CRSC · California Referenced Standards Code
What inspection and sample-collection powers does the Commission have?
The Commission can enter the business premises of manufacturers, distributors or retailers (with owner/lessee consent or a search warrant) during normal working hours to collect representative insulation samples and inspect testing records; it can also have those samples independently tested for enforcement under § 12-13-1558 and § 12-13-1559.
Last reviewed: July 6, 2026
What the code requires — 2-4 sentences
The Commission may access the premises of manufacturers, distributors and retailers of insulating material sold for installation in California to determine compliance, and that access may be with the consent of the owner or lessee or upon securing a search warrant. Access is limited to during normal working hours and is expressly for obtaining representative samples of the subject insulation and inspecting records and documents of tests by approved testing laboratories. The controlling text is § 12-13-1558 .
The Commission can enter (with consent or a warrant), during normal working hours, to take representative samples and inspect testing records from manufacturers, distributors, and retailers. § 12-13-1558
Requirements in detail
Who and where
- Who: manufacturers, distributors and retailers of insulating material sold for installation within the state. § 12-13-1558 .
- Where: the premises of those manufacturers, distributors and retailers (i.e., their business locations), not the text’s scope beyond those categories. § 12-13-1558 .
How access is obtained
- Two lawful bases for entry:
- Consent of the owner or lessee; or
- Search warrant obtained before entry. § 12-13-1558 .
- Time limitation: access only during normal working hours (the phrase used in the section). § 12-13-1558 .
Permitted activities during access
- Obtaining representative samples of the subject insulation (the section uses the phrase “representative samples”). § 12-13-1558 .
- Inspecting records and documents pertaining to tests by approved testing labs. This ties to the Commission’s lab approval and certification program elsewhere in the article (see Related provisions). § 12-13-1558 .
Relationship to independent testing
- The Commission may itself conduct, or contract others to conduct, independent performance tests of representative samples; those tests may form the basis for enforcement. See § 12-13-1559 for this testing authority.
Decision-relevant dimensions (quick reference table)
| Decision dimension | Value / Rule | Code Reference |
|---|---|---|
| Permissible premises | Manufacturers, distributors and retailers of insulating material sold for installation in CA | § 12-13-1558 |
| Entry authority | Consent of owner/lessee OR search warrant | § 12-13-1558 |
| Time for access | During normal working hours | § 12-13-1558 |
| Purpose of access | Obtain representative samples; inspect records/documents of tests by approved labs | § 12-13-1558 |
| Independent testing authority | Commission may conduct or contract independent performance tests; tests can support enforcement | § 12-13-1559 |
| Lab approval / test results | Laboratories are approved under Commission criteria and certification procedures (affects records the Commission may inspect) | § 12-13-1554 and § 12-13-1555 |
Exceptions & special cases
- The statute requires either consent or a search warrant for entry; absent one of those, the section does not authorize forcible or warrantless entry. § 12-13-1558 .
- The text is limited to premises of manufacturers, distributors and retailers of insulating materials sold for installation in the state; it does not say the Commission can enter job sites or private residences under this section. § 12-13-1558 .
- The section does not define “representative samples”, “normal working hours” (beyond the phrase), or how many/which samples may be taken. Those operational details are not specified in the retrieved text of § 12-13-1558 — if you need those specifics, you must consult Commission procedures or other legal authorities (or other CRSC text not retrieved here).
Common mistakes
- Assuming the Commission can enter at any time without consent or a warrant — the code requires consent or a warrant and limits access to normal working hours. § 12-13-1558 .
- Treating the authority as applying to installers’ job sites or homeowners’ properties — the section expressly names manufacturers, distributors and retailers. § 12-13-1558 .
- Expecting the section to set sample sizes, chain-of-custody, or lab methods — § 12-13-1558 authorizes taking representative samples but does not prescribe sampling protocols or quantities. § 12-13-1558 .
- Confusing inspection of labels/identification (addressed elsewhere, e.g., § 12-13-1557) with the sampling/records-inspection authority in § 12-13-1558.
Worked example — concrete scenario (illustrative)
Scenario: A Commission investigator seeks to verify a manufacturer’s certified R-value claims.
- Facility: warehouse of a manufacturer that stores 10,000 rolls of a batt insulation product sold in California.
- Legal basis: the investigator obtains a search warrant to enter (or alternatively secures the consent of the owner or lessee). § 12-13-1558 .
- Timing: entry occurs at 10:00 AM (within normal working hours). § 12-13-1558 .
- Sampling: the investigator takes representative samples — for example, removing 3 cartons (e.g., 30 rolls total) for testing. Note: § 12-13-1558 authorizes taking representative samples but does not set the number or sampling method; the “3 cartons / 30 rolls” here is an illustrative operational choice, not a statutory requirement. § 12-13-1558 .
- Records review: the investigator inspects the manufacturer’s test reports and lab certifications for the product provided by the manufacturer’s approved testing lab. § 12-13-1558 permits inspection of records/documents pertaining to tests by approved testing labs. § 12-13-1558 .
