CFC · California Fire Code

How do air‑transfer openings interact with smoke control systems and damper requirements?

If a duct or grille passes smoke between compartments, the California Fire Code requires it be protected and maintained (see **§ 706**) and, when a smoke control system is involved, be addressed in the smoke control design — typically with a **Class II, 250°F smoke damper** or an approved alternative that does not interfere with the smoke control operation (**§ 909**).

Last reviewed: July 6, 2026

What the code requires — plain English

  • Air‑transfer openings and ducts that penetrate fire- or smoke‑resistive construction must be protected and maintained; the California Fire Code’s § 706 governs maintenance and protection of those openings.
  • When a smoke control system is required or used, the CFC requires ducts and air‑transfer openings to be protected with a minimum Class II, 250°F (121°C) smoke damper complying with Section 717 of the Building Code; smoke control design (pressurization or airflow method) and pressure/commissioning requirements are in § 909.

The single most important rule: protect and maintain dampers (or approved alternatives) at any duct or air‑transfer opening that would otherwise allow smoke to move between smoke control zones; if a smoke control system is used, design the dampers and openings so they do not interfere with the smoke control strategy.

Requirements in detail

Basic CFC requirements (what the Fire Code itself mandates)

  • Maintenance — Dampers protecting ducts and air‑transfer openings must be inspected and maintained in accordance with NFPA 80 and NFPA 105 as required by § 706.1.
  • Unprotected openings — Any unprotected ducts or air‑transfer openings in fire‑resistance‑rated construction or smoke-resisting construction must be brought into compliance with the requirements in force when the building was constructed (repair/replace to restore protection), per § 706.2.

Smoke control (§ 909) — how openings interact with system design

  • Damper requirement for smoke control zones — CFC requires ducts and air‑transfer openings between smoke zones to be protected with a minimum Class II, 250°F smoke damper complying with CBC Section 717 (CFC § 909.5.3.2). This ties the Fire Code requirement to the damper types and ratings in the Building Code.
  • Primary control method — The primary mechanical method is pressurization (pressure difference across smoke barriers); the system must produce the minimum required pressure difference and account for leakage and openings as part of the design (see § 909.6, § 909.5).
  • Airflow (open) method allowed selectively — The airflow method (fixed permanent openings intentionally left open) is permitted only with an approved rational analysis and must meet NFPA 92 criteria; velocity toward the fire must not exceed 200 feet per minute (CFC § 909.7.1).
  • Commissioning, analysis and test — Smoke control systems require a rational analysis, special inspections, and commissioning per § 909.3 and § 909.4; design must account for stack/wind/temp effects and interactions with normal HVAC.

How this works in practice — when dampers vs. alternate protection apply

  • The CFC explicitly cross‑references the Building Code rules for which penetrations require fire or smoke dampers (see CBC Section 717). Where a smoke control system is provided and a damper would interfere with the system’s operation, the CFC requires use of an approved alternative or that the damper not be installed if the smoke control system performance makes the damper unnecessary (CFC § 909.5.3.2 and CBC § 717 exceptions).

Decision‑relevant thresholds and values (quick reference table)

Decision or value What the code specifies Code Reference
Damper type required for ducts/air‑transfer openings used with smoke control Minimum Class II, 250°F (121°C) smoke damper complying with CBC Section 717 § 909.5.3.2
Damper maintenance standard Inspect & maintain per NFPA 80 and NFPA 105 § 706.1
Pressurization minimum (sprinklered buildings) 0.05‑inch water gage across smoke barrier § 909.6.1
Airflow method limit toward fire 200 ft/min maximum toward fire (else prohibit) § 909.7.1
Detector proximity for damper actuation (CBC requirement referenced by CFC) Smoke detector inside or with sampling tube into duct within 5 ft of damper CBC § 717.3.3.2 (see CBC)
System duration of operation after fire detection Not less than 20 minutes or 1.5× calculated egress time, whichever greater § 909.4.6

(Notes: CFC § 909 requires dampers per CBC § 717; the CBC contains detailed damper ratings, actuation and access rules referenced above.)

Exceptions & special cases

  • If installing a smoke or fire damper would interfere with the operation of an approved smoke control system, the code allows the use of approved alternative protection or omission of the damper where justified (CFC § 909.5.3.2; CBC § 717 exceptions).
  • The airflow method (fixed permanent openings deliberately used in the smoke control design) is allowed only when specifically approved by the fire code official and designed per NFPA 92; it is prohibited where the airflow would impair other system functions or exceed velocity limits. § 909.7 lays out those limits.
  • Some thin‑gauge steel ducts and limited single‑compartment duct openings are treated as exceptions (CBC § 717 contains specific thickness/area limits); the CFC points to those CBC exceptions when they apply.

Common mistakes

  • Treating the damper requirement as optional because a smoke control system exists — the correct approach is to evaluate whether the damper would interfere with the smoke control operation; if so, use an approved alternative and document it in the rational analysis/commissioning. Do not assume a smoke control system automatically removes damper responsibilities without analysis.
  • Forgetting damper maintenance — CFC § 706.1 mandates NFPA‑based inspection/maintenance; missing or nonfunctional dampers defeat the smoke control strategy.
  • Designing pressurization without accounting for leakage/opening area — § 909 requires verification of leakage and that the system meet minimum pressure differences; ignoring leakage or door forces is a frequent design omission.
  • Using the airflow method without meeting NFPA 92 and the CFC velocity limits — the CFC prohibits airflow toward the fire greater than 200 ft/min.

Worked example — corridor smoke barrier with ducts

Scenario: A 10,000 ft² smoke compartment separated by a smoke barrier (wall area for leakage purposes = 1,500 ft²). The building is fully sprinklered. A supply duct penetrates the smoke barrier with an air‑transfer grille; the smoke control system uses pressurization.

  1. Damper requirement: CFC § 909.5.3.2 requires ducts/air‑transfer openings be protected with a Class II, 250°F smoke damper complying with CBC § 717 unless the damper would interfere with system operation and an approved alternative is used. You must therefore either provide the damper (and its detector within 5 ft per CBC § 717) or document why the damper would interfere and provide alternate protection.

