade plane building.
506.2 Allowable area determination.¶
The allowable area of a building shall be determined in accordance with the applicable provisions of Sections 506.2.1 through 506.2.4 and Section 506.3.
506.2.1 Single-occupancy, one-story buildings. The allowable area of a single-occupancy building with no
GENERAL BUILDING HEIGHTS AND AREAS
more than one story above grade plane shall be determined in accordance with Equation 5-1:
Aa = At + ( NS × If ) (Equation 5-1)
where: Aa = Allowable area (square feet). At = Tabular allowable area factor (NS, S1, S13R or
S13D value, as applicable) in accordance with Table 506.2.
NS = Tabular allowable area factor in accordance with
Table 506.2 for nonsprinklered building (regardless of whether the building is sprinklered). If = Area factor increase due to frontage (percent) as
calculated in accordance with Section 506.3.
506.2.2 Mixed-occupancy, one-story buildings. The allowable area of a mixed-occupancy building with no more than one story above grade plane shall be determined in accordance with the applicable provisions of Section 508.1 based on Equation 5-1 for each applicable occupancy.
506.2.2.1 Group H-2 or H-3 mixed occupancies. For a building containing Group H-2 or H-3 occupancies, the allowable area shall be determined in accordance with Section 508.4.2, with the sprinkler system increase applicable only to the portions of the building not classified as Group H-2 or H-3.
506.2.3 Single-occupancy, multistory buildings. The allowable area of a single-occupancy building with more than one story above grade plane shall be determined in accordance with Equation 5-2:
Aa = [ At + ( NS × If )] × Sa (Equation 5-2)
where: Aa = Allowable area (square feet). At = Tabular allowable area factor (NS, S13R, S13D or
SM value, as applicable) in accordance with Table 506.2.
NS = Tabular allowable area factor in accordance with
Table 506.2 for a nonsprinklered building (regardless of whether the building is sprinklered). If = Area factor increase due to frontage (percent) as
calculated in accordance with Section 506.3. Sa = For other than Group A, E, H, I, L and R
occupancies, high-rise buildings, and other applications listed in Section 1.11 regulated by the Office of the State Fire Marshal, actual number of building stories above grade plane, not to exceed three. For Group A, E, H, I, L and R occupancies, high-rise buildings, and other applications listed in Section 1.11 regulated by the Office of the State Fire Marshal, actual number of building stories above grade plane, not to exceed two. No individual story shall exceed the allowable area ( Aa ) as determined by Equation 5-2 using the value of Sa = 1.
ove grade plane, not to exceed three. For Group A, E, H, I, L and R occupancies, high-rise buildings, and other applications listed in Section 1.11 regulated by the Office of the State Fire Marshal, actual number of building stories above grade plane, not to exceed two. No individual story shall exceed the allowable area ( Aa ) as determined by Equation 5-2 using the value of Sa = 1.
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
GENERAL BUILDING HEIGHTS AND AREAS
TABLE 506.2 ALLOWABLE AREA FACTOR ( At = NS, S1, S13R, S13D or SM, as applicable) IN SQUARE FEET a, b, j
| OCCUPANCY CLASSIFICATION |
