CFC · California Fire Code
Where to find occupancy/location limits and exceptions for finish classes (Table 803.3)
Homeowner summary: The California Fire Code requires wall and ceiling finishes to meet the fire performance class (A, B or C) shown in Table 803.3 for each occupancy and location. The code tells you where to look (see § 803.3) and how to prove compliance — either by ASTM E84/UL723 class indices or by NFPA 286 testing that meets the acceptance criteria. If the table cell requires Class A, you must supply a Class A material or an NFPA 286 test report that meets the limits; also make sure the finish is properly attached per the stability rule in § 803.2. file
Last reviewed: July 6, 2026
What the code requires — plain English
The code requires that interior wall and ceiling finishes must meet the flame-spread/smoke performance specified for the occupancy and location shown in Table 803.3 — the table is the controlling map that tells you which finish Class (A, B or C) applies where. See § 803.3 for the controlling rule that ties finishes to Table 803.3 . Materials can be tested either by NFPA 286 or by ASTM E84/UL 723; NFPA 286 results that meet the acceptance criteria are treated as Class A where Class A is required (see § 803.1.1 and § 803.1.1.1) .
The single most important rule: interior wall and ceiling finishes must not exceed the flame-spread/smoke limits prescribed for the occupancy and location in Table 803.3 — compliance is verified by the test method and acceptance criteria specified in Chapter 8 (§ 803).
Requirements in detail
Where to look
- The mandatory instruction that finishes follow the table is in § 803.3 (see Table 803.3) — this is the immediate starting point for every finish decision. § 803.3 ties a required finish class to each occupancy/location pairing .
- Test methods and equivalent criteria are in § 803.1, § 803.1.1, § 803.1.1.1, and § 803.1.2 (NFPA 286 acceptance criteria and ASTM E84/UL 723 class definitions) .
- Stability (how finishes are fastened/must remain intact under elevated temp) is in § 803.2 .
- Specific material rules and exceptions are found in the related sections (e.g., § 803.1.3 through § 803.15 and Chapter 8 related sections such as § 806.6 for interior trim) — consult those for textile, foam, lockers, etc. file
Key, decision‑relevant values (summary table)
Note: the uploaded files did not include the printed contents of Table 803.3 itself. The table is referenced in § 803.3, but the actual table entries were not present in the documents provided. Below are the decision‑relevant performance thresholds and the rules you will use when you consult Table 803.3 in the official code.
| Decision dimension | What to look for / numeric value | Code Reference |
|---|---|---|
| Which table controls required finish class | Table 803.3 (use to find Class A/B/C by occupancy & location) | § 803.3 |
| Class A (ASTM E84/UL 723) | Flame spread index 0–25; smoke-developed 0–450 | § 803.1.2 |
| Class B (ASTM E84/UL 723) | Flame spread index 26–75; smoke-developed 0–450 | § 803.1.2 |
| Class C (ASTM E84/UL 723) | Flame spread index 76–200; smoke-developed 0–450 | § 803.1.2 |
| NFPA 286 acceptance (treated as Class A) — peak heat release | ≤ 800 kW peak heat release during the test | § 803.1.1.1 (4) |
| NFPA 286 acceptance — other limits | Flames not to spread to ceiling or sample outer extremity; no flashover; total smoke ≤ 1,000 m² | § 803.1.1.1 (1–3,5) |
| Stability (attachment) | Material must not readily detach when exposed to 200°F (93°C) for 30 minutes | § 803.2 |
| Special occupancy exhibit (trade shows) | Exhibit finishes: if building not fully sprinklered → Class A; if building fully sprinklered → Class B (see exhibit/display rules) | Appendix N, § N104.2 |
(Again: the exact occupancy × location matrix — e.g., "Group A corridors = Class A" — is contained in Table 803.3 itself. That printed table was not included in the uploaded files, so the specific row/column values must be read from the official Table 803.3 in the code.)
How to use the table in practice (step sequence)
- Identify the occupancy group and specific location (corridor, exit access, assembly area, patient room, storage, etc.). See Chapter 2/occupancy chapters for group definitions and Chapter 8 for locations referenced by the table. § 803.3 directs you to the table for the class assignment .
- Read the Table 803.3 cell for that occupancy/location — it will list required finish Class (A, B, or C) or a conditional requirement (e.g., Class B unless sprinklered). If the table cell requires Class A, then either an ASTM E84 Class A product or an NFPA 286 tested product that meets the acceptance criteria is acceptable per § 803.1.1 / § 803.1.1.1 .
- Confirm test reports (ASTM E84/UL 723 or NFPA 286) and attachment stability per § 803.2 .
- Check special sections (e.g., textile wall coverings, foam plastics, interior trim) described in § 803.1.3–§ 803.15 and § 806.6 for additional limits or exceptions file.
Exceptions & special cases
- NFPA 286 test results that meet the acceptance criteria are considered to be Class A for the purposes of Table 803.3 — see § 803.1.1 and § 803.1.1.1 (the NFPA 286 acceptance criteria) .
- The code contains a number of material‑specific provisions and exceptions (for textiles, special plenum finishes, foam plastics, interior trim, lockers, etc.) in § 803.1.3 through § 803.15 and § 806.x; consult those sections for exceptions that alter test method or allowed classification (uploaded snippets reference those sections but full text may be in the code book) file.
- For exhibit booths and trade shows, the finish requirement depends on sprinkler protection: non‑sprinklered exhibition areas require Class A finishes; sprinklered exhibition areas can permit Class B finishes — see § N104.2 (Appendix N) .
- Interior trim has its own rule: except for certain foam plastics, interior trim is limited in size and class per § 806.6 (e.g., combustible trim may be limited to 10% of the wall or ceiling area and must meet the specified class) — consult that section for specifics .
- If the table indicates different requirements based on whether a building is equipped with an automatic sprinkler system, the applicability and the sprinkler exception will be shown in Table 803.3; check the table cell for that condition (the table content itself is required to answer a specific occupancy+sprinkler question) — the controlling rule to consult is § 803.3 .
Common mistakes
- Assuming ASTM E84 results alone are always sufficient — the code allows NFPA 286 as an alternative and NFPA 286 may be required to demonstrate equivalence to Class A for some materials; read § 803.1.1 and § 803.1.1.1 for the acceptance criteria .
- Trying to apply a single class to an entire building without checking the location‑by‑location requirements in Table 803.3 (corridors, exits, assembly spaces, patient rooms often have different requirements) — § 803.3 mandates the table as the deciding authority .
- Not verifying attachment stability — a material that meets flame spread requirements may still be unacceptable if it is not properly fastened per § 803.2 .
- Misreading exhibit/display exceptions — Appendix N has special rules for trade shows (see § N104.2) that differ from the building‑wide requirements .