  2. Pressure design: Minimum pressure difference across the smoke barrier (sprinklered building) per § 909.6.1 is 0.05 in. water gage. The system must be sized to overcome leakage; CFC § 909 leakage area ratios (walls A/Aw = 0.00100) let you compute maximum allowable leakage area = Aw × 0.00100 = 1,500 ft² × 0.001 = 1.5 ft² (≈216 in²). Use this when sizing fans and locating/limiting openings.

  3. Commissioning & documentation: The rational analysis required by § 909.4 must show the damper arrangement and prove that with the damper (or approved alternative) the system will maintain 0.05 in. wg across the barrier for the required duration (≥20 min or 1.5× egress time per § 909.4.6). Testing should be part of the special inspections and commissioning in § 909.3.

Related provisions (quick pointer list)

  • § 706.1 — Maintenance & inspection of dampers and protection for ducts/air transfer openings.
  • § 706.2 — Unprotected openings in fire‑ or smoke‑resisting construction.
  • § 909.3 — Special inspection and test (commissioning) requirements for smoke control systems.
  • § 909.4 — Rational analysis requirements for smoke control design.
  • § 909.5.3.2 — Ducts and air‑transfer openings must be protected with Class II 250°F smoke dampers (ties to CBC § 717).
  • CBC Section § 717 (Ducts & air transfer openings) — damper types, ratings, actuation, access and exceptions referenced by the CFC.

Code references

Grounded in the retrieved California Fire Code — click a citation to read the verbatim passage:

  • CFC § 0.019 High relevance — show source text

    Exceptions:

    1. Smoke dampers are not required where the building is equipped throughout with an approved smoke control system in accordance with Section 909, and smoke dampers are not necessary for the operation and control of the system.
    2. Smoke dampers are not required in corridor penetrations where the duct is constructed of steel not less than 0.019 inch (0.48 mm) in thickness and there are no openings serving the corridor.

    [SFM] For Group A, E, H, I, L and R occupancies, high-rise buildings, and other applications listed in Section 1.11 regulated by the Office of the State Fire Marshal, a listed smoke damper designed to resist the passage of smoke shall also be provided at each point a duct or air transfer opening penetrates a fire-resistance rated corridor enclosure required to have smoke and draft doors in accordance with Section 716.2.2.1 or doors that provide an effective barrier to limit the transfer of smoke in accordance with Section 407.3.1.

    Exceptions: 1. Smoke dampers are not required where ducts are used as part of an approved mechanical smoke control system designed in accordance with Section 909 and where the smoke damper will interfere with the operation of the smoke control system. 2. Smoke dampers are not required in corridor penetrations where the duct is constructed of steel not less than 0.019 inch (0.48 mm) in thickness and there are no openings serving the corridor. 717.5.5 Smoke barriers. A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a smoke barrier. Smoke dampers and smoke damper actuation methods shall comply with Section 717.3.3.2.

    Exception: Smoke dampers are not required where the openings in ducts are limited to a single smoke compartment and the ducts are constructed of steel. � 717.5.6 Exterior walls. Ducts and air transfer openings in fire-resistance-rated exterior walls required to have protected openings in accordance with Section 705.11 shall be protected with listed fire dampers installed in accordance with their listing.

    7-38 2025 CALIFORNIA BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FIRE AND SMOKE PROTECTION FEATURES

    717.5.7 Smoke partitions. A listed smoke damper designed to resist the passage of smoke shall be provided at each point that an air transfer opening penetrates a smoke partition. Smoke dampers and smoke damper actuation methods shall comply with Section 717.3.3.2.

    Exception: Where the installation of a smoke damper will interfere with the operation of a required smoke control system in accordance with Section 909, approved alternative protection shall be utilized.

    717.6 Horizontal assemblies. Penetrations by ducts and air transfer openings of a floor, floor/ceiling assembly or the ceiling membrane of a roof/ceiling assembly shall be protected by a shaft enclosure that complies with Section 713 or shall comply with Sections 717.6.1 through 717.6.3.

  • CFC § 717.5.1 High relevance — show source text

    717.5.1 Fire walls. Ducts and air transfer openings permitted in fire walls in accordance with Section 706.11 shall be protected with listed fire dampers installed in accordance with their listing.

    717.5.1.1 Horizontal exits. A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a fire wall that serves as a horizontal exit.

    717.5.2 Fire barriers. In other than Group A, E, H, I, L and R occupancies, high-rise buildings, and other applications listed in Section 1.11 regulated by the Office of the State Fire Marshal. Ducts and air transfer openings of fire barriers shall be protected with listed fire dampers installed in accordance with their listing. Ducts and air transfer openings shall not penetrate enclosures for interior exit stairways and ramps and exit passageways, except as permitted by Sections 1023.5 and 1024.6, respectively.

    Exceptions: Fire dampers are not required at penetrations of fire barriers where any of the following apply:

    1. Penetrations are tested in accordance with ASTM E119 or UL 263 as part of the fire-resistance-rated assembly.
    2. Ducts are used as part of an approved smoke control system in accordance with Section 909 and where the use of a fire damper would interfere with the operation of a smoke control system.
    3. Such walls are penetrated by fully ducted HVAC systems, have a required fire-resistance rating of 1 hour or less, are in areas of other than Group H and are in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. For the purposes of this exception, a fully ducted HVAC system shall be a duct system for conveying supply, return or exhaust air as part of the structure’s HVAC system. Such a duct system shall be constructed of sheet steel not less than No. 26 gage thickness and shall be continuous from the air-handling appliance or equipment to the air outlet and inlet terminals. Nonmetal flexible air connectors shall be permitted in the following locations in accordance with Section 603 of the California Mechanical Code: 3.1. At the duct connection to the air handling unit or equipment located within the mechanical room. 3.2. From an overhead metal duct to a ceiling diffuser within the same room.

    [SFM] For Group A, E, H, I, L and R occupancies, high-rise buildings, and other applications listed in Section 1.11 regulated by the Office of the State Fire Marshal, ducts and air transfer openings of fire barriers shall be protected with approved fire and smoke dampers installed in accordance with their listing. Ducts and air transfer openings shall not penetrate exit enclosures and exit passageways except as permitted by Sections 1023.5 and 1024.6, respectively.

    Exceptions: 1. Fire dampers are not required at penetrations of fire barriers where penetrations are tested in accordance with ASTM E119 as part of the fire-resistance rated assembly.