- Follow-up testing: the Commission may then conduct or contract independent performance tests on the samples; those results can form the basis of enforcement if they show noncompliance. See § 12-13-1559.
Related provisions
- § 12-13-1559 — Commission authority to conduct or contract independent performance tests of representative samples; tests may form the basis for enforcement.
- § 12-13-1557 — Identification and labeling requirements for insulating materials (relates to what the Commission may check on the product).
- § 12-13-1555 — Manufacturer certification requirements and test-result submissions (records the Commission may inspect).
- § 12-13-1554 — Approval criteria for testing laboratories (relevant to the record-review authority).
Code references
Grounded in the retrieved California Referenced Standards Code — click a citation to read the verbatim passage:
CRSC § 2602.1 High relevance — show source text
(c) Any representation of thermal performance which appear on any label, literature, advertising or any other writing intended for the public shall be consistent with the certification testing results and derating required by this article.
(d) Any insulation with facings and membranes for which the flame spread exceeds 25 when tested with facings and membranes exposed to the flame during the ANSI/ASTM E84-79 test must be clearly labeled with a statement that the product may be highly combustible if used in an exposed application. This subsection shall not apply to any product meeting the requirements of Sections 2602.1-2602.6 of the 1994 Uniform Building Code.
Authority: Section 25218(e), Public Resources Code.
Reference: Section 25921, Public Resources Code.
HISTORY:
- Amendment of subsections (a) and (c) filed 8-10-81; designated effective 9-22-81 (Register 81, No. 33).
INSPECTIONS
Sec. 12-13-1558.
After September 22, 1981, the Commission may, upon the consent of the owner or lessee, or upon securing a search warrant, have access, during normal working hours, to the premises of manufacturers, distributors and retailers of insulating material sold for installation within the state for the purpose of determining compliance with the standards promulgated pursuant to Chapter 10.5 of the California Public Resources Code . Such access shall be for the purposes of obtaining representative samples of subject insulation and inspecting records and documents pertaining to tests by approved testing labs.
Authority: Section 25218 (e), Public Resources Code.
Reference: Section 25926, Public Resources Code.
HISTORY:
- Amendment filed 8-10-81; designated effective 9-22-81 (Register 81, No. 33).
PERFORMANCE TESTS
Sec. 12-13-1559.
The Commission may conduct, or may contract with others to conduct, independent performance tests of representative samples of insulation sold in the state to determine compliance with standards adopted pursuant to Chapter 10.5 of the California Public Resources Code . Such tests shall form the basis for instituting enforcement proceedings.
Authority: Section 25218 (e), Public Resources Code.
Reference: Section 25926, Public Resources Code.
HISTORY:
- Amendment filed 8-10-81; designated effective 9-22-81 (Register 81, No. 33).
2025 CALIFORNIA REFERENCED STANDARDS CODE 99
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
STANDARDS FOR INSULATING MATERIAL
COSTS OF INSPECTION AND TESTING (RESERVED)
Sec. 12-13-1560.
Authority: Section 25218 (e), Public Resources Code.
Reference: Section 25926, Public Resources Code.
HISTORY:
- Repealer filed 8-10-81; designated effective 9-22-81 (Register 81, No. 33).
ENFORCEMENT (RESERVED)
Sec. 12-13-1561.
Authority: Section 25218 (e), Public Resources Code.
Reference: Section 25931, Public Resources Code.
HISTORY:
- Repealer filed 6-26-79; effective thirtieth day thereafter (Register 79, No. 26).
RELEASE OF INFORMATION
CRSC § 25921.1 High relevance — show source text
Reference: Sections 25921 and 25921.1, Public Resources Code.
HISTORY:
- Amendment of subsections (a), (b) (4), (b) (6) and (f) filed 8-10-81; designated effective 9-22-81 (Register 81, No. 33).
QUALITY ASSURANCE (RESERVED)
Sec. 12-13-1556.
Authority: Section 25218 (e), Public Resources Code.
Reference: Section 25921.1, Public Resources Code.
HISTORY:
- Repealer filed 8-10-81; designated effective 9-22-81 (Register 81, No. 33).
IDENTIFICATION
Sec. 12-13-1557.
(a) Except as specified in subsection (b), Item 3, of this section, no insulation shall be sold in California on or after September 22, 1981, unless the insulating material, container, bundle or similar packaging material bears a visible Commission approved statement certifying that a representative sample of the insulation material has been tested and approved by an approved laboratory and complies with the requirements of this article.
(b) The Commission-approved statement shall consist of either:
A design or statement approved by the Executive Director, or
An identification of the manufacturer and any statement that the material meets the quality standards of the State of California.
A statement that the material meets the quality standards of the State of California included in the bill of lading shall meet the requirements of this section only if the product is being shipped in bulk, or the container or product is not otherwise labeled by the manufacturer and the product is being sold to its ultimate user.