Worked example — step‑through (concrete scenario)
Scenario: You are finishing the interior walls and ceilings of a small restaurant (Group A, dining area, corridors and kitchen). You need to know whether a new wall panel product (ASTM E84 tested with flame spread index = 30, smoke-developed = 200) is acceptable.
- Identify occupancy/location: dining room and corridors in a Group A occupancy. Start at § 803.3 to find the Table 803.3 requirement for "Group A — dining/assembly" and "corridor" locations (the exact Class required is shown in Table 803.3) .
- Check the table cell: (because the actual Table 803.3 text was not available in the uploaded files, you must read Table 803.3 in the code to see whether the dining room and corridor require Class A or Class B/C, or whether sprinklering changes the requirement). The procedure is: if Table 803.3 requires Class A, then an ASTM E84 product with flame spread 30 (Class B per § 803.1.2) is NOT acceptable unless the product can instead be shown to meet NFPA 286 acceptance criteria (i.e., be tested under NFPA 286 and meet the limits in § 803.1.1.1) .
- If Table 803.3 requires Class B or allows Class B when sprinklered and the building is sprinklered, the ASTM E84 Class B product (flame spread index 30 → Class B) would be acceptable per § 803.1.2, subject to proper installation and stability per § 803.2 file.
- Always verify test reports and installation method; if NFPA 286 is used, confirm peak heat release ≤ 800 kW and total smoke ≤ 1,000 m² as required by § 803.1.1.1 .
(Important: because the Table 803.3 rows/columns were not included in the files you provided, the decisive step in this example — "what class does Table 803.3 require for Group A dining room/corridor" — must be read directly from Table 803.3 in the official code text. The procedural steps above show how you apply the table once you read the correct cell.)
Related provisions (quick list you should check)
- § 803.1 — General testing and classification approach (NFPA 286 vs ASTM E84/UL 723)
- § 803.1.1 — NFPA 286 classification and relationship to Class A
- § 803.1.1.1 — NFPA 286 acceptance criteria (flame spread to ceiling, flashover, heat‑release and smoke limits)
- § 803.1.2 — Class A/B/C numeric indices (ASTM E84/UL 723)
- § 803.2 — Stability/attachment requirements for finishes
- § 803.1.3 – § 803.15 — Material‑specific requirements and test method directions (textiles, foam plastics, etc.) — consult for exceptions
- § 806.6 — Interior trim limits (size and classification) and exceptions
- Appendix N (N104.1 / N104.2) — Trade shows and exhibitions (special finish rules depending on sprinkler protection)
Note on source material: The uploaded files include the CFC sections that define finish Classes, NFPA 286 acceptance criteria, the stability requirement, and the directive that finished materials must comply with Table 803.3 (see § 803.3) — those are cited above. The actual printed contents of Table 803.3 (the occupancy × location matrix listing the required Class for each cell) were not present among the uploaded files; to determine the precise Class for a specific occupancy/location you must consult the official Table 803.3 in the California Fire Code edition adopted for your project.
Code references
Grounded in the retrieved California Fire Code — click a citation to read the verbatim passage:
CFC § 104.3.1 Medium relevance — show source text
Alteration D103.1 Change of occupancy D103.2 Flood-resistant 104.3.1, Appendix G Historic 101.4.7
Relocated structures D103.3
Repairs 101.4.7, 116.5 Rodentproofing Appendix F Exit (see Means of Egress) 1022, 1023, 1024, 1025, 1026, 1027 Atrium 404.10, 1023.2 Boiler room 1006.2.1.1 Configuration 1007 Construction 713.2, 1019, 1023.2 Doorways 1007 Dwellings 1006.2.2.6, 1006.3.4.1 Electrical rooms 1006.2.2.4
Enclosure 707.3.2, 1023.2 Fire resistance 707.3, 1019, 1023.2
Furnace rooms 1006.2.2.1
Group H-5 415.11.6.6 High rise 403.5, 403.6, 1025 Horizontal 707.3.5, 1026 Incinerator rooms 1006.2.2.1
Interior finish Table 803.13, 804 Luminous 403.5.5, 411.4.1, 1008.2.1, 1013.5, 1025 Mall buildings 402.8 Number, minimum 402.8.3, 403.5,
1006
Occupant load 402.8.2, 1004.2, 1006.3.2
Passageway 707.3.4, 1024 Ramps, exterior 1027 Ramps, interior 1023 Refrigerated room 1006.2.2.2, 1006.2.2.3 Refuge area 407.5.3, 408.6.2, 420.6.1, 422.3.2
Stairways, exterior 1027 Stairways, interior 1023 Stories 1004.2.3, 1006.3, 1017.3.1 Travel distance 404.9, 407.5.2, 410.5.3.2, 412.6 Underground buildings 405.7 Exit Access (see Means of Egress) 1016, 1017, 1018, 1019, 1020, 1021 Aircraft related 412.2.2, 412.4.2,
412.7.3
Aisles 1018 Ambulatory care facilities 422.3 Atrium 404.10, 404.11, 404.9, 1006.3.2, 1017.3.2, 1019.3 Balconies 1017.2.1, 1021 Common path 1006.2.1 Corridors 1020
Doors 1005.7, 1006.2, 1007, 1010,
1022.2
Group H 415.11.3.3 Group I-2 407.4, 407.5.4 Group I-3 408.2, 408.3, 408.6.3 High rise 403.5 Higher education laboratories 428.3.5 Intervening space 1016.2 Malls 402.8
CFC § 803.1 Medium relevance — show source text
INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS
SECTION 803—INTERIOR WALL AND CEILING FINISH IN EXISTING BUILDINGS
803.1 General. The provisions of this section shall limit the allowable fire performance and smoke development of interior wall and ceiling finishes in existing buildings based on location and occupancy classification. Interior wall and ceiling finishes shall be classified in accordance with Section 803 of the California Building Code . Such materials shall be classified in accordance with NFPA 286, as indicated in Section 803.1.1, or in accordance with ASTM E84 or UL 723, as indicated in Section 803.1.2.
Materials tested in accordance with Section 803.1.1 shall not be required to be tested in accordance with Section 803.1.2.
803.1.1 Interior wall and ceiling finish materials tested in accordance with NFPA 286. Interior wall and ceiling finish materials shall be classified in accordance with NFPA 286 and tested in accordance with Section 803.1.1.1. Materials complying with Section 803.1.1.1 shall be considered to comply with the requirements of Class A specified in Section 803.1.2.
803.1.1.1 Acceptance criteria for NFPA 286. The interior finish shall comply with the following:
During the 40 kW exposure, flames shall not spread to the ceiling.
The flame shall not spread to the outer extremity of the sample on any wall or ceiling.
Flashover, as defined in NFPA 286, shall not occur.
The peak heat release rate throughout the test shall not exceed 800 kW.
The total smoke released throughout the test shall not exceed 1,000 m [2] .