    7-36 2025 CALIFORNIA BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FIRE AND SMOKE PROTECTION FEATURES

  • CFC § 0.060 High relevance — show source text

    2. The sleeve shall be secured to both sides of the wall and for all four sides of the sleeve with minimum 1 [1] / 2 -inch by 1 [1] / 2 -inch by 0.060-inch (38 mm by 38 mm by 1.52 mm) steel retaining angles. 3. The retaining angles shall be secured to the sleeve and the wall with No. 10 (M5) screws. 4. The annular space between the steel sleeve and the wall opening shall be filled with mineral wool batting on all sides.

    717.5.4.1 Corridors. In other than Group A, E, H, I, L and R occupancies, high-rise buildings, and other applications listed in Section 1.11 regulated by the Office of the State Fire Marshal, duct and air transfer openings that penetrate corridors shall be protected with dampers as follows:

    1. A corridor damper shall be provided where corridor ceilings, constructed as required for the corridor walls as permitted in Section 708.4, Exception 3, are penetrated.
    2. A ceiling radiation damper shall be provided where the ceiling membrane of a fire-resistance-rated floor-ceiling or roof-ceiling assembly, constructed as permitted in Section 708.4, Exception 2, is penetrated.
    3. A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a corridor enclosure required to have smoke and draft control doors in accordance with Section 716.2.2.1.

    Exceptions:

    1. Smoke dampers are not required where the building is equipped throughout with an approved smoke control system in accordance with Section 909, and smoke dampers are not necessary for the operation and control of the system.
    2. Smoke dampers are not required in corridor penetrations where the duct is constructed of steel not less than 0.019 inch (0.48 mm) in thickness and there are no openings serving the corridor.

    [SFM] For Group A, E, H, I, L and R occupancies, high-rise buildings, and other applications listed in Section 1.11 regulated by the Office of the State Fire Marshal, a listed smoke damper designed to resist the passage of smoke shall also be provided at each point a duct or air transfer opening penetrates a fire-resistance rated corridor enclosure required to have smoke and draft doors in accordance with Section 716.2.2.1 or doors that provide an effective barrier to limit the transfer of smoke in accordance with Section 407.3.1.

    Exceptions: 1. Smoke dampers are not required where ducts are used as part of an approved mechanical smoke control system designed in accordance with Section 909 and where the smoke damper will interfere with the operation of the smoke control system. 2. Smoke dampers are not required in corridor penetrations where the duct is constructed of steel not less than 0.019 inch (0.48 mm) in thickness and there are no openings serving the corridor. 717.5.5 Smoke barriers. A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a smoke barrier. Smoke dampers and smoke damper actuation methods shall comply with Section 717.3.3.2.

  • CFC § 717.5.2.1 High relevance — show source text

    2. Fire and smoke dampers are not required where ducts are used as part of an approved smoke control system in accordance with Section 909 and where the use of a fire or smoke damper would interfere with the operation of a smoke control system.

    717.5.2.1 Horizontal exits. A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a fire barrier that serves as a horizontal exit.

    717.5.3 Shaft enclosures. Shaft enclosures that are permitted to be penetrated by ducts and air transfer openings shall be protected with listed fire and smoke dampers installed in accordance with their listing.

    Exceptions:

    1. Fire dampers are not required at penetrations of shafts where any of the following criteria are met: 1.1. Steel exhaust subducts having a wall thickness of not less than 0.0187 inch (0.4712 mm) are extended not less than 22 inches (559 mm) vertically in exhaust shafts, and an exhaust fan is installed at the upper terminus of the shaft that is powered continuously in accordance with Section 909.11, so as to maintain a continuous upward airflow to the outdoors. 1.2. Penetrations are tested in accordance with ASTM E119 or UL 263 as part of the fire-resistance-rated assembly. 1.3. Ducts are used as part of an approved smoke control system designed and installed in accordance with Section 909 and where the fire damper will interfere with the operation of the smoke control system. 1.4. The penetrations are in parking garage exhaust or supply shafts that are separated from other building shafts by not less than 2-hour fire-resistance-rated construction.
    2. In Group B and R occupancies equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, smoke dampers are not required at penetrations of shafts where all of the following criteria are met: 2.1. Kitchen, clothes dryer, bathroom and toilet room exhaust openings are installed with steel exhaust subducts, having a wall thickness of not less than 0.0187 inch (0.4712 mm). 2.2. The subducts extend not less than 22 inches (559 mm) vertically. 2.3. An exhaust fan is installed at the upper terminus of the shaft that is powered continuously in accordance with the provisions of Section 909.11, so as to maintain a continuous upward airflow to the outdoors.
    3. Smoke dampers are not required at penetration of exhaust or supply shafts in parking garages that are separated from other building shafts by not less than 2-hour fire-resistance-rated construction.
    4. Smoke dampers are not required at penetrations of shafts where ducts are used as part of an approved mechanical smoke control system designed in accordance with Section 909 and where the smoke damper will interfere with the operation of the smoke control system.
    5. Fire dampers and combination fire/smoke dampers are not required in kitchen and clothes dryer exhaust systems where dampers are prohibited by the California Mechanical Code .

    717.5.3.1 Continuous upward airflow. Fire dampers and smoke dampers shall not be installed in shafts that are required to maintain a continuous upward airflow path where closure of the damper would result in the loss of the airflow.

  • CFC § 909.5.3.2 High relevance — show source text

    909.5.3.2 Ducts and air transfer openings. Ducts and air transfer openings are required to be protected with a minimum Class II, 250°F (121°C) smoke damper complying with Section 717 of the California Building Code .

    909.6 Pressurization method. The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers. Maintenance of a tenable environment is not required in the smoke-control zone of fire origin.

    909.6.1 Minimum pressure difference. The pressure difference across a smoke barrier used to separate smoke zones shall be not less than 0.05-inch water gage (0.0124 kPa) in buildings equipped throughout with automatic sprinkler systems.

    In buildings permitted to be not equipped throughout with automatic sprinkler systems, the smoke control system shall be designed to achieve pressure differences not less than two times the maximum calculated pressure difference produced by the design fire.