(c) Any representation of thermal performance which appear on any label, literature, advertising or any other writing intended for the public shall be consistent with the certification testing results and derating required by this article.
(d) Any insulation with facings and membranes for which the flame spread exceeds 25 when tested with facings and membranes exposed to the flame during the ANSI/ASTM E84-79 test must be clearly labeled with a statement that the product may be highly combustible if used in an exposed application. This subsection shall not apply to any product meeting the requirements of Sections 2602.1-2602.6 of the 1994 Uniform Building Code.
Authority: Section 25218(e), Public Resources Code.
Reference: Section 25921, Public Resources Code.
HISTORY:
- Amendment of subsections (a) and (c) filed 8-10-81; designated effective 9-22-81 (Register 81, No. 33).
INSPECTIONS
Sec. 12-13-1558.
After September 22, 1981, the Commission may, upon the consent of the owner or lessee, or upon securing a search warrant, have access, during normal working hours, to the premises of manufacturers, distributors and retailers of insulating material sold for installation within the state for the purpose of determining compliance with the standards promulgated pursuant to Chapter 10.5 of the California Public Resources Code . Such access shall be for the purposes of obtaining representative samples of subject insulation and inspecting records and documents pertaining to tests by approved testing labs.
Authority: Section 25218 (e), Public Resources Code.
Reference: Section 25926, Public Resources Code.
HISTORY:
CRSC § 25921.1 Medium relevance — show source text
- A declaration that the insulating material complies with the requirements of this article.
- The wording of the certification seal, if such seal consists of a statement pursuant to Section 1557 (b) (2) of this article.
(c) Every certification statement shall be dated and signed by the manufacturer attesting to its truth and accuracy. Where the manufacturer is either a corporation or a business association, the certification statement shall be dated, signed and attested to by a responsible official thereof.
(d) Within 45 days after receipt of a certification statement, the Executive Director shall forward, to the manufacturer, an acknowledgment that the statement has been received and that it is complete and accurate on its face.
(e) Certification of the insulation material shall be deemed to occur upon forwarding of the acknowledgement by the Executive Director. If acknowledgment is not forwarded in a timely manner, certification shall be deemed to occur on the 45th day after receipt of the certification statement.
(f) The statement of test results required in the certification may be based upon tests conducted prior to the adoptive date of this article if: (1) the same test was conducted within two years of the date of adoption, (2) the laboratory at which the tests were
98 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
STANDARDS FOR INSULATING MATERIAL
conducted has been approved for those tests as of the date of the certification statement, and (3) the laboratory certifies that the test and product are the same as the test and product referred to in the statement of test results.
Authority: Section 25218(e), Public Resources Code.
Reference: Sections 25921 and 25921.1, Public Resources Code.
HISTORY:
- Amendment of subsections (a), (b) (4), (b) (6) and (f) filed 8-10-81; designated effective 9-22-81 (Register 81, No. 33).
QUALITY ASSURANCE (RESERVED)
Sec. 12-13-1556.
Authority: Section 25218 (e), Public Resources Code.
Reference: Section 25921.1, Public Resources Code.
HISTORY:
- Repealer filed 8-10-81; designated effective 9-22-81 (Register 81, No. 33).
IDENTIFICATION
Sec. 12-13-1557.
(a) Except as specified in subsection (b), Item 3, of this section, no insulation shall be sold in California on or after September 22, 1981, unless the insulating material, container, bundle or similar packaging material bears a visible Commission approved statement certifying that a representative sample of the insulation material has been tested and approved by an approved laboratory and complies with the requirements of this article.
(b) The Commission-approved statement shall consist of either:
A design or statement approved by the Executive Director, or
An identification of the manufacturer and any statement that the material meets the quality standards of the State of California.
A statement that the material meets the quality standards of the State of California included in the bill of lading shall meet the requirements of this section only if the product is being shipped in bulk, or the container or product is not otherwise labeled by the manufacturer and the product is being sold to its ultimate user.
CRSC § 73.4 Medium relevance — show source text
All foam insulation materials using materials other than air or pentane as an expanding agent shall either separately condition samples at 73.4° ± 3.6°F and a relative humidity of 50 ± 5 percent, and at 140°F (60°C) dry heat and test at 30-, 60- and 90-day intervals or shall test samples certified by an approved testing laboratory to have been aged while exposed to free air in a well ventilated room for at least two years at 70° ± 10°F, provided, however, that until 2 [1] / 2 years after the adoption of these quality standards by the Commission, test samples may be aged for six months for certification of the material. Notwithstanding any other provision of this article, this thermal performance standard shall not take effect until 250 days after adoption. If the certification statement submitted pursuant to Section 1555 of these regulations does not include test results for thermal performance, the manufacturer shall submit a new certification statement which includes such test results prior to 250 days after adoption. If the latest certification statement is based on the six-month aging test, a new statement, based upon the two-year aging test or the accelerated aging test shall be submitted by 2 [1] / 2 years after the adoption date. 3. Dimensional stability. All foamed polyurethane and polyisocyanurate insulation materials which are factory formed shall be tested for dimensional stability in accordance with Procedures E and G of ASTM D2126-75 with the following exceptions: (a) sample size shall be 12 inches by 12 inches (305 mm by 305 mm) ± 1 inch (25 mm) and (b) samples shall be tested as manufactured with or without facers.