803.1.2 Interior wall and ceiling finish materials tested in accordance with ASTM E84 or UL 723. Interior wall and ceiling finishes shall be classified in accordance with ASTM E84 or UL 723. Such interior finish materials shall be grouped in the following classes in accordance with their flame spread and smoke-developed indices: Class A: Flame spread index 0–25; smoke-developed index 0–450. Class B: Flame spread index 26–75; smoke-developed index 0–450. Class C: Flame spread index 76–200; smoke-developed index 0–450.
Exception: Materials tested in accordance with Section 803.1.1 and as indicated in Sections 803.1.3 through 803.15.
803.1.3 Interior wall and ceiling finish materials with specific requirements. The materials indicated in Sections 803.4 through 803.15 shall be tested as indicated in the corresponding sections.
803.2 Stability. Interior finish materials regulated by this chapter shall be applied or otherwise fastened in such a manner that such materials will not readily become detached where subjected to room temperatures of 200°F (93°C) for not less than 30 minutes.
803.3 Interior finish requirements based on occupancy. Interior wall and ceiling finish shall have a flame spread index not greater than that specified in Table 803.3 for the group and location designated. Interior wall and ceiling finish materials tested in accordance with NFPA 286, and meeting the acceptance criteria of Section 803.1.1.1, shall be used where a Class A classification in accordance with ASTM E84 or UL 723 is required.
|TABLE 803.
CFC § 150.0 Medium relevance — show source text
0, 150.0(k)|110.9, 130.0, 150.0(k)|110.9, 130.0, 150.0(k)|110.9, 130.0, 150.0(k)| |Single-family|Outdoor Lighting|110.9, 130.0, 150.0(k)|110.9, 130.0, 150.0(k)|110.9, 130.0, 150.0(k)|110.9, 130.0, 150.0(k)| |Single-family|Pool and Spa Systems|110.4, 150.0(p)|N.A.|N.A.|N.A.| |Single-family|Solar Ready Buildings|110.10|N.A.|N.A.|N.A.| |Single-family|Electric Ready|150.0(s), 150.0(t), 150.0(u),
150.0(v)|N.A.|N.A.|N.A.| |Single-family|Solar PV Systems|N.A.|150.0(c)14|150.1(a), (b)|N.A.| |Multifamily|General|160.0|170.2|170.1|180.0| |Multifamily|HVAC (conditioned)|110.6, 110.7, 110.8, 160.1|170.1(a)|170.1(a)|170.1(a)| |Multifamily|Ventilation and Indoor Air Quality|160.2|N.A.|N.A.|N.A.| |Multifamily|HVAC (conditioned)|110.2, 110.5, 160.3|170.2(c)|170.2(c)|170.2(c)| |Multifamily|Water Heating|110.3, 160.4|170.2(d)|170.2(d)|170.2(d)| |Multifamily|Indoor Lighting|110.9, 160.5|170.2(e)|170.2(e)|170.2(e)| |Multifamily|Outdoor Lighting|110.9, 160.5|170.2(e)|170.2(e)|170.2(e)| |Multifamily|Electrical Power Distribution|110.11, 160.6|N.A.|N.A.|N.A.| |Multifamily|Pool and Spa Systems|110.4, 110.5, 160.7|110.4, 110.5, 160.7|110.4, 110.5, 160.7|110.4, 110.5, 160.7| |Multifamily|Solar Ready Buildings|110.10, 160.8|110.10, 160.8|110.10, 160.8|110.10, 160.8| |Multifamily|Electric Ready|160.9|160.9|160.9|N.A.| |Multifamily|Solar PV and Battery Energy
Storage Systems|N.A.|170.2(f), (g), (h)|170.1|N.A.| |N.A. = Not Applicable
1.
Nonresidential and hotel/motel buildings that contain covered processes may conform to the applicable requirements of both occupancy types listed in this table.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1,Public Resources Code.CFC § 803.13 Medium relevance — show source text
Interior finishes Table 803.13, 804 Live load Table 1607.1 Means of egress Corridors 1020.3
Stairway, exit access 1019
Travel distance 407, 1006.3, 1017.2,
1006.2.1
Mixed occupancies 508.3, 508.4 Occupancy exceptions 303.1.1, 303.1.2, 308.5.1, 308.5.4, 310.4.1 Plumbing fixtures Chapter 29 Risk category Table 1604.5 Standby, emergency power 2702.2 Insulation
Concealed 720.2
Duct insulation 720.1
Exposed 720.3 Fiberboard 720.1, Table 1508.2, 2303.1.6.2, 2303.1.6.3 Foam plastic (see Foam Plastics) 720.1
Loose fill 720.4, 720.6 Pipe insulation 720.1, 720.7 Reflective plastic core 2614 Roof 720.5, 1508 Sound 720, 807, 1206 Thermal 720, 807, 1508 Interior Environment Lighting 1204 Rodentproofing Appendix F Sound transmission 1206
Space dimensions 1208 Temperature control 1203 Ventilation 409.3, 414.3, 415.9.1.7,
1202.5
Yards or courts 1205.2, 1205.3 Interior Finishes Chapter 8 Acoustical ceiling systems 807, 808 Application 803.13, 804.4 Atriums 404.8 Children’s play structures 424 Covered and open mall buildings 402.6
Decorative materials 419, 802.3, 806 Floor finish 804, 805 Foam plastic insulation 2603.3, 2603.4 Foam plastic trim 806.6.1, 2604.2 Insulation 807 Light-transmitting plastics 2606 Signs 402.6.4, 2611 Site-fabricated stretch systems 803.10 Trim 806.6, 806.7 Wall and ceiling finishes 803 Wet location 1210 Intermodal Shipping Container 3114 Interpretation, Code 104.1
Jails [see Institutional (see Group I-3)] 308.5, 408 Joint Gypsum board 2508.5 Lumber sheathing 2308.11.10 Waterproofing 1805.3.3 Joints, Fire-resistant Systems 715 Special inspection 1705.18
Kiosks 402.6.2
Kitchens 303.3, 306.2 Accessibility 1133A, 11B-212 Dimensions 1209 Means of egress 1016.2 Occupant load Table 1004.5 Sinks Chapter 29
INDEX-12 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
INDEX
Marquees 3106, H113 Construction 3106.5
CFC § 1006.3 Medium relevance — show source text
Exception: Where the area of the new occupancy is less than 10 percent of the building area. The cumulative effect of occupancy changes over time shall be considered.
[BS] 1006.3 Seismic loads. Where a change of occupancy results in a building being assigned to a higher risk category, or where the change is from a Group S or Group U occupancy to any occupancy other than Group S or Group U, the lateral force-resisting system of the building shall comply with Section 304.3.1 for the new risk category. Where a change of occupancy results in a building being assigned to Risk Category IV and Seismic Design Category D or F, nonstructural components serving any portion of the building changed to Risk Category IV shall comply with the requirements of Section 1613 of the California Building Code or shall comply with ASCE 41 using an objective of operational nonstructural performance with the BSE-1N earthquake hazard level.