    909.6.2 Maximum pressure difference. The maximum air pressure difference across a smoke barrier shall be determined by required door-opening or closing forces. The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 1010.1.3. Opening and closing forces for other doors shall be determined by standard engineering methods for the resolution of forces and reactions. The calculated force to set a side-hinged, swinging door in motion shall be determined by:

    Equation 9-1 F = F dc + K ( WA Δ P )/2( W - d )

    where:

    A = Door area, square feet (m [2] ).

    d = Distance from door handle to latch edge of door, feet (m).

    F = Total door opening force, pounds (N).

    F dc = Force required to overcome closing device, pounds (N).

    K = Coefficient 5.2 (1.0).

    W = Door width, feet (m).

    Δ P = Design pressure difference, inches of water (Pa).

    909.6.3 Pressurized stairways and elevator hoistways. Where stairways or elevator hoistways are pressurized, such pressurization systems shall comply with Section 909 as smoke control systems, in addition to the requirements of Sections 909.20 and 909.21.

    909.7 Airflow design method. Where approved by the fire code official, smoke migration through openings fixed in a permanently open position, which are located between smoke control zones by the use of the airflow method, shall be permitted. The design airflow shall be in accordance with this section. Airflow shall be directed to limit smoke migration from the fire zone. The geometry of openings shall be considered to prevent flow reversal from turbulent effects. Smoke control systems using the airflow method shall be designed in accordance with NFPA 92.

    909.7.1 Prohibited conditions. This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system, unduly intensify the fire, disrupt plume dynamics or interfere with exiting. Airflow toward the fire shall not exceed 200 feet per minute (1.02 m/s). Where the calculated airflow exceeds this limit, the airflow method shall not be used.

  • CFC § 717.3.3.5 High relevance — show source text

    717.3.3.5 Corridor damper actuation. Corridor damper actuation shall be in accordance with Sections 717.3.3.1 and 717.3.3.2.

    717.4 Access and identification. Access and identification of fire and smoke dampers shall comply with Sections 717.4.1 through 717.4.2.

    717.4.1 Access. Fire and smoke dampers shall be provided with an approved means of access that is large enough to permit inspection and maintenance of the damper and its operating parts. Dampers equipped with fusible links, internal operators, or both shall be provided with an access door that is not less than 12 inches (305 mm) square or provided with a removable duct section.

    717.4.1.1 Access openings. The access shall not affect the integrity of fire-resistance-rated assemblies. The access openings shall not reduce the fire-resistance rating of the assembly. Access doors in ducts shall be tight fitting and suitable for the required duct construction.

    717.4.1.2 Restricted access. Where space constraints or physical barriers restrict access to a damper for periodic inspection and testing, the damper shall be a single- or multi-blade type damper and shall comply with the remote inspection requirements of NFPA 80 or NFPA 105.

    717.4.2 Identification. Access points shall be permanently identified on the exterior by a label having letters not less than [1] / 2 inch (12.7 mm) in height reading: “FIRE/SMOKE DAMPER,” “SMOKE DAMPER” or “FIRE DAMPER.”

    717.5 Where required. Fire dampers, smoke dampers, combination fire/smoke dampers, ceiling radiation dampers and corridor dampers shall be provided at the locations prescribed in Sections 717.5.1 through 717.5.7 and 717.6. Where an assembly is required to have both fire dampers and smoke dampers, combination fire/smoke dampers or a fire damper and a smoke damper shall be provided.

    717.5.1 Fire walls. Ducts and air transfer openings permitted in fire walls in accordance with Section 706.11 shall be protected with listed fire dampers installed in accordance with their listing.

    717.5.1.1 Horizontal exits. A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a fire wall that serves as a horizontal exit.

    717.5.2 Fire barriers. In other than Group A, E, H, I, L and R occupancies, high-rise buildings, and other applications listed in Section 1.11 regulated by the Office of the State Fire Marshal. Ducts and air transfer openings of fire barriers shall be protected with listed fire dampers installed in accordance with their listing. Ducts and air transfer openings shall not penetrate enclosures for interior exit stairways and ramps and exit passageways, except as permitted by Sections 1023.5 and 1024.6, respectively.

    Exceptions: Fire dampers are not required at penetrations of fire barriers where any of the following apply:

    1. Penetrations are tested in accordance with ASTM E119 or UL 263 as part of the fire-resistance-rated assembly.
    2. Ducts are used as part of an approved smoke control system in accordance with Section 909 and where the use of a fire damper would interfere with the operation of a smoke control system.
  • CFC § 7-35 High relevance — show source text
    1. Where a smoke damper is installed above smoke barrier doors in a smoke barrier, a spot-type detector shall be installed on either side of the smoke barrier door opening. The detector shall be listed for releasing service if used for direct interface with the damper.
    2. Where a smoke damper is installed within an air transfer opening in a wall, a spot-type detector shall be installed within 5 feet (1524 mm) horizontally of the damper. The detector shall be listed for releasing service if used for direct interface with the damper.

    2025 CALIFORNIA BUILDING CODE 7-35

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FIRE AND SMOKE PROTECTION FEATURES

    1. Where a smoke damper is installed in a corridor wall or ceiling, the damper shall be permitted to be controlled by a smoke detection system installed in the corridor.
    2. Where a smoke detection system is installed in all areas served by the duct in which the damper will be located, the smoke dampers shall be permitted to be controlled by the smoke detection system.

    717.3.3.3 Combination fire/smoke damper actuation. Combination fire/smoke damper actuation shall be in accordance with Sections 717.3.3.1 and 717.3.3.2. Combination fire/smoke dampers installed in smoke control system shaft penetrations shall not be activated by local area smoke detection unless it is secondary to the smoke control system controls.

    717.3.3.4 Ceiling radiation damper actuation. The operating temperature of a ceiling radiation damper actuation device shall be 50°F (27.8°C) above the normal temperature within the duct system, but not less than 160°F (71°C).

    717.3.3.5 Corridor damper actuation. Corridor damper actuation shall be in accordance with Sections 717.3.3.1 and 717.3.3.2.

    717.4 Access and identification. Access and identification of fire and smoke dampers shall comply with Sections 717.4.1 through 717.4.2.

    717.4.1 Access. Fire and smoke dampers shall be provided with an approved means of access that is large enough to permit inspection and maintenance of the damper and its operating parts. Dampers equipped with fusible links, internal operators, or both shall be provided with an access door that is not less than 12 inches (305 mm) square or provided with a removable duct section.