The average percent change in length or width shall not exceed ± 2 percent in 24 hours or ± 4 percent in 7 days. The average percent change in thickness shall not exceed ± 10 percent in 7 days. Samples shall be regarded as failing if: (1) delamination area of “faced” samples exceeds 25 percent or (2) warping or cupping exceeds [1] / 4 inch (6 mm) when checked by a straight edge across raised diagonal corners.
- Resistance to combustion.
A. The material shall be tested to meet the requirements of Sections 2602.1-2602.6 of the 1994 Uniform Building Code, with the additional provision that the surface-burning characteristics shall be determined according to ANSI/ASTM E84-79 and shall not exceed the following values:
Flame spread . . . . . . . . . . . . . . . . . . . . . 75 Smoke developed . . . . . . . . . . . . . . . . 450 B. This subsection shall not apply to any product recognized by the International Conference of Building Officials, as of the date of adoption of this article, as complying with Sections 2602.1-2602.6 of the 1994 Uniform Building Code based solely upon diversified testing. The manufacturer of any product which is recognized by the International Conference of Building Officials, subsequent to the date of approval of these regulations, as complying with Sections 2602.12602.6 of the 1994 Uniform Building Code based solely upon diversified testing, may petition the Commission for an exemption of that product from the provisions of this subsection. 5. Identification. Foam containers shall state the conditions of proper storage.
CRSC § 12-13 Medium relevance — show source text
PERFORMANCE TESTS
Sec. 12-13-1559.
The Commission may conduct, or may contract with others to conduct, independent performance tests of representative samples of insulation sold in the state to determine compliance with standards adopted pursuant to Chapter 10.5 of the California Public Resources Code . Such tests shall form the basis for instituting enforcement proceedings.
Authority: Section 25218 (e), Public Resources Code.
Reference: Section 25926, Public Resources Code.
HISTORY:
- Amendment filed 8-10-81; designated effective 9-22-81 (Register 81, No. 33).
2025 CALIFORNIA REFERENCED STANDARDS CODE 99
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
STANDARDS FOR INSULATING MATERIAL
COSTS OF INSPECTION AND TESTING (RESERVED)
Sec. 12-13-1560.
Authority: Section 25218 (e), Public Resources Code.
Reference: Section 25926, Public Resources Code.
HISTORY:
- Repealer filed 8-10-81; designated effective 9-22-81 (Register 81, No. 33).
ENFORCEMENT (RESERVED)
Sec. 12-13-1561.
Authority: Section 25218 (e), Public Resources Code.
Reference: Section 25931, Public Resources Code.
HISTORY:
- Repealer filed 6-26-79; effective thirtieth day thereafter (Register 79, No. 26).
RELEASE OF INFORMATION
Sec. 12-13-1562.
Persons submitting information to the Commission who wish information to be kept confidential shall comply with the provisions of Sections 2501-2511 of the Public Resources Code.
Authority: Section 25218(e), Public Resources Code.
Reference: Sections 25223 and 25921.1, Public Resources Code.
HISTORY:
- Amendment filed 8-10-81; designated effective 9-22-81 (Register 81, No. 33).
LIABILITY
Sec. 12-13-1563.
Nothing in this article shall be construed as imposing responsibility on manufacturers for misuse of properly labeled insulation.
Authority: Section 25218(e), Public Resources Code.
Reference: Sections 25926 and 25931, Public Resources Code.
HISTORY:
- Amendment filed 8-10-81; designated effective 9-22-81 (Register 81, No. 33).
INSULATING EXISTING BUILDINGS
Sec. 12-13-1564.
(a) On or after March 25, 1982, if insulating material is installed in an existing building, in any of the applications specified in California Code of Regulations, Title 24, Part 6, Section 118, the installing contractor shall certify that the amount of insulation installed meets or exceeds the requirements of Part 6, Section 118 for that application. Such certification shall be made on completion of the installation by posting in a conspicuous location a certificate signed under penalty of perjury.
CRSC § 3102F.3.5.3 Medium relevance — show source text
The samples may be limited to particular zones or portions of members if damage is_ suspected, based on the physical evidence of potential problems. A minimum sample size of three members should be used. A five-percent sample size, up to 30 total members, may be adequate as an upper limit.
For wrapped timber components, Level III efforts should consist of removal of the wraps from a representative sample of components in order to evaluate the condition of the timber beneath the wrap. The sample may be limited to particular zones or portions of the members if damage is suspected (e.g., at the mudline/ bottom of wrap or in the tidal zone). The sample size should be determined based on the physical evidence of potential problems and the aggressiveness of the environment. A mini- mum sample size of three members should be used. A five-percent sample size, up to 30 total members, may be adequate as an upper limit.