SEE FOOTNOTES | TYPE OF CONSTRUCTION | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| OCCUPANCY CLASSIFICATION |
SEE FOOTNOTES | TYPE I | TYPE I | TYPE II | TYPE II | TYPE III | TYPE III | TYPE IV | TYPE V | TYPE V |
| OCCUPANCY CLASSIFICATION |
SEE FOOTNOTES | A | B | A | B | A | B | HT | A | B |
| A-1 | NS | UL | UL | 15,500 | 8,500 | 14,000 | 8,500 | 15,000 | 11,500 | 5,500 |
| A-1 | S1 | UL | UL | 62,000 | 34,000 | 56,000 | 34,000 | 60,000 | 46,000 | 22,000 |
| A-1 | SM_ (without area increase)_ | UL | UL | 46,500 | 25,500 | 42,000 | 25,500 | 45,000 | 34,500 | 16,500 |
| A-1 | SM (with area increase) | UL | UL | 15,500 | 8,500 | 14,000 | 8,500 | 15,000 | 11,500 | 5,500 |
| A-2 | NS | UL | UL | 15,500 | 9,500 | 14,000 | 9,500 | 15,000 | 11,500 | 6,000 |
| A-2 | S1 | UL | UL | 62,000 | 38,000 | 56,000 | 38,000 | 60,000 | 46,000 | 24,000 |
| A-2 | SM_ (without area increase)_ | UL | UL | 46,500 | 28,500 | 42,000 | 28,500 | 45,000 | 34,500 | 18,000 |
| A-2 | SM (with area increase) | UL | UL | 15,500 | 9,500 | 14,000 | 9,500 | 15,000 | 11,500 | 6,000 |
| A-3 | NS | UL | UL | 15,500 | 9,500 | 14,000 | 9,500 | 15,000 | 11,500 | 6,000 |
| A-3 | S1 | UL | UL | 62,000 | 38,000 | 56,000 | 38,000 | 60,000 | 46,000 | 24,000 |
| A-3 | SM_ (without area increase)_ | UL | UL | 46,500 | 28,500 | 42,000 | 28,500 | 45,000 | 34,500 | 18,000 |
| A-3 | SM (with area increase) | UL | UL | 15,500 | 9,500 | 14,000 | 9,500 | 15,000 | 11,500 | 6,000 |
| A-4 | NS | UL | UL | 15,500 | 9,500 | 14,000 | 9,500 | 15,000 | 11,500 | 6,000 |
| A-4 | S1 | UL | UL | 62,000 | 38,000 | 56,000 | 38,000 | 60,000 | 46,000 | 24,000 |
| A-4 | SM_ (without area increase)_ | UL | UL | 46,500 | 28,500 | 42,000 | 28,500 | 45,000 | 34,500 | 18,000 |
| A-4 | SM (with area increase) | UL | UL | 15,500 | 9,500 | 14,000 | 9,500 | 15,000 | 11,500 | 6,000 |
| A-5 | NS | UL | UL | UL | UL | UL | UL | UL | UL | UL |
| A-5 | S1 | S1 | S1 | S1 | S1 | S1 | S1 | S1 | S1 | S1 |
| A-5 | SM | SM | SM | SM | SM | SM | SM | SM | SM | SM |
| B | NS | UL | UL | 37,500 | 23,000 | 28,500 | 19,000 | 36,000 | 18,000 | 9,000 |
| B | S1 | UL | UL | 150,000 | 92,000 | 114,000 | 76,000 | 144,000 | 72,000 | 36,000 |
| B | SM | UL | UL | 112,500 | 69,000 | 85,500 | 57,000 | 108,000 | 54,000 | 27,000 |
| E | NS | UL | UL | 26,500 | 14,500 | 23,500 | 14,500 | 25,500 | 18,500 | 9,500 |
| E | S1 | UL | UL | 106,000 | 58,000 | 94,000 | 58,000 | 102,000 | 74,000 | 38,000 |
| E | SM_ (without area increase)_ | UL | UL | 79,500 | 43,500 | 70,500 | 43,500 | 76,500 | 55,500 | 28,500 |
| E | SM (with area increase) | UL | UL | 26,500 | 14,500 | 23,500 | 14,500 | 25,500 | 18,500 | 9.500 |
| F-1 | NS | UL | UL | 25,000 | 15,500 | 19,000 | 12,000 | 33,500 | 14,000 | 8,500 |
| F-1 | S1 | UL | UL | 100,000 | 62,000 | 76,000 | 48,000 | 134,000 | 56,000 | 34,000 |
| F-1 | SM | UL | UL | 75,000 | 46,500 | 57,000 | 36,000 | 100,500 | 42,000 | 25,500 |
| F-2 | NS | UL | UL | 37,500 | 23,000 | 28,500 | 18,000 | 50,500 | 21,000 | 13,000 |
| F-2 | S1 | UL | UL | 150,000 | 92,000 | 114,000 | 72,000 | 202,000 | 84,000 | 52,000 |
| F-2 | SM | UL | UL | 112,500 | 69,000 | 85,500 | 54,000 | 151,500 | 63,000 | 39,000 |
| H-1 | NSc | 21,000 | 16,500 | 11,000 | 7,000 | 9,500 | 7,000 | 10,500 | 7,500 | NP |
| H-1 | S1 | S1 | S1 | S1 | S1 | S1 | S1 | S1 | S1 | S1 |
| H-2 | NSc | 21,000 | 16,500 | 11,000 | 7,000 | 9,500 | 7,000 | 10,500 | 7,500 | 3,000 |