    717.4.1.1 Access openings. The access shall not affect the integrity of fire-resistance-rated assemblies. The access openings shall not reduce the fire-resistance rating of the assembly. Access doors in ducts shall be tight fitting and suitable for the required duct construction.

    717.4.1.2 Restricted access. Where space constraints or physical barriers restrict access to a damper for periodic inspection and testing, the damper shall be a single- or multi-blade type damper and shall comply with the remote inspection requirements of NFPA 80 or NFPA 105.

    717.4.2 Identification. Access points shall be permanently identified on the exterior by a label having letters not less than [1] / 2 inch (12.7 mm) in height reading: “FIRE/SMOKE DAMPER,” “SMOKE DAMPER” or “FIRE DAMPER.”

  • CFC § 0.76 High relevance — show source text

    Combination fire/smoke dampers shall comply with the requirements of both UL 555 and UL 555S. 4. Ceiling radiation dampers shall comply with the requirements of UL 555C or shall be tested as part of a fire-resistancerated floor/ceiling or roof/ceiling assembly in accordance with ASTM E119 or UL 263. 5. Corridor dampers shall comply with requirements of both UL 555 and UL 555S. Corridor dampers shall demonstrate acceptable closure performance when subjected to 150 feet per minute (0.76 mps) velocity across the face of the damper during the UL 555 fire exposure test.

    717.3.2 Damper rating. Damper ratings shall be in accordance with Sections 717.3.2.1 through 717.3.2.4.

    717.3.2.1 Fire damper ratings. Fire dampers shall have the minimum rating specified in Table 717.3.2.1.

    TABLE 717.3.2.1—FIRE DAMPER RATING Col2
    TYPE OF PENETRATION MINIMUM DAMPER RATING (hours)
    Less than 3-hour fire-resistance-rated assemblies 1.5
    3-hour or greater fire-resistance-rated assemblies 3

    717.3.2.2 Smoke damper ratings. Smoke damper leakage ratings shall be Class I or II. Elevated temperature ratings shall be not less than 250°F (121°C).

    717.3.2.3 Combination fire/smoke damper ratings. Combination fire/smoke dampers shall have the minimum rating specified for fire dampers in Table 717.3.2.1 and shall have the minimum rating specified for smoke dampers in Section 717.3.2.2.

    717.3.2.4 Corridor damper ratings. Corridor dampers shall have the following minimum ratings:

    1. One-hour fire-resistance rating.
    2. Class I or II leakage rating as specified in Section 717.3.2.2.

    717.3.3 Damper actuation. Damper actuation shall be in accordance with Sections 717.3.3.1 through 717.3.3.5 as applicable.

    717.3.3.1 Fire damper actuation. Primary heat responsive devices used to actuate fire dampers shall meet one of the following requirements:

    1. The operating temperature shall be approximately 50°F (10°C) above the normal temperature within the duct system, but not less than 160°F (71°C).
    2. The operating temperature shall be not more than 350°F (177°C) where located in a smoke control system complying with Section 909.

    717.3.3.2 Smoke damper actuation. The smoke damper shall close upon actuation of a listed smoke detector or detectors installed in accordance with Section 907.3 and one of the following methods, as applicable:

    1. Where a smoke damper is installed within a duct, a smoke detector shall be installed inside the duct or outside the duct with sampling tubes protruding into the duct. The detector or tubes within the duct shall be within 5 feet (1524 mm) of the damper. Air outlets and inlets shall not be located between the detector or tubes and the damper. The detector shall be listed for the air velocity, temperature and humidity anticipated at the point where it is installed. Other than in mechanical smoke control systems, dampers shall be closed upon fan shutdown where local smoke detectors require a minimum velocity to operate.
  • CFC § 716.3.5.1 High relevance — show source text

    716.3.5.1 Fire window frames. Fire window frames shall be approved for the intended application.

    716.3.5.2 Labeling requirements. Fire-protection-rated glazing shall bear a label or other identification showing the name of the manufacturer, the test standard and information required in Section 716.1.2.2.2 and Table 716.1(3) that shall be issued by an approved agency and permanently identified on the glazing.

    716.3.6 Installation. Fire window assemblies shall be installed in accordance with the provisions of this section.

    716.3.6.1 Closure. Fire-protection-rated glazing shall be in the fixed position or be automatic-closing and shall be installed in labeled frames.

    716.4 Fire protective curtain assembly. Approved fire protective curtain assemblies shall be constructed of any materials or assembly of component materials tested without hose stream in accordance with UL 10D, and shall comply with the Sections 716.4.1 through 716.4.3.

    716.4.1 Label. Fire protective curtain assemblies used as opening protectives in fire-rated walls and smoke partitions shall be labeled in accordance with Section 716.2.9.

    716.4.2 Smoke and draft control. Fire protective curtain assemblies used to protect openings where smoke and draft control assemblies are required shall comply with Section 716.2.1.4.

    716.4.3 Installation. Fire protective curtain assemblies shall be installed in accordance with NFPA 80.

    SECTION 717—DUCTS AND AIR TRANSFER OPENINGS

    717.1 General. The provisions of this section shall govern the protection of duct penetrations and air transfer openings in assemblies required to be protected and duct penetrations in nonfire-resistance-rated floor assemblies.

    717.1.1 Ducts and air transfer openings. Ducts transitioning horizontally between shafts shall not require a shaft enclosure provided that the duct penetration into each associated shaft is protected with dampers complying with this section.

    717.1.2 Ducts that penetrate fire-resistance-rated assemblies without dampers. Ducts that penetrate fire-resistance-rated walls and are not required by this section to have fire dampers shall comply with the requirements of Sections 714.3 through 714.4.3. Ducts that penetrate horizontal assemblies not required to be contained within a shaft and not required by this section to have fire dampers shall comply with the requirements of Sections 714.5 through 714.6.2.

    717.1.2.1 Ducts that penetrate nonfire-resistance-rated assemblies. The space around a duct penetrating a nonfire-resistance-rated floor assembly shall comply with Section 717.6.3.