3102F.3.5.3 Mechanical and electrical inspections. The mechanical and electrical inspections shall include but not be limited to the following:
1. Loading arms
2. Cranes and lifting equipment, including cables
3. Piping/manifolds and supports
4. Oil transfer hoses
5. Fire detection and suppression systems
6. Vapor control system
7. Sumps/sump tanks
8. Vent systems
9. Pumps and pump systems
10. Lighting
11. Communications equipment
12. Gangways
13. Electrical switches and junction boxes
14. Emergency power equipment
15. Air compressors
16. Meters
17. Cathodic protection systems
18. Winches
19. ESD and other control systems
20. Ladders
All alarms, limit switches, load cells, current meters, anemometers, leak detection equipment, etc., shall be operated and/or tested to the extent feasible, to ensure proper function.
Utility, auxiliary and fire protection piping shall have external visual inspections, similar to that defined in Section 10.1 of API RP 574 [2.3] (N/E).
3102F.3.5.4 Corrosion inspection. During each audit, a comprehensive corrosion inspection shall be performed by a qualified engineer or technician. This inspection shall include all steel and metallic components, and any installed cathodic protection system (CPS). CPS inspection during the audit is not intended to substitute for required testing and maintenance performed on a
31F-10 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MARINE OIL TERMINALS
more frequent schedule per Section 3111F.10. All inspection results shall be documented, and shall be used in the corrosion assess- ment (Section 3102F.3.6.5).
Submerged wharf structures and associated cathodic protection equipment (if installed) shall be inspected per [2.2]. Above water structures, ancillary equipment, supports and hardware shall be visually inspected. Corrosion inspection of utility, auxiliary and fire pipelines shall be done per Section 3102F.3.5.3.
CRSC § 3.1. Medium relevance — show source text
Defects in the system or leaks detected shall be documented and repaired. 2. A cylinder-filling performance test shall be conducted to verify compliance with the required breathing air cylinder refill rate from the exterior mobile air connection and, where provided, a stored air pressure supply system. 3. The air quality monitoring system shall be tested to verify both of the following conditions: 3.1. Visual indicators required by Section L104.15.1 function properly. 3.2. Supervisory signals are transmitted as required by Section L104.15.2 for each sensor based on a sensor function test. 4. Connections intended for fire department use shall be confirmed as compatible with the fire department’s mobile air unit, SCBA cylinders and, where provided, RIC/UAC connections. 5. Air samples shall be taken from not less than two fill stations and submitted to an approved gas analysis laboratory to verify compliance with NFPA 1989. The FARS shall not be placed into service until a written report verifying compliance with NFPA 1989 has been provided to the fire code official.
SECTION L106—INSPECTION, TESTING AND MAINTENANCE
L106.1 Periodic inspection, testing and maintenance. A FARS shall be continuously maintained in an operative condition and shall be inspected not less than annually. Not less than quarterly, an air sample shall be taken from the system and tested to verify compliance with NFPA 1989. The laboratory test results shall be maintained on site and readily available for review by the fire code official.
SECTION L107—REFERENCED STANDARDS
L107.1 General. See Table L107.1 for standards that are referenced in various sections of this appendix. Standards are listed by the standard identification with the effective date, standard title, and the section or sections of this appendix that reference the standard.
TABLE L107.1—REFERENCED STANDARDS Col2 Col3 STANDARD ACRONYM STANDARD NAME SECTIONS HEREIN REFERENCED ASME B31.3—2022 Process Piping L104.2.1, L105.1 CGA S-1.3—2020 Pressure Relief Device Standards—Part 3
Stationary Storage Containers for Compressed GasesL104.7 NFPA 1901—16 Standard for Automotive Fire Apparatus L104.5.1 NFPA 1989—13 Breathing Air Quality for Fire Emergency Services Respiratory Protection L104.2.2, L105.1, L106.1 2025 CALIFORNIA FIRE CODE APPENDIX L-5
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX L-6 2025 CALIFORNIA FIRE CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
CALIFORNIA FIRE CODE – MATRIX ADOPTION TABLE
APPENDIX M – HIGH-RISE BUILDINGS—RETROACTIVE AUTOMATIC SPRINKLER REQUIREMENT
(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
(Not adopted by the State Fire Marshal)
CRSC § 0.75. Medium relevance — show source text
- Except as provided in Items 5 and 6, the thermal performance test results certified under Section 1555 of this article shall be the average of the values obtained from at least three tests.
- The average measured thermal performance of the tests required by Items 5, 6 and 7 shall not be more than 5 percent below the value specified on the product. In addition, all insulation material sold within the state after September 22, 1981, shall have a measured thermal performance not more than 10 percent below the value specified on the product.
- All numbered test descriptions shall be contained in the document “Test Descriptions for Insulating Material” dated February 27, 1981.