| H-2 | S1 | S1 | S1 | S1 | S1 | S1 | S1 | S1 | S1 | S1 |
| H-2 | SM | SM | SM | SM | SM | SM | SM | SM | SM | SM |
| H-3 | NSc | UL | 60,000 | 26,500 | 14,000 | 17,500 | 13,000 | 25,500 | 10,000 | 5,000 |
| H-3 | S1 | S1 | S1 | S1 | S1 | S1 | S1 | S1 | S1 | S1 |
| H-3 | SM | SM | SM | SM | SM | SM | SM | SM | SM | SM |
(continued)
186 2019 CALIFORNIA BUILDING CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
GENERAL BUILDING HEIGHTS AND AREAS
TABLE 506.2—continued
| ALLOWABLE AREA FACTO | OR (At = NS, S1, S13R, S13D or SM, as applicable) IN SQUARE FEETa, b, j | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| OCCUPANCY CLASSIFICATION |
SEE FOOTNOTES | TYPE OF CONSTRUCTION | TYPE OF CONSTRUCTION | TYPE OF CONSTRUCTION | TYPE OF CONSTRUCTION | TYPE OF CONSTRUCTION | TYPE OF CONSTRUCTION | TYPE OF CONSTRUCTION | TYPE OF CONSTRUCTION | TYPE OF CONSTRUCTION |
| OCCUPANCY CLASSIFICATION |
SEE FOOTNOTES | TYPE I | TYPE I | TYPE II | TYPE II | TYPE III | TYPE III | TYPE IV | TYPE V | TYPE V |
| OCCUPANCY CLASSIFICATION |
SEE FOOTNOTES | A | B | A | B | A | B | HT | A | B |
| H-4 | NSc, d | UL | UL | 37,500 | 17,500 | 28,500 | 17,500 | 36,000 | 18,000 | 6,500 |
| H-4 | S1 | UL | UL | 150,000 | 70,000 | 114,000 | 70,000 | 144,000 | 72,000 | 26,000 |
| H-4 | SM_ (without area increase)_ | UL | UL | 112,500 | 52,500 | 85,500 | 52,500 | 108,000 | 54,000 | 19,500 |
| H-4 | SM (with area increase) | UL | UL | 37,500 | 17,500 | 28,500 | 17,500 | 36,000 | 18,000 | 6,500 |
| H-5 | NSc, d | UL | UL | 37,500 | 23,000 | 28,500 | 19,000 | 36,000 | 18,000 | 9,000 |
| H-5 | S1 | UL | UL | 150,000 | 92,000 | 114,000 | 76,000 | 144,000 | 72,000 | 36,000 |
| H-5 | SM_ (without area increase)_ | UL | UL | 112,500 | 69,000 | 85,500 | 57,000 | 108000 | 54,000 | 27,000 |
| H-5 | SM (with area increase) | UL | UL | 37,500 | 23,000 | 28,500 | 19,000 | 36,000 | 18,000 | 9,000 |
| I-2_, I-2.1_ | NSd, f | UL | UL | 15,000 | 11,000 | 12,000 | NP | 12,000 | 9,500 | NP |
| I-2_, I-2.1_ | S1 | UL | UL | 60,000 | 44,000 | 48,000 | NP | 48,000 | 38,000 | NP |
| I-2_, I-2.1_ | SM_ (without area increase)_ | UL | UL | 45,000 | 33,000 | 36,000 | NP | 36,000 | 28,500 | NP |
| I-2_, I-2.1_ | SM (with area increase) | UL | UL | 15,000 | 11,000 | 12,000 | NP | 12,000 | 9,500 | NP |
| I-3 | NSd, e | UL | 15,100 | NP | NP | NP | NP | NP | NP | NP |
| I-3 | S1 | UL | 45,300 | NP | NP | NP | NP | NP | NP | NP |
| I-3 | SM_ (without area increase)_ | UL | 30,200 | NP | NP | NP | NP | NP | NP | NP |
| I-3 | SM (with area increase) | UL | 15,100 | NP | NP | NP | NP | NP | NP | NP |
| I-4 | NSd, g | UL | 60,500 | 26,500 | 13,000 | 23,500 | 13,000 | 25,500 | 18,500 | 9,000 |
| I-4 | S1 | UL | 121,000 | 106,000 | 52,000 | 94,000 | 52,000 | 102,000 | 74,000 | 36,000 |
| I-4 | SM_ (without area increase)_ | UL | 181,500 | 79,500 | 39,000 | 70,500 | 39,000 | 76,500 | 55,500 | 27,000 |
| I-4 | SM (with area increase) | UL | 60,500 | 26,500 | 13,000 | 23,500 | 13,000 | 25,500 | 18,500 | 9,000 |
| L | NS | UL | 60,000 | 37,500 | 17,500 | 28,500 | 17,500 | 36,000 | 18,000 | 6,500 |
| L | S1 | S1 | S1 | S1 | S1 | S1 | S1 | S1 | S1 | S1 |
| L | SM | SM | SM | SM | SM | SM | SM | SM | SM | SM |
| M | NS | UL | UL | 21,500 | 12,500 | 18,500 | 12,500 | 20,500 | 14,000 | 9,000 |
| M | S1 | UL | UL | 86,000 | 50,000 | 74,000 | 50,000 | 82,000 | 56,000 | 36,000 |