Exceptions:
Where a change of use results in a building being reclassified from Risk Category I or II to Risk Category III and the seismic coefficient, S DS, is less than 0.33, compliance with this section is not required.
Where the area of the new occupancy is less than 10 percent of the building area, the occupancy is not changing from a Group S or Group U occupancy, and the new occupancy is not assigned to Risk Category IV, compliance with this section is not required. The cumulative effect of occupancy changes over time shall be considered.
Reserved.
Where the change is from a Group S or Group U occupancy and there is no change of risk category, compliance with Section 304.3.2 shall be permitted.
[BS] 1006.4 Access to Risk Category IV. Any structure that provides operational access to an adjacent structure assigned to Risk Category IV as the result of a change of occupancy shall itself comply with Sections 1608 and 1609 of the California Building Code and Section 304.3.1 of this code. Where operational access to Risk Category IV is less than 10 feet (3048 mm) from either an interior lot line or from another structure, access protection from potential falling debris shall be provided.
SECTION 1007—ELECTRICAL
1007.1 Special occupancies. Where the occupancy of an existing building or part of an existing building is changed to one of the following special occupancies as described in the California Electrical Code, the electrical wiring and equipment of the building or portion thereof that contains the proposed occupancy shall comply with the applicable requirements of the California Electrical Code :
Hazardous locations.
Commercial garages, repair and storage.
Aircraft hangars.
Gasoline dispensing and service stations.
Bulk storage plants.
Spray application, dipping and coating processes.
Reserved.
Places of assembly.
Theaters, audience areas of motion picture and television studios, and similar locations.
Motion picture and television studios and similar locations.
Motion picture projectors.
Agricultural buildings.
1007.2 Unsafe conditions. Where the occupancy of an existing building or part of an existing building is changed, all unsafe conditions shall be corrected without requiring that all parts of the electrical system comply with the California Electrical Code .
1007.3 Service upgrade. Where the occupancy of an existing building or part of an existing building is changed, electrical service shall be upgraded to meet the requirements of the California Electrical Code for the new occupancy.
CFC § 803.13 Medium relevance — show source text
1||X||||||||||||||||||||||| |Table 803.13|||X|||||||||||||||||||||| |804.1|||X|||||||||||||||||||||| |804.4|||X|||||||||||||||||||||| |804.4.1|||X|||||||||||||||||||||| |804.4.2|||X|||||||||||||||||||||| |804.4.3|||X|||||||||||||||||||||| |806.4|||X|||||||||||||||||||||| |806.6|||X||||||||||||||||||||||
The state agency does not adopt sections identified by the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.
2025 CALIFORNIA BUILDING CODE 8-1
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-2 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8 INTERIOR FINISHES
User notes:
About this chapter: Chapter 8 contains the performance requirements for controlling fire growth and smoke propagation within buildings by restricting interior finish and decorative materials. The provisions of this chapter require materials used as interior finishes and decorations to meet certain flame spread index or flame propagation criteria and smoke development criteria based on the relative fire hazard associated with the occupancy. The performance of the material is evaluated based on test standards.
SECTION 801—SCOPE
801.1 Scope. The provisions of this chapter shall govern the use of materials used as interior finishes, trim and decorative materials.
[BSC-CG] See California Green Building Standards Code, Chapter 5, Division 5.5 for additional finish material pollutant control requirements.
SECTION 802—GENERAL
802.1 Interior wall and ceiling finish. The provisions of Section 803 shall limit the allowable fire performance and smoke development of interior wall and ceiling finish materials based on occupancy classification.
802.2 Interior floor finish. The provisions of Section 804 shall limit the allowable fire performance of interior floor finish materials based on occupancy classification.
[F] 802.3 Decorative materials and trim. Decorative materials and trim shall be restricted by combustibility, fire performance or flame propagation performance criteria in accordance with Section 806.
802.4 Applicability. For buildings in flood hazard areas as established in Section 1612.3, interior finishes, trim and decorative materials below the elevation required by Section 1612 shall be flood-damage-resistant materials.
802.5 Application. Combustible materials shall be permitted to be used as finish for walls, ceilings, floors and other interior surfaces of buildings.
802.6 Windows. Show windows in the exterior walls of the first story above grade plane shall be permitted to be of wood or of unprotected metal framing.
802.7 Foam plastics. Foam plastics shall not be used as interior finish except as provided in Section 803.4. Foam plastics shall not be used as interior trim except as provided in Section 806.6.1 or 2604.2. This section shall apply both to exposed foam plastics and to foam plastics used in conjunction with a textile or vinyl facing or cover.
SECTION 803—WALL AND CEILING FINISHES
CFC § 404.2. Medium relevance — show source text
The locations and widths of exits and aisles.
The locations of exit signs.
The total square footage (square meters) of spaces.
The location and arrangement of all booths and cooking equipment.
The location of all fire protection equipment.
The type and location of any heating and electrical equipment, where applicable.
The location of any covered or multiple-level booths.
Construction documents for any covered or multiple-level booths.
The storage locations and quantities of any highly combustible goods.
The location and type of any vehicle displays, where applicable.
SECTION N102—DEFINITIONS
N102.1 Definitions. For the purpose of this appendix, certain terms are defined as follows:
COOKING. Heating food products to a temperature of 145°F (63°C) or higher by baking, braising, boiling, frying or grilling.
COVERED BOOTH. An exhibit that has an obstruction placed over the exhibit above floor level that resembles a roof, canopy, tent or other obstruction, other than vertical signs or banners.
MULTIPLE-LEVEL BOOTH. An exhibit that has a second level or tier constructed on top of the exhibit or portion of the exhibit that is open to the public, or includes a live load above the exhibit area floor level.
2025 CALIFORNIA FIRE CODE APPENDIX N-3
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX N—INDOOR TRADE SHOWS AND EXHIBITIONS
SECTION N103—PUBLIC SAFETY FOR EVENTS
N103.1 Fire safety and evacuation plan. A fire safety and evacuation plan shall be provided in accordance with Section 404.2.
Exception: Where the fire code official determines that the nature of the exhibition, display or the activities therein does not pose an increased hazard to public safety.
N103.2 Fire watch personnel. Where, in the opinion of the fire code official, it is essential for public safety in a trade show or exhibition, either because of the number or persons present or because of the nature of the performance, exhibition, display or activity, the owner or owner’s authorized agent shall provide one or more fire watch personnel in accordance with Section 403.11.1.
N103.3 Crowd managers. Where events involve a gathering of more than 1,000 people, trained crowd managers shall be provided in accordance with Section 403.11.3.
