STRUCTURAL SEALANT GLAZING (SSG)

2410.1 General.

The requirements of this section address the use of structural sealant glazing (SSG). These requirements shall not be used for butt joint glazing, point supported glass and glass fins.

Design, construction, testing, and inspection shall satisfy the requirements of this code except as modified in Sections 2410.1.1 through 2410.1.4.

Exception: [OSHPD 2] Single-story Type V skilled nurs- ing or intermediate care facilities utilizing wood-frame or light-steel-frame construction.

2410.1.1 Design. Design of SSG shall satisfy the following requirements:

1. SSG shall be weather tight and serviceable, as defined in AAMA 501.4, under design story drifts associated with the design earthquake and no glass fallout shall occur at the drifts determined by ASCE 7, Section 13.5.9.

2. The sealant utilized in the insulated glass units used in SSG shall be designed in accordance with ASTM C1249. The insulated glass unit design shall be in accordance with ASTM C1249, Section 6.7.2.

388 2019 CALIFORNIA BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

GLASS AND GLAZING

i. Quality assurance and inspection requirements

shall include formalized post-installation tests using the point load testing procedure in accordance with ASTM C1392. The point load tests shall be done after the initial installation.

j. Where the SSG is field assembled, hand pull tab

tests in accordance with ASTM C1401, Section X2.1, one test every 100 linear feet, but not less than one test for each building elevation view shall be required.

Existing AAMA 501.4 and 501.6 test results satisfying the requirements of this section shall be permitted, in lieu of project specific tests, when approved by the building official.

2410.1.3 Monitoring. Short- and long-term periodic per- formance monitoring shall be provided in accordance with ASTM C1401, C1392 and C1394. Inspection frequencies recommended in ASTM C1392 Section 5.1 shall be fol- lowed.

2410.1.4 Construction documents. Complete design of the SSG system for gravity, wind and seismic forces shall be subject to review by the enforcement agency. Construction documents shall show structural details of glass and cur- tain wall system including:

1. A design narrative explaining how the SSG is sup-

ported by the building and the mechanism used to accommodate seismic racking.

2. Type of SSG and whether field or shop built.

3. The means of supporting the glass during struc-

tural sealant curing time.

4. Typical curtain wall panel elevation, plan view

and sections.

5. Details of building corner joint to verify how the

corner vertical mullion will move to accommodate the seismic drift.

6. Joints between panel and floors at top and bottom.

7. Joints between panels, including vertical and hori-

zontal stack joints at intermediate and edge mul- lion.

8. Member sizes for curtain wall panels.

9. Glass pane sizes, thickness and type of glass.

10. Contact width and thickness of structural sealant and sealant materials for shop and field installa- tion/reglazing.

11. Glass to aluminum joints (including primers, if any).

12. Maximum roof/floor dead and live load deflection of the roof/floor framing members supporting the exterior curtain wall system.

13. Required seismic separation or gap distance between the SSG curtain wall and other adjacent cladding units.

3. Allowable stress for SSG shall not exceed 20 psi and shall have a minimum factor of safety of 5 as required by ASTM C1401.

4. Design methodology shall address seismic movement in accordance with ASTM C1401, Section 30.3.4.

5. SSG systems shall be supported for self-weight and lateral loading at each floor level of the building.

6. Unitized SSG framing shall be anchored to the building floor bearing plate by screws or bolts and shall not rely upon gravity or frictional forces for attachment.

7. Framing shall satisfy the out-of-plane deflection requirements of this code.

2410.1.2 Testing and inspection. Testing and inspection of SSG shall satisfy the following requirements:

a. The seismic drift capability of SSG shall be deter-

mined by tests in accordance with AAMA 501.6, AAMA 501.4 and ASCE 7, Section 13.5.9.2.

b. The applicability of the specific AAMA 501.6 and

AAMA 501.4 testing shall be subject to approval by the building official.

c. The panel test specimens used in the AAMA 501.6

and AAMA 501.4 testing shall include all glass types (annealed, heat strengthened, laminated, tempered) and insulated glass units that comprise more than 5 percent of the total glass curtain wall area used in the building.