| M | SM | UL | UL | 64,500 | 37,500 | 55,500 | 37,500 | 61,500 | 42,000 | 27,000 |
| R-1h | NSd | UL | UL | 24,000 | 16,000 | 24,000 | 16,000 | 20,500 | 12,000 | 7,000 |
| R-1h | S13R | S13R | S13R | S13R | S13R | S13R | S13R | S13R | S13R | S13R |
| R-1h | S1 | UL | UL | 96,000 | 64,000 | 96,000 | 64,000 | 82,000 | 48,000 | 28,000 |
| R-1h | SM_ (without area increase)_ | UL | UL | 72,000 | 48,000 | 72,000 | 48,000 | 61,500 | 36,000 | 21,000 |
| R-1h | SM (with area increase) | UL | UL | 24,000 | 16,000 | 24,000 | 16,000 | 20,500 | 12,000 | 7,000 |
| R-2h | NSd | UL | UL | 24,000 | 16,000 | 24,000 | 16,000 | 20,500 | 12,000 | 7,000 |
| R-2h | S13R | S13R | S13R | S13R | S13R | S13R | S13R | S13R | S13R | S13R |
| R-2h | S1 | UL | UL | 96,000 | 64,000 | 96,000 | 64,000 | 82,000 | 48,000 | 28,000 |
| R-2h | SM_ (without area increase)_ | UL | UL | 72,000 | 48,000 | 72,000 | 48,000 | 61,500 | 36,000 | 21,000 |
| R-2h | SM (with area increase) | UL | UL | 24,000 | 16,000 | 24,000 | 16,000 | 20,500 | 12,000 | 7,000 |
| R-2 Type VA constructionk |
NSd | NP | NP | NP | NP | NP | NP | NP | 12,000 | NP |
| R-2 Type VA constructionk |
S13R | NP | NP | NP | NP | NP | NP | NP | 12,000 | NP |
| R-2 Type VA constructionk |
S1 | NP | NP | NP | NP | NP | NP | NP | 48,000 | NP |
| R-2 Type VA constructionk |
SM (without height increase) | NP | NP | NP | NP | NP | NP | NP | 36,000 | NP |
| R-2 Type VA constructionk |
SM (with height increase) | NP | NP | NP | NP | NP | NP | NP | 36,000 j | NP |
(continued)
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
GENERAL BUILDING HEIGHTS AND AREAS
TABLE 506.2—continued ALLOWABLE AREA FACTOR ( At = NS, S1, S13R, S13D or SM, as applicable) IN SQUARE FEET a, b, j
| OCCUPANCY CLASSIFICATION |
SEE FOOTNOTES | TYPE OF CONSTRUCTION | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| OCCUPANCY CLASSIFICATION |
SEE FOOTNOTES | TYPE I | TYPE I | TYPE II | TYPE II | TYPE III | TYPE III | TYPE IV | TYPE V | TYPE V |
| OCCUPANCY CLASSIFICATION |
SEE FOOTNOTES | A | B | A | B | A | B | HT | A | B |
| R-2.1h | NSd | UL | 55,000 | 19,000 | NP | 16,500 | NP | NP | 10,500 | NP |
| R-2.1h | S13R | UL | 55,000 | 19,000 | NP | 16,500 | NP | NP | 10,500 | NP |
| R-2.1h | S1 | UL | 220,000 | 76,000 | NP | 66,000 | NP | 72,000 | 42,000 | NP |
| R-2.1h | SM (without height increase) | UL | 165,000 | 57,000 | NP | 49,500 | NP | 54,000 | 31,500 | NP |
| R-2.1h | SM (with height increase) | UL | 55,000 | 19,000 | NP | 16,500 | NP | NP | 10,500 | NP |
| R-2.2h | S1 | UL | UL | 96,000 | 64,000 | 96,000 | 64,000 | 82,000 | 48,000 | 28,000 |
| R-2.2h | SM (without height increase) | UL | UL | 72,000 | 48,000 | 72,000 | 48,000 | 61,500 | 36,000 | 21,000 |
| R-2.2h | SM (with height increase) | UL | UL | 24,000 | 16,000 | 24,000 | 16,000 | 20,500 | 12,000 | 7,000 |
| R-3_, R-3.1h_ | NSd | UL | UL | UL | UL | UL | UL | UL | UL | UL |
| R-3_, R-3.1h_ | S13D | S13D | S13D | S13D | S13D | S13D | S13D | S13D | S13D | S13D |
| R-3_, R-3.1h_ | S13R | S13R | S13R | S13R | S13R | S13R | S13R | S13R | S13R | S13R |
| R-3_, R-3.1h_ | S1 | S1 | S1 | S1 | S1 | S1 | S1 | S1 | S1 | S1 |
| R-3_, R-3.1h_ | SM | SM | SM | SM | SM | SM | SM | SM | SM | SM |
| R-4h | NSd | UL | UL | 24,000 | 16,000 | 24,000 | 16,000 | 20,500 | 12,000 | 7,000 |
| R-4h | S13D | S13D | S13D | S13D | S13D | S13D | S13D | S13D | S13D | S13D |