SECTION N104—INTERIOR FINISH AND DECORATIVE MATERIALS
N104.1 General. Interior finish, interior trim, furniture, furnishings and decorative materials, including decorative vegetation, used in exhibition areas shall comply with the requirements of this section and Chapter 8.
N104.2 Interior wall and ceiling finish. The materials used for interior wall and ceiling finish of exhibit booths and displays in exhibition areas shall comply with one of the following:
- Where the building is not equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, the wall and ceiling finish materials are required to be Class A in accordance with Section 803.
- Where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, the wall and ceiling finish materials are required to be not less than Class B in accordance with Section 803.
SECTION N105—MULTIPLE-LEVEL BOOTHS
CFC § 403.4.7 Medium relevance — show source text
Smoke exhaust 910 Smoke removal, high-rise buildings 403.4.7 Smokeproof enclosure 909.20.3, 909.20.5, 1023.12 Spray rooms and spaces 416.2.2, 416.3 Stages 410.2.5, 410.2.7 Under-floor ventilation 202.4 Vents, Penetration Protection 714 Vermiculite, Fire Resistant 721 Vertical Opening Protection Atriums 404.6
Duct penetrations 717.1 Elevators 713.14, 3007.6.1, 3008.6.1 Exceptions 1019, 1023.2 Group I-3 408.5 High-rise 403.2.1.2, 403.2.2, 403.5.1 Live/work units 508.5.6 Open parking garages 406.5.9 Permitted vertical openings 712 Shaft enclosure 713, 1019, 1023.2 Vestibules, Exit Discharge 1028.2 Vinyl Expanded 803.7, 803.8 Rigid 1404.15 Violations 114 Voice Alarm (see Alarms, Voice) Walkway 402.4.3.1, 3104 During construction 3306 Encroachment, public right-of-way 3202.3.4
Fire resistance Table 601
Live load Table 1607.1 Materials per construction type Chapter 6 Opening protection 716, 717, 1026.2 Wall, Exterior 705, 1401 Bearing Chapter 6
California Energy Code and International Energy Conservation Code Climate Zones 1404.3.3 Combustible wall covering 1405 Coverings 1404 Drawings 107.2.4 Exterior insulation and finish systems (EIFS) 1407 Exterior structural members 704.9
Fire district D102.2.6, D102.1 Fire-resistance ratings 703, 705.5, Table 705.5, 706.5.1, 707.4, 1402.4 Flashing, veneered walls 1404.11.1, 1404.4
Foam plastic insulation 2603.4.1.4, 2603.5 Glazing, rated 715.8 Joints 705.10, 714 Light-transmitting plastic panels 2607 Materials 705.4, 1403.1, 1405 Metal composite material (MCM) 1406 Nonbearing Chapter 6 Opening protection 705.11, 705.9, 716.2.5.4
Parapets 705.12 Performance requirements 1402 Projections 705.2 Structural stability 705.7 Vapor retarders 1404.3 Veneer (see Veneer) Weather resistance 1402.2, 1404.2, 1406.6, 1407.4 Weather-resistant barriers 1404.2 Wall, Fire (see Fire Walls) Wall, Foundation (see Foundations) Wall, Interior Finishes 803, 1210.2 Opening protection 716, 717 Wall, Interior Nonbearing (See Partitions) Wall, Masonry 202 Wood Contact 2304.12.1.3,
CFC § 802.1 Medium relevance — show source text
SECTION 802—DEFINITIONS
802.1 Definitions. The following terms are defined in Chapter 2:
FLAME SPREAD.
FLAME SPREAD INDEX.
INTERIOR FLOOR-WALL BASE.
SITE-FABRICATED STRETCH SYSTEM.
SMOKE-DEVELOPED INDEX.
[California Code of Regulations, Title 19, Division 1, §1191] Approved.
“Approved” means approved by the State Fire Marshal.
[California Code of Regulations, Title 19, Division 1, §1196] Flame-retardant Chemical.
“Flame-Retardant Chemical,” as used herein, means any chemical, chemical compound or chemical mixture which when properly applied to a fabric or material will render such fabric or material incapable of supporting combustion to the extent that it will success- fully withstand the tests and meet the specifications promulgated by the State Fire Marshal.
[California Code of Regulations, Title 19, Division 1, §1201] Nonflammable Material.
“Nonflammable Material,” as used herein, means a fabric or material which is inherently flame-resistant to the extent that it will meet the requirements of the fire resistance test herein prescribed, but shall not include materials which must be chemically treated or processed after manufacture to make them flame-resistant.
[California Code of Regulations, Title 19, Division 1, §1202] Place of Public Assemblage.
“Place of Public Assemblage,” as used herein, means any occupancy mentioned in Sections 13115 or 13119 of the Health and Safety Code.
2025 CALIFORNIA FIRE CODE 8-3
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS
SECTION 803—INTERIOR WALL AND CEILING FINISH IN EXISTING BUILDINGS
803.1 General. The provisions of this section shall limit the allowable fire performance and smoke development of interior wall and ceiling finishes in existing buildings based on location and occupancy classification. Interior wall and ceiling finishes shall be classified in accordance with Section 803 of the California Building Code . Such materials shall be classified in accordance with NFPA 286, as indicated in Section 803.1.1, or in accordance with ASTM E84 or UL 723, as indicated in Section 803.1.2.
Materials tested in accordance with Section 803.1.1 shall not be required to be tested in accordance with Section 803.1.2.
803.1.1 Interior wall and ceiling finish materials tested in accordance with NFPA 286. Interior wall and ceiling finish materials shall be classified in accordance with NFPA 286 and tested in accordance with Section 803.1.1.1. Materials complying with Section 803.1.1.1 shall be considered to comply with the requirements of Class A specified in Section 803.1.2.
803.1.1.1 Acceptance criteria for NFPA 286. The interior finish shall comply with the following:
During the 40 kW exposure, flames shall not spread to the ceiling.
The flame shall not spread to the outer extremity of the sample on any wall or ceiling.
Flashover, as defined in NFPA 286, shall not occur.
The peak heat release rate throughout the test shall not exceed 800 kW.
The total smoke released throughout the test shall not exceed 1,000 m [2] .