d. AAMA 501.4 test specimen shall include the same

materials, sections, connections, and attachment details to the test apparatus as used in the building.

e. Serviceability tests of SSG test specimen shall be

performed in accordance with AAMA 501.4 after seismic displacement tests to the design story drift.

f. The window wall system using structural sealant by

different manufacturer/product category shall be qualified in accordance with AAMA 501.6 and AAMA 501.4 testing for the seismic drift required. Analysis as an alternative to testing is not accept- able for the purposes of satisfying the seismic drift requirements of the SSG system.

g. Where unitized SSG is used with horizontal stack

joints at each floor level and split vertical mullions that can move independently, only a story height sin- gle unit need to be tested under AAMA 501.6. Where continuous horizontal bands of SSG are used in the building, either two or four sided, the aspect ratio (height-to-length) of the test specimen shall be less than 1.0, contain not less than two interior vertical joints and all joints (vertical in the case of two sided), including the perimeter of the glass, shall be glazed with SSG.

h. Where SSG continues around corners, the AAMA

501.4 test specimen shall include one corner panel to verify the kinematics of the corner condition under seismic drift.

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

GLASS AND GLAZING

14. Mitigation of galvanic reactions between the roof/ floor slab anchors, steel screw connections of alu- minum sections and the aluminum anchorage components, if any.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Building Code (Title 24, Part 2)
California Building Code (Title 24, Part 2)
  1. Chapter 2 — DEFINITIONS AND ABBREVIATIONS
  2. Appendix G — FLOOD-RESISTANT
  3. Appendix L — EARTHQUAKE RECORDING
  4. Appendix M — TSUNAMI-GENERATED
  5. Chapter 1 — SCOPE AND ADMINISTRATION
  6. Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
  7. Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED
  8. Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
  9. Chapter 6 — TYPES OF CONSTRUCTION
  10. Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
  11. Chapter 7A — MATERIALS AND CONSTRUCTION
  12. Chapter 8 — INTERIOR FINISHES
  13. Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
  14. Chapter 10 — MEANS OF EGRESS
  15. Chapter 11A — HOUSING ACCESSIBILITY
  16. Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
  17. Chapter 12 — INTERIOR ENVIRONMENT
  18. Chapter 14 — EXTERIOR WALLS
  19. Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
  20. Chapter 16 — STRUCTURAL DESIGN
  21. Chapter 16A — STRUCTURAL DESIGN
  22. Chapter 17 — SPECIAL INSPECTIONS AND TESTS
  23. Chapter 18 — SOILS AND FOUNDATIONS
  24. Chapter 19 — CONCRETE
  25. Chapter 20 — ALUMINUM
  26. Chapter 21 — MASONRY
  27. Chapter 22 — STEEL
  28. Chapter 23 — WOOD
  29. Chapter 24 — GLASS AND GLAZING
  30. Chapter 25 — GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER
  31. Chapter 26 — PLASTIC
  32. Chapter 27 — ELECTRICAL
  33. Chapter 28 — MECHANICAL SYSTEMS
  34. Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
  35. Chapter 31 — SPECIAL CONSTRUCTION
  36. Chapter 31B — PUBLIC POOLS
  37. Chapter 31C — RADIATION
  38. Chapter 31D — FOOD ESTABLISHMENTS
  39. Chapter 31F — MARINE OIL TERMINALS
  40. Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
  41. Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
  42. Chapter 35 — REFERENCED STANDARDS
  43. Appendix A — EMPLOYEE QUALIFICATIONS
  44. Appendix B — BOARD OF APPEALS
  45. Appendix C — GROUP U – AGRICULTURAL BUILDINGS
  46. Appendix D — FIRE DISTRICTS
  47. Appendix F — RODENTPROOFING
  48. Appendix H — SIGNS
  49. Appendix I — PATIO COVERS
  50. Appendix J — GRADING
  51. Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES
  52. Appendix N — REPLICABLE BUILDINGS
  53. Appendix O — EMERGENCY HOUSING

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.