Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
3302 Owner’s Responsibility for Fire Protection — 2025 California Building Code
California Building Code (Title 24, Part 2) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Building Code (Title 24, Part 2) § 3302 · Effective January 1, 2026 · Official source: Building Standards Commission
3302.1 Site safety plan.¶
The owner or owner’s authorized agent shall be responsible for the development, implementation and maintenance of an approved, written site safety plan establishing a fire prevention program at the project site applicable throughout all phases of the construction, repair, alteration or demolition work. The plan shall be submitted and approved before a building permit is issued. Any changes to the plan shall address the requirements of this chapter and other applicable portions of the Califor- nia Fire Code, the duties of staff and staff training requirements. The plan shall be submitted for approval in accordance with the California Fire Code .
3302.1.1 Components of site safety plans. Site safety plans shall include the following, as applicable:
Name and contact information of site safety director.
Documentation of the training of the site safety director and fire watch personnel.
Procedures for reporting emergencies.
Fire department vehicle access routes.
Location of fire protection equipment, including portable fire extinguishers, standpipes, fire department connections and fire hydrants.
Smoking and cooking policies, designated areas to be used where approved, and signage locations in accordance with the California Fire Code.
Location and safety considerations for temporary heating equipment.
Hot-work permit plan.
Plans for control of combustible waste material.
Locations and methods for storage and use of flammable and combustible liquids and other hazardous materials.
Provisions for site security and, where required, for a fire watch.
Changes that affect this plan.
Other site-specific information required by the California Fire Code .
SAFEGUARDS DURING CONSTRUCTION
3302.2 Site safety director.¶
The owner shall designate a person to be the site safety director. The site safety director shall be responsible for ensuring compliance with the site safety plan. The site safety director shall have the authority to enforce the provisions of this chapter and other provisions as necessary to secure the intent of this chapter. Where guard service is provided in accordance with the California Fire Code, the site safety director shall be responsible for the guard service.
3302.3 Daily fire safety inspection.¶
The site safety director shall be responsible for the completion of a daily fire safety inspection at the project site. Each day, all building and outdoor areas shall be inspected to ensure compliance with the inspection list in this section. The results of each inspection shall be documented and maintained on-site until a certificate of occupancy has been issued. Documentation shall be immediately available for on-site inspection and review.
Any contractors entering the site to perform hot work each day have been instructed in the hot work safety requirements in the California Fire Code, and hot work is performed only in areas approved by the site safety director.
Temporary heating equipment is maintained away from combustible materials in accordance with the equipment manufacturer’s instructions.
Combustible debris, rubbish and waste material is removed from the building in areas where work is not being performed.
Temporary wiring does not have exposed conductors.
Flammable liquids and other hazardous materials are stored in locations that have been approved by the site safety director when not involved in work that is being performed.
Fire apparatus access roads required by the California Fire Code are maintained clear of obstructions that reduce the width of the usable roadway to less than 20 feet (6096 mm).
Fire hydrants are clearly visible from access roads and are not obstructed.
The location of fire department connections to standpipe and in-service sprinkler systems are clearly identifiable from the access road and such connections are not obstructed.
Standpipe systems are in service and continuous to the highest work floor, as specified in Section 3311.
Portable fire extinguishers are available in locations required by Section 3309 and for roofing operations in accordance with the California Fire Code .
Where a fire watch is required, fire watch records complying with the California Fire Code are up-to-date.
3302.3.1 Violations. Failure to properly conduct, document and maintain documentation required by this section shall constitute an unlawful act in accordance with Section 114.1 and shall result in the issuance of a notice of violation to the site safety director in accordance with Section 114.2. Upon the third offense, the building official is authorized to issue a stop work order in accordance with Section 115, and work shall not resume until satisfactory assurances of future compliance have been presented to and approved by the building official.