    717.2 Installation. Fire dampers, smoke dampers, combination fire/smoke dampers and ceiling radiation dampers located within air distribution and smoke control systems shall be installed in accordance with the manufacturer’s instructions, the dampers’ listing and Sections 717.2.1 through 717.2.4.

    717.2.1 Smoke control system. Where the installation of a fire damper will interfere with the operation of a required smoke control system in accordance with Section 909, approved alternative protection shall be utilized. Where mechanical systems including ducts and dampers utilized for normal building ventilation serve as part of the smoke control system, the expected performance of these systems in smoke control mode shall be addressed in the rational analysis required by Section 909.4.

  • CFC § 3.1. High relevance — show source text

    For the purposes of this exception, a fully ducted HVAC system shall be a duct system for conveying supply, return or exhaust air as part of the structure’s HVAC system. Such a duct system shall be constructed of sheet steel not less than No. 26 gage thickness and shall be continuous from the air-handling appliance or equipment to the air outlet and inlet terminals. Nonmetal flexible air connectors shall be permitted in the following locations in accordance with Section 603 of the California Mechanical Code: 3.1. At the duct connection to the air handling unit or equipment located within the mechanical room. 3.2. From an overhead metal duct to a ceiling diffuser within the same room.

    [SFM] For Group A, E, H, I, L and R occupancies, high-rise buildings, and other applications listed in Section 1.11 regulated by the Office of the State Fire Marshal, ducts and air transfer openings of fire barriers shall be protected with approved fire and smoke dampers installed in accordance with their listing. Ducts and air transfer openings shall not penetrate exit enclosures and exit passageways except as permitted by Sections 1023.5 and 1024.6, respectively.

    Exceptions: 1. Fire dampers are not required at penetrations of fire barriers where penetrations are tested in accordance with ASTM E119 as part of the fire-resistance rated assembly.

    7-36 2025 CALIFORNIA BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FIRE AND SMOKE PROTECTION FEATURES

    2. Fire and smoke dampers are not required where ducts are used as part of an approved smoke control system in accordance with Section 909 and where the use of a fire or smoke damper would interfere with the operation of a smoke control system.

    717.5.2.1 Horizontal exits. A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a fire barrier that serves as a horizontal exit.

    717.5.3 Shaft enclosures. Shaft enclosures that are permitted to be penetrated by ducts and air transfer openings shall be protected with listed fire and smoke dampers installed in accordance with their listing.

    Exceptions:

    1. Fire dampers are not required at penetrations of shafts where any of the following criteria are met: 1.1. Steel exhaust subducts having a wall thickness of not less than 0.0187 inch (0.4712 mm) are extended not less than 22 inches (559 mm) vertically in exhaust shafts, and an exhaust fan is installed at the upper terminus of the shaft that is powered continuously in accordance with Section 909.11, so as to maintain a continuous upward airflow to the outdoors. 1.2. Penetrations are tested in accordance with ASTM E119 or UL 263 as part of the fire-resistance-rated assembly. 1.3. Ducts are used as part of an approved smoke control system designed and installed in accordance with Section 909 and where the fire damper will interfere with the operation of the smoke control system. 1.4. The penetrations are in parking garage exhaust or supply shafts that are separated from other building shafts by not less than 2-hour fire-resistance-rated construction.
  • CFC § 717.5.6 High relevance — show source text

    Exception: Smoke dampers are not required where the openings in ducts are limited to a single smoke compartment and the ducts are constructed of steel. � 717.5.6 Exterior walls. Ducts and air transfer openings in fire-resistance-rated exterior walls required to have protected openings in accordance with Section 705.11 shall be protected with listed fire dampers installed in accordance with their listing.

    7-38 2025 CALIFORNIA BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FIRE AND SMOKE PROTECTION FEATURES

    717.5.7 Smoke partitions. A listed smoke damper designed to resist the passage of smoke shall be provided at each point that an air transfer opening penetrates a smoke partition. Smoke dampers and smoke damper actuation methods shall comply with Section 717.3.3.2.

    Exception: Where the installation of a smoke damper will interfere with the operation of a required smoke control system in accordance with Section 909, approved alternative protection shall be utilized.

    717.6 Horizontal assemblies. Penetrations by ducts and air transfer openings of a floor, floor/ceiling assembly or the ceiling membrane of a roof/ceiling assembly shall be protected by a shaft enclosure that complies with Section 713 or shall comply with Sections 717.6.1 through 717.6.3.

    717.6.1 Through penetrations. A duct constructed of approved materials in accordance with the California Mechanical Code that penetrates a fire-resistance-rated floor/ceiling assembly that connects not more than two stories is permitted without shaft enclosure protection, provided that a listed fire damper is installed at the floor line or the duct is protected in accordance with Section 714.5. For air transfer openings, see Section 712.1.9.

    Exception: In occupancies other than Groups I-2 and I-3, a duct is permitted to penetrate three floors or less without a fire damper at each floor, provided that such duct meets all of the following requirements:

    1. The duct shall be contained and located within the cavity of a wall and shall be constructed of steel having a minimum wall thickness of 0.0187 inches (0.4712 mm) (No. 26 gage).
    2. The duct shall open into only one dwelling unit or sleeping unit and the duct system shall be continuous from the unit to the exterior of the building.
    3. The duct shall not exceed 4-inch (102 mm) nominal diameter and the total area of such ducts shall not exceed 100 square inches (0.065 m [2] ) in any 100 square feet (9.3 m [2] ) of floor area.
    4. The annular space around the duct is protected with materials that prevent the passage of flame and hot gases sufficient to ignite cotton waste where subjected to ASTM E119 or UL 263 time-temperature conditions under a minimum positive pressure differential of 0.01 inch of water (2.49 Pa) at the location of the penetration for the time period equivalent to the fire-resistance rating of the construction penetrated.
    5. Grille openings located in a ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assembly shall be protected with a listed ceiling radiation damper installed in accordance with Section 717.6.2.1.
  • CFC § 909.5.2 High relevance — show source text

    [F] 909.5.2 Testing of leakage area. Compliance with the maximum total leakage area shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems utilizing the pressurization method. Compliance with the maximum total leakage area of passive smoke control systems shall be verified through methods such as door fan testing or other methods, as approved by the fire code official.

    [F] 909.5.3 Opening protection. Openings in smoke barriers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system. Door openings shall be protected by fire door assemblies complying with Section 716.