90 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
STANDARDS FOR INSULATING MATERIAL
Facings on representative samples may be removed or modified by slitting for the ANSI/ASTM C177-76 and ANSI/ASTM C518-76 tests.
All thermal performance testing equipment used for testing insulating materials shall be calibrated with samples referenced to the United States National Bureau of Standards.
Manufacturers of loose fill insulations for which no settled density test is required by this section shall be required to include the installed design density in the identifying information described in Section 1557. The manufacturer shall provide sufficient documentation to establish a valid basis for the determination of installed design density. The Executive Director shall determine whether a valid basis exists for the installed design density claimed by the manufacturer. If it is determined that a valid basis does not exist, the director may assign an appropriate installed design density or may require an appropriate test to determine the installed design density. The manufacturer may appeal the Executive Director’s determination to the full Commission.
Within 180 days after the availability of appropriate representative thickness calibration samples from the National Bureau of Standards, all insulating materials thicker than 1 inch (25 mm), which have not previously been tested at the representative thickness of a representative sample, shall be tested at representative thickness and recertified. Test results and a revised certification statement will be submitted to the Executive Director. The Executive Director shall determine if and when an appropriate representative thickness calibration sample is available from the National Bureau of Standards and shall publish a list of available representative thickness calibration samples. The manufacturer may appeal the Executive Director’s determination to the full Commission.
All products which may be used for pressure fill retrofit wall application shall be separately tested for thermal performance using a sample prepared at the manufacturer’s recommended wall density for such applications.
All water heater insulation kits and nonpreformed pipe insulation shall be tested for thermal performance at the installed compressed thickness of a typical application. Installed compressed thickness shall be determined according to Test Description Number 6. All nonpreformed duct insulation shall be labeled, in accordance with Section 1557(c), with an installed R -value equal to the R -value of the uncompressed insulation times 0.75. (b) Aluminum foil.
Composition. The insulation shall have uniform flat surfaces and shall not be crumpled, torn or punctured. Aluminum foil shall contain not less than 99 percent aluminum. Kraft paper and flangeboard shall meet the requirements of ANSI/TAPPI T400 0S75. Flangeboard used for more than two insulation layers shall be of 28 point grade minimum, if single sheet flangeboard is used or 14 point grade minimum if double sheet flangeboard is used.
California Referenced Standards Code Medium relevance — show source text
|100 psf|1 hr
23 min|||7|1, 2|11/3| |F/C-4-RC-9|4″|4″ deep (4370 psi);1/4″ reinforcement bars
at 6″ pitch with3/4″ cover;1/4″ main rein-
forcement bars at 4″ pitch perpendicular
with1/2″ cover; 13′1″ span restrained.|150 psf|2 hrs|||7|1, 3|2| |F/C-4-RC-10|4″|4″ thick (5140 psi) deck;1/4″ reinforce-
ment bars at 71/2″ pitch with7/8″ cover;3/8″
main reinforcement bars at 33/4″ pitch
perpendicular with1/2″ cover; 13′1″ span
restrained.|140 psf|1 hr
16 min|||7|1, 5|11/4| |F/C-4-RC-11|4″|4″ thick (4000 psi) concrete deck;
3″ × 11/2″ × 4 lbs R.S.J.; 2′6″ C.R.S.; flush
with top surface; 4″ × 6″ x 13 SWG mesh
reinforcement 1″ from bottom of slab; 6′6″
span restrained.|150 psf|2 hrs|||7|1, 3|2| |F/C-4-RC-12|4″|4″ deep (2380 psi) concrete deck;
3″ × 11/2″ × 4 lbs R.S.J.; 2′6″ C.R.S.; flush
with top surface; 4″ × 6″ x 13 SWG mesh
reinforcement 1″ from bottom surface;
6′6″ span restrained.|150 psf|1 hr
3 min|||7|1, 2|1| |F/C-4-RC-13|41/2″|41/2″ thick (5200 psi) deck;1/4″ reinforce-
ment bars at 71/4″ pitch with7/8″ cover;3/8″
main reinforcement bars at 33/4″ pitch
perpendicular with1/2″ cover; 13′1″ span
restrained.|140 psf|2 hrs|||7|1, 3|2| |F/C-4-RC-14|41/2″|41/2″ deep (2525 psi) concrete deck;1/4″
reinforcement bars at 71/2″ pitch with7/8″
cover;3/8″ main reinforcement bars at
33/8″ pitch perpendicular with1/2″ cover;
13′1″ span restrained.|150 psf|42 min|||7|1, 5|2/3| |F/C-4-RC-15|41/2″|41/2″ deep (4830 psi) concrete deck;
11/2″ × No.CRSC § 73.4 Medium relevance — show source text
- Thermal performance. Determination of the thermal performance shall be in accordance with ANSI/ASTM C177-76, ANSI/ASTM C236-66 or ANSI/ASTM C518-76 at the manufacturer’s option. All foam insulation materials using materials other than air or pentane as an expanding agent shall either separately condition samples at 73.4° ± 3.6°F and a relative humidity of 50 ± 5 percent, and at 140°F dry heat and test at 30-, 60- and 90-day intervals or shall test samples certified by an approved testing laboratory to have been aged while exposed to free air in a well ventilated room for at least two years at 70° ± 10°F, provided, however, that until 2 [1] / 2 years after the adoption of these quality standards by the Commission, test samples may be aged for six months for certification of the material. Notwithstanding any other provision of this article, this thermal performance standard shall not take effect until 250 days after adoption. If the certification statement submitted pursuant to Section 1555 of this article does not include test results for thermal performance, the manufacturer shall submit a new certification statement which includes such test results prior to 250 days after adoption. If the latest certification statement is based on the six-month aging test, a new statement, based upon the two-year aging test or the accelerated aging test shall be submitted by 2 [1] / 2 years after the adoption date.
