Chapter 25 — GYPSUM PANEL PRODUCTS AND PLASTER
Section 2508 — GYPSUM CONSTRUCTION
2025 California Building Code (Title 24, Part 2) · 2025 edition · updated 2026-07-29 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
2508.1 General. ¶
Gypsum panel products and gypsum plaster construction shall be of the materials listed in Tables 2506.2 and 2507.2. These materials shall be assembled and installed in compliance with the appropriate standards listed in Tables 2508.1 and 2511.1.1 and Chapter 35.
TABLE 2508.1—INSTALLATION OF GYPSUM CONSTRUCTION
| MATERIAL | STANDARD |
|---|---|
| Gypsum panel products | GA-216; ASTM C840 |
| Gypsum sheathing and gypsum panel products | ASTM C1280; GA-253 |
| Gypsum veneer base | ASTM C844 |
| Interior lathing and furring | ASTM C841 |
| Steel framing for gypsum panel products | ASTM C754; C1007 |
2508.2 Limitations. ¶
Gypsum wallboard or gypsum plaster shall not be used in any exterior surface where such gypsum construction will be exposed directly to the weather. Gypsum wallboard shall not be used where there will be direct exposure to water or continuous high humidity conditions. Gypsum sheathing shall be installed on exterior surfaces in accordance with ASTM C1280 or GA-253.
2508.2.1 Weather protection. Gypsum wallboard, gypsum lath or gypsum plaster shall not be installed until weather protection for the installation is provided.
2508.3 Single-ply application. ¶
Edges and ends of gypsum panel products shall occur on the framing members, except those edges and ends that are perpendicular to the framing members. Edges and ends of gypsum panel products shall be in moderate contact except in concealed spaces where fire-resistance-rated construction, shear resistance or diaphragm action is not required.
2508.3.1 Floating angles. Fasteners at the top and bottom plates of vertical assemblies, or the edges and ends of horizontal assemblies perpendicular to supports, and at the wall line are permitted to be omitted except on shear resisting elements or fireresistance-rated assemblies. Fasteners shall be applied in such a manner as not to fracture the face paper with the fastener head.
2508.4 Adhesives. ¶
Gypsum panel products secured to framing with adhesives in ceiling assemblies shall be attached using an approved fastening schedule. Expandable foam adhesives for fastening gypsum wallboard shall conform to ASTM D6464. Other adhesives for the installation of gypsum wallboard shall conform to ASTM C557.
2508.5 Joint treatment. ¶
Gypsum panel product fire-resistance-rated assemblies shall have joints and fasteners treated.
Exceptions: Joint and fastener treatment need not be provided where any of the following conditions occur:
- Where the gypsum panel product is to receive a decorative finish such as wood paneling, battens, acoustical finishes or any similar application that would be equivalent to joint treatment.
- On single-layer systems where joints occur over wood framing members.
- Square edge or tongue-and-groove edge gypsum board (V-edge), gypsum panel products, gypsum backing board or gypsum sheathing.
- On multilayer systems where the joints of adjacent layers are offset.
- Assemblies tested without joint treatment.
2508.6 Horizontal gypsum panel product diaphragm ceilings. ¶
Gypsum panel products shall be permitted to be used on wood joists to create a horizontal diaphragm ceiling in accordance with Table 2508.6.
25-6 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
GYPSUM PANEL PRODUCTS AND PLASTER
TABLE 2508.6—SHEAR CAPACITY FOR HORIZONTAL WOOD-FRAME GYPSUM PANEL PRODUCT DIAPHRAGM CEILING ASSEMBLIES
| MATERIAL | THICKNESS OF MATERIAL (MINIMUM) (inches) |
SPACING OF FRAMING MEMBERS (inches) |
SHEAR VALUEa, b (PLF OF CEILING) |
MIMIMUM FASTENER SIZE |
|---|---|---|---|---|
| Gypsum panel product | 1/2 | 16 o.c. | 90 | 5d cooler or wallboard nail; 15/8-inch long; 0.086-inch shank;15/64-inch headc |
| Gypsum panel product | 1/2 | 24 o.c. | 70 | 5d cooler or wallboard nail; 15/8-inch long; 0.086-inch shank;15/64-inch headc |
| For SI: 1 inch = 25.4 mm, 1 pound per foot = 14.59 N/m. a. Values are not cumulative with other horizontal diaphragm values and are for short-term wind or seismic loading. Values shall be reduced 25 percent for normal loading. b. Values shall be reduced 50 percent in Seismic Design Categories D, E and F. c. 11/4-inch, No. 6 Type S or W screws are permitted to be substituted for the listed nails. |
2508.6.1 Diaphragm proportions. The maximum allowable diaphragm proportions shall be 1 [1] / 2 :1 between shear resisting elements. Rotation or cantilever conditions shall not be permitted.
2508.6.2 Installation. Gypsum panel products used in a horizontal diaphragm ceiling shall be installed perpendicular to ceiling framing members. End joints of adjacent courses of gypsum board shall not occur on the same joist.
