Section 2604
California Building Code (Title 24, Part 2) · 2019 edition · updated 2026-09-12 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
2604.1 General.¶
Plastic materials installed as interior finish or trim shall comply with Chapter 8. Foam plastics shall only be installed as interior finish where approved in accordance with the special provisions of Section 2603.9. Foam plastics that are used as interior finish shall meet the flame spread and smoke-developed index requirements for interior finish in accordance with Chapter 8. Foam plastics installed as interior trim shall comply with Section 2604.2.
2604.1.1 Plenums. Foam plastics installed in plenums as interior wall or ceiling finish shall comply with Section 2603.7. Foam plastics installed in plenums as interior trim shall comply with Sections 2604.2 and 2603.7.
[F] 2604.2 Interior trim. Foam plastic used as interior trim shall comply with Sections 2604.2.1 through 2604.2.4.
[F] 2604.2.1 Density. The minimum density of the interior trim shall be 20 pcf (320 kg/m 3 ).
TABLE 2603.13.2 FURRING MINIMUM FASTENING REQUIREMENTS FOR APPLICATION OVER FOAM PLASTIC SHEATHING TO SUPPORT CLADDING WEIGHT a, b
| FURRING MATERIAL | FRAMING MEMBER | FASTENER TYPE AND MINIMUM SIZE | MINIMUM PENETRATION INTO WALL FRAMING (INCHES) | FASTENER SPACING IN FURRING (INCHES) | MAXIMUM THICKNESS OF FOAM SHEATHINGd (INCHES) | |||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| FURRING MATERIAL | FRAMING MEMBER | FASTENER TYPE AND MINIMUM SIZE |
MINIMUM PENETRATION INTO WALL FRAMING (INCHES) |
FASTENER SPACING IN FURRING (INCHES) |
16″** o.c. furringe** | 16″** o.c. furringe** | 16″** o.c. furringe** | 16″** o.c. furringe** | 24″** o.c. furringe** | 24″** o.c. furringe** | 24″** o.c. furringe** | 24″** o.c. furringe** |
| FURRING MATERIAL | FRAMING MEMBER | FASTENER TYPE AND MINIMUM SIZE |
MINIMUM PENETRATION INTO WALL FRAMING (INCHES) |
FASTENER SPACING IN FURRING (INCHES) |
Siding weight: | Siding weight: | Siding weight: | Siding weight: | Siding weight: | Siding weight: | Siding weight: | Siding weight: |
| FURRING MATERIAL | FRAMING MEMBER | FASTENER TYPE AND MINIMUM SIZE |
MINIMUM PENETRATION INTO WALL FRAMING (INCHES) |
FASTENER SPACING IN FURRING (INCHES) |
3 psf | 11 psf | 18 psf | 25 psf | 3 psf | 11 psf | 18 psf | 25 psf |
| Minimum 1x Wood Furringc |
Minimum 2x Wood Stud |
0.131" diameter nail |
11/4 | 8 | 4.00 | 2.45 | 1.45 | 0.95 | 4.00 | 1.60 | 0.85 | DR |
| Minimum 1x Wood Furringc |
Minimum 2x Wood Stud |
0.131" diameter nail |
11/4 | 12 | 4.00 | 1.60 | 0.85 | DR | 4.00 | 0.95 | DR | DR |
| Minimum 1x Wood Furringc |
Minimum 2x Wood Stud |
0.131" diameter nail |
11/4 | 16 | 4.00 | 1.10 | DR | DR | 3.05 | 0.60 | DR | DR |
| Minimum 1x Wood Furringc |
Minimum 2x Wood Stud |
0.162" diameter nail |
11/4 | 8 | 4.00 | 4.00 | 2.45 | 1.60 | 4.00 | 2.75 | 1.45 | 0.85 |
| Minimum 1x Wood Furringc |
Minimum 2x Wood Stud |
0.162" diameter nail |
11/4 | 12 | 4.00 | 2.75 | 1.45 | 0.85 | 4.00 | 1.65 | 0.75 | DR |
| Minimum 1x Wood Furringc |
Minimum 2x Wood Stud |
0.162" diameter nail |
11/4 | 16 | 4.00 | 1.90 | 0.95 | DR | 4.00 | 1.05 | DR | DR |
| Minimum 1x Wood Furringc |
Minimum 2x Wood Stud |
No. 10 wood screw |
1 | 12 | 4.00 | 2.30 | 1.20 | 0.70 | 4.00 | 1.40 | 0.60 | DR |
| Minimum 1x Wood Furringc |
Minimum 2x Wood Stud |
No. 10 wood screw |
1 | 16 | 4.00 | 1.65 | 0.75 | DR | 4.00 | 0.90 | DR | DR |
| Minimum 1x Wood Furringc |
Minimum 2x Wood Stud |
No. 10 wood screw |
1 | 24 | 4.00 | 0.90 | DR | DR | 2.85 | DR | DR | DR |
| Minimum 1x Wood Furringc |
Minimum 2x Wood Stud |
1/4" lag screw |
11/2 | 12 | 4.00 | 2.65 | 1.50 | 0.90 | 4.00 | 1.65 | 0.80 | DR |
| Minimum 1x Wood Furringc |
Minimum 2x Wood Stud |
1/4" lag screw |
11/2 | 16 | 4.00 | 1.95 | 0.95 | 0.50 | 4.00 | 1.10 | DR | DR |
| Minimum 1x Wood Furringc |
Minimum 2x Wood Stud |
1/4" lag screw |
11/2 | 24 | 4.00 | 1.10 | DR | DR | 3.25 | 0.50 | DR | DR |
For SI: 1 inch = 25.4 mm, 1 pound per square foot (psf) = 0.0479 kPa, 1 pound per square inch = 0.00689 MPa.