| R-4h | S13R | S13R | S13R | S13R | S13R | S13R | S13R | S13R | S13R | S13R |
| R-4h | S1 | UL | UL | 96,000 | 64,000 | 96,000 | 64,000 | 82,000 | 48,000 | 28,000 |
| R-4h | SM_ (without height increase)_ | UL | UL | 72,000 | 48,000 | 72,000 | 48,000 | 61,500 | 36,000 | 21,000 |
| R-4h | SM (with height increase) | UL | UL | 24,000 | 16,000 | 24,000 | 16,000 | 20,500 | 12,000 | 7,000 |
| S-1 | NS | UL | 48,000 | 26,000 | 17,500 | 26,000 | 17,500 | 25,500 | 14,000 | 9,000 |
| S-1 | S1 | UL | 192,000 | 104,000 | 70,000 | 104,000 | 70,000 | 102,000 | 56,000 | 36,000 |
| S-1 | SM | UL | 144,000 | 78,000 | 52,500 | 78,000 | 52,500 | 76,500 | 42,000 | 27,000 |
| S-2 | NS | UL | 79,000 | 39,000 | 26,000 | 39,000 | 26,000 | 38,500 | 21,000 | 13,500 |
| S-2 | S1 | UL | 316,000 | 156,000 | 104,000 | 156,000 | 104,000 | 154,000 | 84,000 | 54,000 |
| S-2 | SM | UL | 237,000 | 117,000 | 78,000 | 117,000 | 78,000 | 115,500 | 63,000 | 40,500 |
| U | NSi | UL | 35,500 | 19,000 | 8,500 | 14,000 | 8,500 | 18,000 | 9,000 | 5,500 |
| U | S1 | UL | 142,000 | 76,000 | 34,000 | 56,000 | 34,000 | 72,000 | 36,000 | 22,000 |
| U | SM | UL | 106,500 | 57,000 | 25,500 | 42,000 | 25,500 | 54,000 | 27,000 | 16,500 |
For SI: 1 square foot = 0.0929 m 2 .
UL = Unlimited; NP = Not Permitted; NS = Buildings not equipped throughout with an automatic sprinkler system; S1 = Buildings a maximum of one story above grade plane equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; SM = Buildings two or more stories above grade plane equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; S13R = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2; S13D = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.3. a. See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter. b. See Section 903.2 for the minimum thresholds for protection by an automatic sprinkler system for specific occupancies. c. New Group H and all Group L occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.5. d. The NS value is only for use in evaluation of existing building area in accordance with the California Existing Building Code . e. New Group I-1 and I-3 occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.6. For new Group I-1
occupancies, Condition 1, see Exception 1 of Section 903.2.6. f. New and existing Group I-2 occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.6 and Section 1103.5
of the California Fire Code . g. New Group I-4 occupancies see Exceptions 2 and 3 of Section 903.2.6. h. New Group R occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.8. i. The maximum allowable area for a single-story nonsprinklered Group U greenhouse is permitted to be 9,000 square feet, or the allowable area shall be
permitted to comply with Table C102.1 of Appendix C. j. In other than Group A, E, H, I, L, and R occupancies, high-rise buildings, and other applications listed in Section 1.11 regulated by the Office of the State Fire
Marshal, the S increases for height and stories in Tables 504.3 and 504.4 are permitted in addition to the S area increase in accordance with Table 506.2. k. For Group R-2 buildings of Type VA construction equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1,
S area increase is permitted in addition to the height and story increase provided the height shall not exceed 60 feet and 4 stories.