2508.6.3 Blocking of perimeter edges. Perimeter edges shall be blocked using a wood member not less than 2-inch by 6-inch (51 mm by 152 mm) nominal dimension. Blocking material shall be installed flat over the top plate of the wall to provide a nailing surface not less than 2 inches (51 mm) in width for the attachment of the gypsum panel product.
2508.6.4 Fasteners. Fasteners used for the attachment of gypsum panel products to a horizontal diaphragm ceiling shall be as defined in Table 2508.6. Fasteners shall be spaced not more than 7 inches (178 mm) on center at all supports, including perimeter blocking, and not more than [3] / 8 inch (9.5 mm) from the edges and ends of the gypsum panel product.
2508.6.5 Lateral force restrictions. Gypsum panel products shall not be used in diaphragm ceilings to resist lateral forces imposed by masonry or concrete construction.
2508.6.6 Diaphragm ceiling connection to partitions. [DSA-SS & DSA-SS/CC and OSHPD 1, 1R, 2, 4 & 5] Gypsum board shall not be used in diaphragm ceilings to resist lateral forces imposed by partitions. Connection of diaphragm ceiling to the vertical lateral force resisting elements shall be designed and detailed to transfer lateral forces.
Exception: [OSHPD 2] Single-story Type V skilled nursing or intermediate care facilities utilizing wood-frame or light-steel-frame construction.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Building Code (Title 24, Part 2)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
- Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
- Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
- Chapter 6 — TYPES OF CONSTRUCTION
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 7A — MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR W…
- Chapter 8 — INTERIOR FINISHES
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
- Chapter 11 — RESERVED
- Chapter 11A — HOUSING ACCESSIBILITY
- Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
- Chapter 12 — INTERIOR ENVIRONMENT
- Chapter 13 — ENERGY EFFICIENCY
- Chapter 14 — EXTERIOR WALLS
- Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
- Chapter 16 — STRUCTURAL DESIGN
- Chapter 16A — STRUCTURAL DESIGN
- Chapter 17 — SPECIAL INSPECTIONS AND TESTS
- Chapter 17A — SPECIAL INSPECTIONS AND TESTS
- Chapter 18 — SOILS AND FOUNDATIONS
- Chapter 18A — SOILS AND FOUNDATIONS
- Chapter 19 — CONCRETE
- Chapter 19A — CONCRETE
- Chapter 20 — ALUMINUM
- Chapter 21 — MASONRY
- Chapter 21A — MASONRY
- Chapter 22 — STEEL
- Chapter 22A — STEEL
- Chapter 23 — WOOD
- Chapter 24 — GLASS AND GLAZING
-
▸ Chapter 25 — GYPSUM PANEL PRODUCTS AND PLASTER
Overview- Section 2501 — GENERAL
- Section 2502 — PERFORMANCE
- Section 2503 — INSPECTION
- Section 2504 — VERTICAL AND HORIZONTAL ASSEMBLIES
- Section 2505 — SHEAR WALL CONSTRUCTION
- Section 2506 — GYPSUM PANEL PRODUCT MATERIALS
- Section 2507 — LATHING AND PLASTERING
- Section 2508 — GYPSUM CONSTRUCTION
- Section 2509 — SHOWERS AND WATER CLOSETS
- Section 2510 — LATHING AND FURRING FOR CEMENT PLASTER (STUCCO)
- Section 2511 — INTERIOR PLASTER
- Section 2512 — EXTERIOR PLASTER
- Section 2513 — EXPOSED AGGREGATE PLASTER
- Section 2514 — REINFORCED GYPSUM CONCRETE
- Chapter 26 — PLASTIC
- Chapter 27 — ELECTRICAL
- Chapter 28 — MECHANICAL SYSTEMS
- Chapter 29 — PLUMBING SYSTEMS
- Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
- Chapter 31 — SPECIAL CONSTRUCTION
- Chapter 31A — SYSTEMS FOR WINDOW CLEANING OR EXTERIOR BUILDING…
- Chapter 31B — PUBLIC POOLS
- Chapter 31C — RADIATION
- Chapter 31D — FOOD ESTABLISHMENTS
- Chapter 31F — MARINE OIL TERMINALS
- Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
- Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
- Chapter 34 — RESERVED
- Chapter 35 — REFERENCED STANDARDS
- Appendix A — EMPLOYEE QUALIFICATIONS
- Appendix B — BOARD OF APPEALS
- Appendix C — GROUP U—AGRICULTURAL BUILDINGS
- Appendix D — FIRE DISTRICTS
- Appendix E — RESERVED
- Appendix F — RODENTPROOFING
- Appendix G — FLOOD-RESISTANT CONSTRUCTION
- Appendix H — SIGNS
- Appendix I — PATIO COVERS
- Appendix J — GRADING
- Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES PROTECTED B…
- Appendix L — EARTHQUAKE RECORDING INSTRUMENTATION
- Appendix M — TSUNAMI-GENERATED FLOOD HAZARDS
- Appendix N — REPLICABLE BUILDINGS
- Appendix O — PERFORMANCE-BASED APPLICATION
- Appendix P — SLEEPING LOFTS
- Appendix Q — EMERGENCY HOUSING