    Exceptions:

    1. Passive smoke control systems with automatic-closing devices actuated by spot-type smoke detectors listed for releasing service installed in accordance with Section 907.3. When used in Group I-2, such detectors shall activate the fire alarm system and shall close all the smoke barrier doors within the effected zone.

    2. Fixed openings between smoke zones that are protected utilizing the airflow method in other than Group I-2.

    3. In Group I-2, R-2.1 and ambulatory care facilities, where a pair of opposite-swinging doors are installed across a corridor in accordance with Section 909.5.3.1, the doors shall be protected in accordance with Section 716. The doors shall not have a center mullion. Positive-latching devices are required. Doors installed across corridors shall comply with Section 1010.1.1.

    4. In Group I-2, R-2.1 and ambulatory care facilities, where such doors are special-purpose horizontal sliding, accordion or folding door assemblies installed in accordance with Section 1010.3.3 and are automatic closing by smoke detection in accordance with Section 716.2.6.6, they shall be protected in accordance with Section 716. Doors installed across corridors shall comply with Section 1010.1.1.

    5. Group I-3.

    6. Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size. 7. In Group I-2, smoke damper activation may be accomplished by a fire alarm control unit provided that an open area smoke detection system is provided within all areas served by an HVAC system.

    [F] 909.5.3.1 Group I-2, R-2.1 and ambulatory care facilities. In Group I-2, R-2.1 and ambulatory care facilities, where doors are installed across a corridor, the doors shall be automatic closing by smoke detection in accordance with Section 716.2.6.5 and shall have a vision panel with fire-protection-rated glazing materials in fire protection-rated frames, the area of which shall not exceed that tested. Vision panels consisting of fire-rated glazing in approved frames shall be provided in each cross-corridor swinging door and at each cross-corridor horizontal-sliding door in a smoke barrier. In Group I-2, where swinging doors are installed across a corridor, such doors shall be opposite swinging pairs.

    [F] 909.5.3.2 Ducts and air transfer openings. Ducts and air transfer openings are required to be protected with a minimum Class II, 250°F (121°C) smoke damper complying with Section 717.

  • CFC § 717.1.1 High relevance — show source text

    717.1.1 Ducts and air transfer openings. Ducts transitioning horizontally between shafts shall not require a shaft enclosure provided that the duct penetration into each associated shaft is protected with dampers complying with this section.

    717.1.2 Ducts that penetrate fire-resistance-rated assemblies without dampers. Ducts that penetrate fire-resistance-rated walls and are not required by this section to have fire dampers shall comply with the requirements of Sections 714.3 through 714.4.3. Ducts that penetrate horizontal assemblies not required to be contained within a shaft and not required by this section to have fire dampers shall comply with the requirements of Sections 714.5 through 714.6.2.

    717.1.2.1 Ducts that penetrate nonfire-resistance-rated assemblies. The space around a duct penetrating a nonfire-resistance-rated floor assembly shall comply with Section 717.6.3.

    717.2 Installation. Fire dampers, smoke dampers, combination fire/smoke dampers and ceiling radiation dampers located within air distribution and smoke control systems shall be installed in accordance with the manufacturer’s instructions, the dampers’ listing and Sections 717.2.1 through 717.2.4.

    717.2.1 Smoke control system. Where the installation of a fire damper will interfere with the operation of a required smoke control system in accordance with Section 909, approved alternative protection shall be utilized. Where mechanical systems including ducts and dampers utilized for normal building ventilation serve as part of the smoke control system, the expected performance of these systems in smoke control mode shall be addressed in the rational analysis required by Section 909.4.

    717.2.2 Hazardous exhaust ducts. Fire dampers for hazardous exhaust duct systems shall comply with the California Mechanical Code .

    717.2.3 Static dampers. Fire dampers and ceiling radiation dampers that are listed for use in static systems shall only be installed in heating, ventilation and air-conditioning systems that are automatically shut down in the event of a fire.

    7-34 2025 CALIFORNIA BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FIRE AND SMOKE PROTECTION FEATURES

    717.2.4 Mechanical, electrical and plumbing controls. Mechanical, electrical and plumbing controls shall not be installed in air duct systems.

    Exception: Controls where the wiring is directly associated with the air distribution system. The wiring shall comply with the requirements of Section 601 of the California Mechanical Code and be as short as practicable.

    717.2.4.1 Controls not permitted to be installed through dampers. Mechanical, electrical and plumbing controls shall not be installed through fire dampers, smoke dampers, combination fire/smoke dampers or ceiling radiation dampers unless otherwise permitted by the manufacturer and the listing.

    717.3 Damper testing, ratings and actuation. Damper testing, ratings and actuation shall be in accordance with Sections 717.3.1 through 717.3.3.

    717.3.1 Damper testing. Dampers shall be listed and labeled in accordance with the standards in this section.

    1. Fire dampers shall comply with the requirements of UL 555.
    2. Smoke dampers shall comply with the requirements of UL 555S.
    3. Combination fire/smoke dampers shall comply with the requirements of both UL 555 and UL 555S.
  • CFC § 714.5.2 High relevance — show source text
    1. A shaft enclosure in accordance with Section 713.

    2. A listed ceiling radiation damper installed at the ceiling line where a duct penetrates the ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assembly. Exceptions:

    3. A fire-resistance-rated assembly tested in accordance with ASTM E119 or UL 263 showing that ceiling radiation dampers are not required in order to maintain the fire-resistance rating of the assembly.

    4. Where exhaust duct or outdoor air duct penetrations protected in accordance with Section 714.5.2 are located within the cavity of a wall and do not pass through another dwelling unit or tenant space.

    5. Where duct and air transfer openings are protected with a duct outlet penetration system tested as part of a fire-resistance-rated assembly in accordance with ASTM E119 or UL 263.

    6. A listed ceiling radiation damper installed at the ceiling line where a diffuser with no duct attached penetrates the ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assembly. Exceptions:

    7. A fire-resistance-rated assembly tested in accordance with ASTM E119 or UL 263 showing that ceiling radiation dampers are not required in order to maintain the fire-resistance rating of the assembly.

    8. Where duct and air transfer openings are protected with a duct outlet penetration system tested as part of a fire-resistance-rated assembly in accordance with ASTM E119 or UL 263.