CFC § 105.2 Medium relevance — show source text
105.2 Bay and Oriel Windows 705.2.4, 1406.2,
1408.2 Public right-of-way encroachments 3202.3.2, 3202.3.3 Bleachers 303.6, 1030.1.1, 1030.17 Accessibility Chapter 11B Egress 1030.1.1, 1030.17 Live load 1607.18, Table 1607.1 Occupant load 1004.6 Separation 903.2.1.5.1, 1030.1.1.1 Block (see Concrete Block and Glass Unit Masonry) Board of Appeals 104.8, 113, Appendix B Alternate members B101.3.2 Application for appeal B101.1 Board decision B101.7
2025 CALIFORNIA BUILDING CODE INDEX-3
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
INDEX
Educational 303.1, 304.1 Live/work units 508.5 Mall buildings 402 Parking below/above 510.7, 510.8, 510.9
Special mixed 510.2 Occupancy exceptions 303.1.1, 303.1.2 Public fixtures Chapter 29 Risk category Table 1604.5 Sprinkler protection 903.2.2.1 Unlimited area 507.4, 507.5, 507.13
Cables, Steel Structural 2214 Calculated Fire Resistance (see Fire Resistance, Calculated) California Administration Chapter 1, Division I Canopies 706.5.2, 3105 Design and construction 3105.2 Drainage, water 3201.4 Encroachment, public right-ofway 3202.3.1 Fire district D102.2.8
Live load Table 1607.1, 1607.14.1 Materials 3105.3
Motor vehicle related 406.2.2, 406.7.2 Permanent 3105, D102.2.8 Plastic 2606.10 Capillary Break 1805.4.1, 1907.4.1 Carbon Monoxide Alarms and
Detection 915 Care Facilities (see Health Care) Care Provider Stations 407.2.2
Care Suites 407.4.4
Carpet 105.2 Floor covering 804.2, 804.3 Textile ceiling finish 803.6 Textile wall coverings 803.5 Catwalks (see Technical Production Areas) Construction 410.2.2
Live Load Table 1607.1 Means of egress 410.5, 1011.16 Sprinkler protection 410.6 Ceiling Acoustical 808 Height 406.2.2, 409.2, 1003.2, 1011.3, 1012.5.2, 1204.2.2, 1208.2 Interior finish 803
Penetration of fire-resistant assemblies
CFC § 1020.2 Medium relevance — show source text
Corridors 1020.2
Doors 1010.2.13, 1010.2.11, 1010.2.9, 1010.2.7, 1010.2.12.1 Lighting 1008.2, 1008.2.4 Stairway, exterior exit 1027.2 Stairways, exit access 1019 Travel distance 1006.3, 1017.2 Sprinkler protection 903.2.6, 903.3.2 Integrated Testing (Fire Protection and Life Safety Systems) 202, 901.6.2 Interconnection Fire-extinguishing systems with cooking appliances 904.14.2 Smoke alarms 907.2.11.5, 1103.8.2 Standpipe risers 905.4.2 Interior Finish Chapter 8 Defined 202
Interior Floor-Wall Base 804.4
Defined 202 Interior Wall and Ceiling Finish 803, 804 Defined 202 Interior Wall and Ceiling Finish and Trim 803, 804 Intumescent Fire-Resistant Materials 708 Investigations, Fire 104.10 Irritant
Defined 202
Gases 5004.7.1, 5307.1
Iso-Butane (see Liquefied Petroleum Gas)
Jurisdiction
Defined 202
Kettles [see Organic Coating or Asphalt (Tar) Kettles] Key Boxes 202, 506 Maintenance 506.2
Nonstandard fire service elevator keys 506.1.2 Required 506.1 Keys, Fire Service Elevator 604.6
Laboratory Suite 202 Ladders 1104.16.6, 5704.2.8.15 Boiler, incinerator and furnace rooms
1006.2.2.1
Construction 1011.15, 1011.16, 1014.2, 1014.7, 1015.3, 1015.4 Emergency escape window wells 1031.5.2
Group I-3 1011.15, 1011.16 Refrigeration machinery rooms 1006.2.2.2
Ship’s ladders 1011.15 Landing Ramps 1012.6, 1012.10 Stairs and stairways 1010.1.4, 1010.1.5, 1011.6, 1025.2.4 Landscaped Roofs (see also Rooftop Gardens) 317, 504.3, 905.3.7 Dead foliage 317.2.2 Irrigation 317.2.1 Maintenance equipment 317.4 Maintenance plan 317.3 Laundry Carts 318.1 Lead-Acid Battery System, Stationary (see Battery Systems, Stationary Storage) Lead-Acid Battery System, Valve-Regulated (see Battery Systems, Stationary Storage) Leaks Compressed gases 5303.12 Cryogenic fluids 5503.9 Explosive materials 5604.10 Flammable and combustible
CFC § 105.5.27 Medium relevance — show source text
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
INDEX
Fuel piping 3004 Interlocks 3005
Location 3003 Operation and maintenance 3007 Permit 105.5.27, 105.6.15 Inert Gas 2501.1, 2906.4, Table 5003.1.1(1), Table 5003.1.1(3), 5305.8, 5703.6.3.1,
5705.2.2
Defined 202 Inflatable Amusement Device 202, 3106 Inhabited Building Defined 202 Initiating Device Defined 202
Identification 907.6.3 Insecticidal Fogging (see Fumigation and Insecticidal Fogging) Inspection 104.7.2, 105.2.2, 109, 109.2.1,
901.6 Emergency and standby power system 1203.4 Fire department connections 912.7 Fire hydrant 507.5.2 Fireworks display 5608.5.3, 5608.9 Hose 3509.7
Magazines 5604.9 Masonry chimneys 605.2.1.1 Tents 3103.6 Institutional Occupancies (Group I) 203 Alarm and detection 907.2.10, 907.2.11.2, 907.2.6.1, 907.5.2.3.2 Means of egress Aisles 1018.5
Corridors 1020.2
Doors 1010.2.13, 1010.2.11, 1010.2.9, 1010.2.7, 1010.2.12.1 Lighting 1008.2, 1008.2.4 Stairway, exterior exit 1027.2 Stairways, exit access 1019 Travel distance 1006.3, 1017.2 Sprinkler protection 903.2.6, 903.3.2 Integrated Testing (Fire Protection and Life Safety Systems) 202, 901.6.2 Interconnection Fire-extinguishing systems with cooking appliances 904.14.2 Smoke alarms 907.2.11.5, 1103.8.2 Standpipe risers 905.4.2 Interior Finish Chapter 8 Defined 202
Interior Floor-Wall Base 804.4
Defined 202 Interior Wall and Ceiling Finish 803, 804 Defined 202 Interior Wall and Ceiling Finish and Trim 803, 804 Intumescent Fire-Resistant Materials 708 Investigations, Fire 104.10 Irritant
Defined 202
Gases 5004.7.1, 5307.1
Iso-Butane (see Liquefied Petroleum Gas)
Jurisdiction
Defined 202
Kettles [see Organic Coating or Asphalt (Tar) Kettles] Key Boxes 202, 506 Maintenance 506.2
Nonstandard fire service elevator keys 506.1.2 Required 506.1 Keys, Fire Service Elevator 604.6
CFC § 5.5 Medium relevance — show source text
[BSC-CG] See California Green Building Standards Code, Chapter 5, Division 5.5 for additional finish material pollutant control requirements.