- A. Resistance to combustion. The material shall be tested to meet the requirements of Sections 2603.2 and 2603.3 of the California Building Code, with the additional provision that the surface-burning characteristics shall be determined according to ANSI/ASTM E84-79 and shall not exceed the following values:
Flame spread . . . . . . . . . . . . . . . . . . . . 75 Smoke developed . . . . . . . . . . . . . . . .450 Exception: Polystyrene foam insulation boards with a maximum thickness of 2 inches (51 mm) when installed below a minimum 3.5-inch-thick (89 mm) concrete slab on grade.
94 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
STANDARDS FOR INSULATING MATERIAL
B. This subsection shall not apply to any product recognized by the International Conference of Building Officials, as of the date of adoption of these regulations, as complying with Sections 2602.1-2602.6 of the 1994 Uniform Building Code based solely upon diversified testing. The manufacturer of any product which is recognized by the International Conference of Building Officials, subsequent to the date of approval of these regulations, as complying with Sections 2602.1-2602.6 of the 1994 Uniform Building Code based solely upon diversified testing, may petition the Commission for an exemption of that product from the provisions of this subsection. 4. Dimensional stability. All foamed polystyrene insulation materials which are factory formed shall be tested for dimensional stability in accordance with Procedures E and G of ASTM D2126-75 with the following exceptions: (a) sample size shall be 12 inches by 12 inches (305 mm by 305 mm) ± 1 inch (25 mm), and (b) samples shall be tested as manufactured with or without facers.
CRSC § 12-7 Medium relevance — show source text
TABLE SFM 12-7-1A—CONDITIONS FOR HOSE STREAM TEST Col2 Col3 WATER PRESSURE AT BASE OF NOZZLE
(POUNDS PER SQUARE INCH)DURATION OF APPLICATION,
MINUTES PER 100 SQUARE FEET OF EXPOSED
AREA4 hours and over 45 5 2 hours and over, if less than 4 30 21/2 11/2 hours and over, if less than 2 30 11/2 1 hour and over, if less than 11/2 30 1 Less than 1 hour, if desired 30 1 For SI: 1 square foot = 92 903 mm2 For SI: 1 square foot = 92 903 mm2 For SI: 1 square foot = 92 903 mm2 2025 CALIFORNIA REFERENCED STANDARDS CODE 21
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
22 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
12-7-2 FIRE-RESISTIVE STANDARDS
RESERVED
2025 CALIFORNIA REFERENCED STANDARDS CODE 23
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
24 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
12-7-3 FIRE-RESISTIVE STANDARDS
FIRE TESTING FURNACES
STANDARD 12-7-3
STATE FIRE MARSHAL
SCOPE
Sec. 12-7-300. This standard sets forth the general requirements for the design and control of fire testing furnaces intended for fire exposure testing and assignment of fire endurance ratings of building materials, assemblies of building materials, equipment and devices.
FURNACE DESIGN AND DIMENSIONS
Sec. 12-7-301. Furnaces shall consist of a furnace chamber and an insulated specimen frame. The furnace chamber walls and floor shall consist of insulating fire brick or equivalent heat-reflective materials. Furnace dimensions shall be not less than shown in the following:
(a) Vertical large-scale wall furnace. The furnace exposure panel or door shall consist of an insulated steel restraining frame having an available opening for the test sample of not less than 200 square feet (18.6 m [2] ) in area with neither dimension less than 9 feet (2743 mm).
(b) Vertical half-scale wall furnace. The furnace exposure panel or door shall consist of an insulated steel restraining frame having an available opening of not less than 50 square feet (4.6 m [2] ) for the test sample. Neither dimension of the furnace opening shall be less than 7 feet (2133 mm).
(c) Horizontal large-scale floor furnace. The furnace exposure panel shall consist of an insulated steel restraining frame having an available opening of not less than 180 square feet (16.7 m [2] ) for the test sample. Neither dimension of the furnace opening shall be less than 12 feet (3657 mm).