DR = Design Required, o.c. = on center. a. Wood framing and furring shall be spruce-pine-fir or any wood species with a specific gravity of 0.42 or greater in accordance with ANSI/AWC NDS. b. Nail fasteners shall comply with ASTM F1667, except nail length shall be permitted to exceed ASTM F1667 standard lengths. c. Where the required cladding fastener penetration into wood material exceeds 3 /4 inch and is not more than 1 1 /2 inches, a minimum 2-inch nominal wood furring
or an approved design shall be used. d. Foam sheathing shall have a minimum compressive strength of 15 psi in accordance with ASTM C578 or ASTM C1289. e. Furring shall be spaced not greater than 24 inches on center in a vertical or horizontal orientation. In a vertical orientation, furring shall be located over wall
studs and attached with the required fastener spacing. In a horizontal orientation, the indicated 8-inch and 12-inch fastener spacing in furring shall be achieved by use of two fasteners into studs at 16 inches and 24 inches on center, respectively.
412 2019 CALIFORNIA BUILDING CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
[F] 2604.2.2 Thickness. The maximum thickness of the interior trim shall be 1 /2 inch (12.7 mm) and the maximum width shall be 8 inches (204 mm).
[F] 2604.2.3 Area limitation. The interior trim shall not constitute more than 10 percent of the specific wall or ceiling areas to which it is attached.
[F] 2604.2.4 Flame spread. The flame spread index shall not exceed 75 where tested in accordance with ASTM E84 or UL 723. The smoke-developed index shall not be limited.
Exception: Where the interior trim material has been tested as an interior finish in accordance with NFPA 286 and complies with the acceptance criteria in Section 803.1.1.1, it shall not be required to be tested for flame spread index in accordance with ASTM E84 or UL 723.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Building Code (Title 24, Part 2)
- Chapter 2 — DEFINITIONS AND ABBREVIATIONS
- Appendix G — FLOOD-RESISTANT
- Appendix L — EARTHQUAKE RECORDING
- Appendix M — TSUNAMI-GENERATED
- Chapter 1 — SCOPE AND ADMINISTRATION
- Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
- Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED
- Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
- Chapter 6 — TYPES OF CONSTRUCTION
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 7A — MATERIALS AND CONSTRUCTION
- Chapter 8 — INTERIOR FINISHES
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
- Chapter 11A — HOUSING ACCESSIBILITY
- Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
- Chapter 12 — INTERIOR ENVIRONMENT
- Chapter 14 — EXTERIOR WALLS
- Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
- Chapter 16 — STRUCTURAL DESIGN
- Chapter 16A — STRUCTURAL DESIGN
- Chapter 17 — SPECIAL INSPECTIONS AND TESTS
- Chapter 18 — SOILS AND FOUNDATIONS
- Chapter 19 — CONCRETE
- Chapter 20 — ALUMINUM
- Chapter 21 — MASONRY
- Chapter 22 — STEEL
- Chapter 23 — WOOD
- Chapter 24 — GLASS AND GLAZING
- Chapter 25 — GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER
- Chapter 27 — ELECTRICAL
- Chapter 28 — MECHANICAL SYSTEMS
- Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
- Chapter 31 — SPECIAL CONSTRUCTION
- Chapter 31B — PUBLIC POOLS
- Chapter 31C — RADIATION
- Chapter 31D — FOOD ESTABLISHMENTS
- Chapter 31F — MARINE OIL TERMINALS
- Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
- Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
- Chapter 35 — REFERENCED STANDARDS
- Appendix A — EMPLOYEE QUALIFICATIONS
- Appendix B — BOARD OF APPEALS
- Appendix C — GROUP U – AGRICULTURAL BUILDINGS
- Appendix D — FIRE DISTRICTS
- Appendix F — RODENTPROOFING
- Appendix H — SIGNS
- Appendix I — PATIO COVERS
- Appendix J — GRADING
- Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES
- Appendix N — REPLICABLE BUILDINGS
- Appendix O — EMERGENCY HOUSING