SECTION 802—GENERAL
802.1 Interior wall and ceiling finish. The provisions of Section 803 shall limit the allowable fire performance and smoke development of interior wall and ceiling finish materials based on occupancy classification.
802.2 Interior floor finish. The provisions of Section 804 shall limit the allowable fire performance of interior floor finish materials based on occupancy classification.
[F] 802.3 Decorative materials and trim. Decorative materials and trim shall be restricted by combustibility, fire performance or flame propagation performance criteria in accordance with Section 806.
802.4 Applicability. For buildings in flood hazard areas as established in Section 1612.3, interior finishes, trim and decorative materials below the elevation required by Section 1612 shall be flood-damage-resistant materials.
802.5 Application. Combustible materials shall be permitted to be used as finish for walls, ceilings, floors and other interior surfaces of buildings.
802.6 Windows. Show windows in the exterior walls of the first story above grade plane shall be permitted to be of wood or of unprotected metal framing.
802.7 Foam plastics. Foam plastics shall not be used as interior finish except as provided in Section 803.4. Foam plastics shall not be used as interior trim except as provided in Section 806.6.1 or 2604.2. This section shall apply both to exposed foam plastics and to foam plastics used in conjunction with a textile or vinyl facing or cover.
SECTION 803—WALL AND CEILING FINISHES
803.1 General. Interior wall and ceiling finish materials shall be classified for fire performance and smoke development in accordance with Section 803.1.1 or 803.1.2, except as shown in Sections 803.1.3 through 803.15. Materials tested in accordance with Section 803.1.1 shall not be required to be tested in accordance with Section 803.1.2.
803.1.1 Interior wall and ceiling finish materials tested in accordance with NFPA 286. Interior wall and ceiling finish materials shall be classified in accordance with NFPA 286 and comply with Section 803.1.1.1. Materials complying with Section 803.1.1.1 shall be considered to also comply with the requirements of Class A.
803.1.1.1 Acceptance criteria for NFPA 286. The interior finish shall comply with the following:
During the 40 kW exposure, flames shall not spread to the ceiling.
The flame shall not spread to the outer extremity of the sample on any wall or ceiling.
Flashover, as defined in NFPA 286, shall not occur.
The peak heat release rate throughout the test shall not exceed 800 kW.
The total smoke released throughout the test shall not exceed 1,000 m [2] .
803.1.2 Interior wall and ceiling finish materials tested in accordance with ASTM E84 or UL 723. Interior wall and ceiling finish materials shall be classified in accordance with ASTM E84 or UL 723. Such interior finish materials shall be grouped in the following classes in accordance with their flame spread and smoke-developed indices.
Class A = Flame spread index 0–25; smoke-developed index 0–450.
Class B = Flame spread index 26–75; smoke developed index 0–450.
Class C = Flame spread index 76–200; smoke-developed index 0–450.
California Fire Code Medium relevance — show source text
800
14 600
13 600
12 700
12 000|25 600
23 600
22 000
20 600
19 500|52 700
48 500
45 100
42 300
40 000|95 700
88 100
81 900
76 900
72 600|152 000
139 000
130 000
122 000
115 000| |125
150
175
200
250|44
40
37
34
30|92
83
77
71
63|173
157
144
134
119|355
322
296
275
244|532
482
443
412
366|1020
928
854
794
704|1630
1480
1360
1270
1120|2890
2610
2410
2240
1980|5890
5330
4910
4560
4050|10 600
9650
8880
8260
7320|17 200
15 600
14 400
13 400
11 900|35 400
32 100
29 500
27 500
24 300|64 300
58 300
53 600
49 900
44 200|102 000
92 300
84 900
79 000
70 000| |300
350
400
450
500|27
25
23
22
21|57
53
49
46
43|108
99
92
86
82|221
203
189
177
168|331
305
283
266
251|638
587
546
512
484|1020
935
870
816
771|1800
1650
1540
1440
1360|3670
3370
3140
2940
2780|6630
6100
5680
5330
5030|10 700
9880
9190
8620
8150|22 100
20 300
18 900
17 700
16 700|40 100
36 900
34 300
32 200
30 400|63 400
58 400
54 300
50 900
48CFC § 6-3 Medium relevance — show source text
” Division 1, “Housing and Community](https://govt.westlaw.com/calregs/Document/I63FDC8F082C911E2BD79AA7206D382EB?viewType=FullText&originationContext=documenttoc&transitionType=CategoryPageItem&contextData=(sc.Default)) Development,” Chapter 2, “Mobilehome Parks and Installations,” Article 7, “MH-Unit and Commercial Modular Installations and Facilities,” Section 1333, “Foundation Systems.”
B. PG&E will make an exception and install utility services to a location where mobile homes may be moved, including mobile home parks, under certain, specific conditions.
The mobile homes must be served by meter pedestals or other PG&E-approved services and the meter facilities must be installed at a fixed location.
Applicants are responsible for connecting their mobile homes to those fixed locations and to the meter pedestals or other utility facilities.
See Numbered Document 052521, “Electrical Service Requirements for Mobile Home Developments,” for more information and for specifications. This PG&E document is included in Appendix C, “Electric and Gas Engineering Documents,” and also in PG&E’s Electric Underground Construction Manual, Book 1.
6-3 2022 – 2023
Section 6, Electric Metering: Residential
6.4. Services
6.4.1. Single Meter: Underground Service
A. Services, 0 Amps Through 225 Amps, Single Phase
Figure 6-1, “Typical Underground Service-Termination Enclosure, Combination Meter-Socket Panel (Residential, 0 Amps−225 Amps),” on Page 6-5, illustrates a single, underground, residential, single-phase meter panel (i.e., 4 terminal for a 120/240-volt service and 5 terminal for a 120/208-volt service).
CFC § 7-21 Medium relevance — show source text
713 Shaft Enclosures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21
714 Penetrations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-23
715 Joints and Voids . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-26
716 Opening Protectives . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-27
717 Ducts and Air Transfer Openings . . . . . . . . . . . . . . . . 7-34
718 Concealed Spaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-40
719 Fire-Resistance Requirements for Plaster . . . . . . . . 7-42
720 Thermal- and Sound-Insulating Materials . . . . . . . . 7-42
721 Prescriptive Fire Resistance. . . . . . . . . . . . . . . . . . . . . 7-43
722 Calculated Fire Resistance. . . . . . . . . . . . . . . . . . . . . . 7-66
CHAPTER 7A [SFM] MATERIALS AND CONSTRUCTION
METHODS FOR EXTERIOR WILDFIRE EXPOSURE . . . . . . . 7A-1
CHAPTER 8 INTERIOR FINISHES. . . . . . . . . . . . . . . . . . . . . .8-1
801 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
802 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
803 Wall and Ceiling Finishes . . . . . . . . . . . . . . . . . . . . . . . . 8-3
804 Interior Floor Finish . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
805 Combustible Materials in Types I and II Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-7
806 Decorative Materials and Trim . . . . . . . . . . . . . . . . . . . 8-7
807 Insulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-8
808 Acoustical Ceiling Systems . . . . . . . . . . . . . . . . . . . . . . 8-8
CHAPTER 9 FIRE PROTECTION AND LIFE
CFC § 806.6. Medium relevance — show source text
Exception: Interior trim materials that comply with Section 806.6.