    717.6.2.1 Ceiling radiation dampers testing and installation. Ceiling radiation dampers shall be tested in accordance with Section 717.3.1. Ceiling radiation dampers shall be installed in accordance with the details specified in the fire-resistance-rated assembly and the manufacturer’s instructions and the listing.

    717.6.2.1.1 Dynamic systems. Only ceiling radiation dampers labeled for use in dynamic systems shall be installed in heating, ventilation and air-conditioning systems designed to operate with fans on during a fire.

    717.6.2.1.2 Static systems. Static ceiling radiation dampers shall be provided with systems that are not designed to operate during a fire.

    Exceptions:

    1. Where a static ceiling radiation damper is installed at the opening of a duct, a smoke detector shall be installed inside the duct or outside the duct with sampling tubes protruding into the duct. The detector or tubes in the duct shall be within 5 feet (1524 mm) of the damper. Air outlets and inlets shall not be located between the detector or tubes and the damper. The detector shall be listed for the air velocity, temperature and humidity

    2025 CALIFORNIA BUILDING CODE 7-39

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FIRE AND SMOKE PROTECTION FEATURES

    anticipated at the point where it is installed. Other than in mechanical smoke control systems, dampers shall be closed upon fan shutdown where local smoke detectors require a minimum velocity to operate. 2. Where a static ceiling radiation damper is installed in a ceiling, the ceiling radiation damper shall be permitted to be controlled by a smoke detection system installed in the same room or area as the ceiling radiation damper. 3. A static ceiling radiation damper shall be permitted to be installed in a room where an occupant sensor is provided within the room that will shut down the system.

    717.6.3 Nonfire-resistance-rated floor assemblies. Duct systems constructed of approved materials in accordance with the California Mechanical Code that penetrate nonfire-resistance-rated floor assemblies shall be protected by any of the following methods:

  • CFC § 606.2 Medium relevance — show source text

    606.2 Fire Dampers. Fire dampers shall comply with UL 555, and shall be installed in accordance with the manufacturer’s installation instructions where required by the building code. Fire dampers shall have been tested for closure under airflow conditions and shall be labeled for both maximum airflow permitted and direction of flow. Where more than one damper is installed at a point in a single air path, the entire airflow shall be assumed to be passing through the smallest damper area.

    Ductwork shall be connected to damper sleeves or assemblies in accordance with the fire damper manufacturer’s installation instructions.

    606.3 Ceiling Radiation Dampers. Ceiling radiation dampers shall comply with UL 555C or shall be tested as part of a fire-resistance-rated floor-ceiling or roof-ceiling assembly in accordance with ASTM E119 or UL 263, and shall be installed in accordance with the manufacturer’s installation instructions in the fire-resistive ceiling membrane of floorceiling and roof-ceiling assemblies where required by the building code. Fire dampers not meeting the temperature limitation of ceiling radiation dampers shall not be used as a substitute.

    606.4 Combination Fire/Smoke Dampers. Combination fire/smoke dampers shall comply with UL 555 and UL 555S and the requirements in Section 606.1 and Section 606.2.

    606.4.1 When the automatic activation of a smoke damper or a combination smoke-fire damper occurs, the HVAC system serving such dampers shall immediately shut down.

    Exceptions:

    (1) HVAC systems that are part of an engineered smoke evacuation system.

    (2) Where the automatic activation causes all the smoke dampers and combination smoke-fire dampers to close in the enclosed space having a common atmos- phere where openings are required to be protected.

    (3) Where analysis demonstrates shutoff would create a greater hazard.

    The HVAC system shall not be restarted again until all the dampers are reset and fully opened. 606.5 Corridor Dampers. Corridor dampers shall comply with the requirements of combination fire/smoke dampers in Section 606.4.

    606.6 Periodic Testing and Inspection. Testing and inspection of dampers shall be in accordance with the following:

    (1) Smoke dampers shall be tested in accordance with NFPA 105.

    (2) Fire dampers shall be tested in accordance with NFPA 80.

    (3) Combination fire/smoke dampers shall be tested in accordance with NFPA 80 and NFPA 105.

    606.7 Multiple Arrangements. Where size requires the use of multiple dampers, each damper shall be listed for use in multiple arrangements and installed in accordance with the manufacturer’s installation instructions.

    606.8 Access and Identification. Fire and smoke

    dampers shall be provided with an approved means of access large enough to allow inspection and maintenance of the damper and its operating parts. The access shall not affect the integrity of the fire-resistance-rated assembly. The access openings shall not reduce the fire-resistance rating of the assembly.

    Access shall not require the use of tools. Access doors in ducts shall be tight fitting and approved for the required duct construction. Access points shall be permanently identified on the exterior by a label with letters not less than [1] ⁄ 2 of an inch (12.7 mm) in height reading as one of the following:

    (1) Smoke Damper

    (2) Fire Damper

Frequently asked questions

Can I omit a smoke damper if my building has a smoke control system?

Only if the damper would interfere with the proper operation of an approved smoke control system and you provide an approved alternative or justify omission in the rational analysis/commissioning. The CFC requires protection unless it hinders system operation (§ 909.5.3.2).

How close must a smoke detector be to a damper?

Where the Building Code’s damper actuation requirements apply, a detector (or sampling tube) must be installed within 5 feet of a damper when the detector is used to actuate it (see CBC § 717 actuation rules referenced by the CFC).

What pressure difference must a pressurization smoke control system provide?

In buildings equipped throughout with sprinklers the minimum design pressure difference is 0.05‑inch water gage across the smoke barrier (CFC § 909.6.1).

Is periodic testing required?

Yes. Smoke control systems and smoke removal equipment require special inspections and testing/commissioning per § 909.3; dampers must be inspected and maintained per § 706.1 (NFPA 80 / 105).

When is the airflow (open) method allowed for fixed openings?

The airflow method is allowed only with fire code official approval, a design per NFPA 92, and provided the airflow toward the fire does not exceed 200 ft/min and does not adversely affect other system performance (§ 909.7 / § 909.7.1).

More in California Fire Code

Ask about the CFC

Get cited, plain-English answers on the California Fire Code for your project — any code section, any scenario.

Start Free Trial

Related in the CFC