188 2019 CALIFORNIA BUILDING CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
GENERAL BUILDING HEIGHTS AND AREAS
less of the actual width of the public way or open space. Where the value of W varies along the perimeter of the building, the calculation performed in accordance with Equation 5-5 shall be based on the weighted average calculated in accordance with Equation 5-4.
W = ( L1 × w1 + L2 × w2 + L3 × w3 …)/ F (Equation 5-4)
where:
W (Width: weighted average) = Calculated width of public way or open space (feet). Ln = Length of a portion of the exterior perimeter wall. wn = Width ( 20 feet) of a public way or open space
associated with that portion of the exterior perimeter wall.
F = Building perimeter that fronts on a public way or
open space having a width of 20 feet (6096 mm) or more.
Exception: Where a building meets the requirements of Section 507, as applicable, except for compliance with the minimum 60-foot (18 288 mm) public way or yard requirement, and the value of W is greater than 30 feet (9144 mm), the value of W shall not exceed 60 feet (18 288 mm).
506.3.3 Amount of increase. The area factor increase based on frontage shall be determined in accordance with Equation 5-5:
If = [ F/P - 0.25] W /30 (Equation 5-5)
where: If = Area factor increase due to frontage. F = Building perimeter that fronts on a public way or
open space having minimum distance of 20 feet (6096 mm).
P = Perimeter of entire building (feet).
W = Width of public way or open space (feet) in
accordance with Section 506.3.2.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Building Code (Title 24, Part 2)
- Chapter 2 — DEFINITIONS AND ABBREVIATIONS
- Appendix G — FLOOD-RESISTANT
- Appendix L — EARTHQUAKE RECORDING
- Appendix M — TSUNAMI-GENERATED
- Chapter 1 — SCOPE AND ADMINISTRATION
- Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
- Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED
▸Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
- Chapter 6 — TYPES OF CONSTRUCTION
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 7A — MATERIALS AND CONSTRUCTION
- Chapter 8 — INTERIOR FINISHES
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
- Chapter 11A — HOUSING ACCESSIBILITY
- Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
- Chapter 12 — INTERIOR ENVIRONMENT
- Chapter 14 — EXTERIOR WALLS
- Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
- Chapter 16 — STRUCTURAL DESIGN
- Chapter 16A — STRUCTURAL DESIGN
- Chapter 17 — SPECIAL INSPECTIONS AND TESTS
- Chapter 18 — SOILS AND FOUNDATIONS
- Chapter 19 — CONCRETE
- Chapter 20 — ALUMINUM
- Chapter 21 — MASONRY
- Chapter 22 — STEEL
- Chapter 23 — WOOD
- Chapter 24 — GLASS AND GLAZING
- Chapter 25 — GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER
- Chapter 26 — PLASTIC
- Chapter 27 — ELECTRICAL
- Chapter 28 — MECHANICAL SYSTEMS
- Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
- Chapter 31 — SPECIAL CONSTRUCTION
- Chapter 31B — PUBLIC POOLS
- Chapter 31C — RADIATION
- Chapter 31D — FOOD ESTABLISHMENTS
- Chapter 31F — MARINE OIL TERMINALS
- Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
- Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
- Chapter 35 — REFERENCED STANDARDS
- Appendix A — EMPLOYEE QUALIFICATIONS
- Appendix B — BOARD OF APPEALS
- Appendix C — GROUP U – AGRICULTURAL BUILDINGS
- Appendix D — FIRE DISTRICTS
- Appendix F — RODENTPROOFING
- Appendix H — SIGNS
- Appendix I — PATIO COVERS
- Appendix J — GRADING
- Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES
- Appendix N — REPLICABLE BUILDINGS
- Appendix O — EMERGENCY HOUSING