[F] 806.8 Combustible lockers. Where lockers constructed of combustible materials are used, the lockers shall be considered to be interior finish and shall comply with Section 803.
Exception: Lockers constructed entirely of wood and noncombustible materials shall be permitted to be used wherever interior finish materials are required to meet a Class C classification in accordance with Section 803.1.2.
SECTION 807—INSULATION
807.1 Insulation. Thermal and acoustical insulation shall comply with Section 720.
SECTION 808—ACOUSTICAL CEILING SYSTEMS
808.1 Acoustical ceiling systems. The quality, design, fabrication and erection of metal suspension systems for acoustical tile and lay-in panel ceilings in buildings or structures shall conform to generally accepted engineering practice, the provisions of this chapter and other applicable requirements of this code.
808.1.1 Materials and installation. Acoustical materials complying with the interior finish requirements of Section 803 shall be installed in accordance with the manufacturer’s recommendations and applicable provisions for applying interior finish.
808.1.1.1 Suspended acoustical ceilings. Suspended acoustical ceiling systems shall be installed in accordance with the provisions of ASTM C635 and ASTM C636.
808.1.1.2 Fire-resistance-rated construction. Acoustical ceiling systems that are part of fire-resistance-rated construction shall be installed in the same manner used in the assembly tested and shall comply with the provisions of Chapter 7.
8-8 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
CALIFORNIA BUILDING CODE – MATRIX ADOPTION TABLE
CHAPTER 9 – FIRE PROTECTION AND LIFE SAFETY SYSTEMS
(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
CFC § 706.5.2 Medium relevance — show source text
Cables, Steel Structural 2214 Calculated Fire Resistance (see Fire Resistance, Calculated) California Administration Chapter 1, Division I Canopies 706.5.2, 3105 Design and construction 3105.2 Drainage, water 3201.4 Encroachment, public right-ofway 3202.3.1 Fire district D102.2.8
Live load Table 1607.1, 1607.14.1 Materials 3105.3
Motor vehicle related 406.2.2, 406.7.2 Permanent 3105, D102.2.8 Plastic 2606.10 Capillary Break 1805.4.1, 1907.4.1 Carbon Monoxide Alarms and
Detection 915 Care Facilities (see Health Care) Care Provider Stations 407.2.2
Care Suites 407.4.4
Carpet 105.2 Floor covering 804.2, 804.3 Textile ceiling finish 803.6 Textile wall coverings 803.5 Catwalks (see Technical Production Areas) Construction 410.2.2
Live Load Table 1607.1 Means of egress 410.5, 1011.16 Sprinkler protection 410.6 Ceiling Acoustical 808 Height 406.2.2, 409.2, 1003.2, 1011.3, 1012.5.2, 1204.2.2, 1208.2 Interior finish 803
Penetration of fire-resistant assemblies
713.4, 716.1.2.3, 716.3.4 Suspended acoustical 808.1.1, 2506.2.1 Ceiling Radiation Damper 202 Cellulose Nitrate Film 409.1, 903.2.5.3 Cement Plaster 2109.2.4.8.6
Ceramic Fiber Blanket 202
Ceramic Tile
Mortar 2103.2.3 Certificate of Compliance 202 Certificate of Occupancy 106.2, 111 Change of Occupancy 101.4.7, 111.1, 116.5, 3113.1.1, D103.2 Child Care (see Day Care) 305.2, 308.5, 452 Chimneys 202 Factory-built 718.2.5 Flashing 1503.5 Masonry 2111, 2112, 2113 Protection from adjacent construction 3307.1
Churches (see Religious Worship, Places of) Clay Roof Tile 1507.3, 1513 Testing 1504.3 Climate Zone 1202.3.1, Table 1202.3.1,
1404.3.3
Clinic
Hospital [see Institutional (Group I-2)] 308.2 Outpatient (see Ambulatory Care Facilities) 304.1, 422 Clinics [OSHPD 3] 1226 Application 1226.2 Definitions 1226.3
Frequently asked questions
Where is the binding statement that says "use Table 803.3"?
The controlling directive is in § 803.3: interior wall and ceiling finish shall have a flame spread index not greater than that specified in Table 803.3 for the group and location designated .
If a product is tested to NFPA 286 and passes, can it be used where Class A is required?
Yes. Materials tested and meeting the NFPA 286 acceptance criteria are considered to comply with Class A where Class A is required — see § 803.1.1 and § 803.1.1.1 .
What numeric flame‑spread ranges define Classes A/B/C?
Class A = flame spread 0–25; Class B = 26–75; Class C = 76–200 (smoke-developed indices must be ≤450 for these classifications) — see § 803.1.2 .
Does having sprinklers always let me use a lower finish class?
Not automatically — Table 803.3 may include conditional cells that reduce the required class when the building is equipped with an automatic sprinkler system, but you must read the specific table cell for that occupancy/location (the table is the authoritative source per § 803.3) .
Where are special rules for exhibit booths and trade shows?
See Appendix N — § N104.2 spells out that exhibit finishes are Class A when the building is not sprinklered, and can be Class B where the building is sprinklered throughout .
More in California Fire Code
- Administration and Definitions
- General Requirements and Emergency Planning
- Fire Service Features and Fire Department Access
- Referenced Standards and Adoptable Appendices (Chapter 80; Appendices A–Q)
- Fire and Smoke Protection Features (fire‑resistance, barriers)
- Interior Finish, Decorative Materials and Furnishings
- Fire Protection and Life‑Safety Systems (sprinklers, alarms, smoke control)
- Means of Egress (exit design and maintenance)
- Construction Requirements for Existing Buildings (retrofit rules)
- Energy Systems and Stationary Energy Storage (ESS)
- Special Occupancies and Operations (chapters 20–41, 48–49)
- Hazardous Materials — Storage, Use and Handling (Chapters 50–67)
Ask about the CFC
Get cited, plain-English answers on the California Fire Code for your project — any code section, any scenario.
Start Free TrialRelated in the CFC
What flame-spread and smoke development limits apply to interior wall and ceiling finishes in existing buildings?
When are fire‑retardant coatings permitted and how must they be maintained?
How must textile wall coverings be tested and classified?
What surfaces are considered ‘interior finish’ vs decorative materials?
Wall and Ceiling Finish — Existing Buildings
California Fire Code