CRSC § 73.4 Medium relevance — show source text
** All foamed polystyrene insulation materials which are factory formed shall be tested for dimensional stability in accordance with Procedures E and G of ASTM D2126-75 with the following exceptions: (a) sample size shall be 12 inches by 12 inches (305 mm by 305 mm) ± 1 inch (25 mm), and (b) samples shall be tested as manufactured with or without facers.
The average percent change in length or width shall not exceed ± 2 percent in 24 hours or ± 4 percent in 7 days. The average percent change in thickness shall not exceed ± 10 percent in 7 days. Samples shall be regarded as failing if: (1) delamination area of “faced” samples exceeds 25 percent or (2) warping or cupping exceeds [1] / 4 inch (6 mm) when checked by a straight edge across raised diagonal corners.
(l) Polyurethane and polyisocyanurate in board form and field applied.
- Composition. The manufacture of the insulation shall be based mainly on the reaction of an organic polyisocyanate with a polyol resin.
Board shall be of uniform texture, reasonably free from accumulation of unexpanded material and foreign inclusions, and reasonably free of broken edges and corners. It shall be reasonably free from holes, voids, depressions and objectionable odor. Laminated composite boards shall be included in this quality standard. The faces of laminated boards shall adhere firmly throughout to the foam, and shall show no excessive amounts of slits, voids or depressions. 2. Thermal performance. Determination of the thermal performance shall be in accordance with ANSI/ASTM C177-76, ANSI/ASTM C236-66 or ANSI/ASTM C518-76 at the manufacturer’s option. All foam insulation materials using materials other than air or pentane as an expanding agent shall either separately condition samples at 73.4° ± 3.6°F and a relative humidity of 50 ± 5 percent, and at 140°F (60°C) dry heat and test at 30-, 60- and 90-day intervals or shall test samples certified by an approved testing laboratory to have been aged while exposed to free air in a well ventilated room for at least two years at 70° ± 10°F, provided, however, that until 2 [1] / 2 years after the adoption of these quality standards by the Commission, test samples may be aged for six months for certification of the material. Notwithstanding any other provision of this article, this thermal performance standard shall not take effect until 250 days after adoption. If the certification statement submitted pursuant to Section 1555 of these regulations does not include test results for thermal performance, the manufacturer shall submit a new certification statement which includes such test results prior to 250 days after adoption. If the latest certification statement is based on the six-month aging test, a new statement, based upon the two-year aging test or the accelerated aging test shall be submitted by 2 [1] / 2 years after the adoption date. 3. Dimensional stability. All foamed polyurethane and polyisocyanurate insulation materials which are factory formed shall be tested for dimensional stability in accordance with Procedures E and G of ASTM D2126-75 with the following exceptions: (a) sample size shall be 12 inches by 12 inches (305 mm by 305 mm) ± 1 inch (25 mm) and (b) samples shall be tested as manufactured with or without facers.
Frequently asked questions
Can the Commission enter a retail store without a warrant?
No — under § 12-13-1558 the Commission may enter with the consent of the owner or lessee or upon securing a search warrant; absent consent or a warrant, the section does not authorize entry.
Does § 12-13-1558 set how many samples the Commission can take?
No — § 12-13-1558 authorizes taking representative samples but does not prescribe sample sizes or sampling methodology. Operational sampling rules are not specified in the retrieved text.
May the Commission test samples itself?
Yes — the Commission may conduct or contract independent performance tests of representative samples; such tests can form the basis for enforcement proceedings under § 12-13-1559.
Can the Commission inspect test reports from unapproved labs?
The section specifically authorizes inspection of records and documents pertaining to tests by approved testing labs; approval procedures and lab status are addressed elsewhere (e.g., § 12-13-1554 and § 12-13-1555).
Is the Commission’s access limited to business hours only?
Yes — the language of § 12-13-1558 limits access to during normal working hours. The statute does not define “normal working hours” in the retrieved text.
More in California Referenced Standards Code
- Administration and scope — CRSC Chapter 12 overview
- Air filter standards (Chapter 12‑71)
- Building and facility access / accessibility standards (Chapters 12‑11A, 12‑11B)
- Engineering regulations — quality and design of construction materials (12‑16 series)
- Exits and means of egress (Chapters 12‑10 series)
- Protective signaling systems and detectors (Chapters 12‑72‑1, ‑2, ‑3)
- Radiation shielding standards (Chapter 12‑31C)
- Referenced standards index / cross‑reference table (Part 12 listing of referenced standards)
- Releasing systems for security bars (egress-release standards)
- Standards for insulating materials (Chapter 12‑13)
Ask about the CRSC
Get cited, plain-English answers on the California Referenced Standards Code for your project — any code section, any scenario.
Start Free TrialRelated in the CRSC
Where are costs of inspection and enforcement addressed (reserved)?
How are testing laboratories approved for insulation testing?
Can the Commission order independent performance tests and use results for enforcement?
Testing, laboratory approval, inspections and performance testing
California Referenced Standards Code