CFC · California Fire Code

Commissioning, Decommissioning, Retrofits & O&M

This hub explains where and how the California Fire Code requires commissioning, decommissioning, retrofits and O&M—primarily in Chapter 12 (§1207.2) and related maintenance sections.

Last reviewed: July 6, 2026

Overview

This topic groups the California Fire Code (CFC) requirements that govern how fire- and life‑safety systems — and in particular energy systems such as energy storage systems (ESS) — are brought into service, modified, maintained, and removed. Chapter 12 (Energy Systems) establishes the scope for installations, retrofits, testing, commissioning and decommissioning of energy systems (see §1201.1 and Chapter 12 overview) .

The CFC spells out specific deliverables and processes: approved commissioning plans, initial acceptance testing and commissioning reports before final approval (§1207.2.1 and §1207.2.1.1–.1.2); written operation & maintenance manuals and ongoing inspection/testing requirements (§1207.2.2 and §1207.2.2.1); and decommissioning plans with required notifications and contingencies (§1207.2.3) — requirements that are central for ESS safety and fire remediation planning . Commissioning practices and plan elements used for building systems are also reflected in CALGreen guidance on commissioning, OPR/BOD documentation and training expectations . Routine inspection, testing and maintenance of fire protection equipment is reinforced elsewhere in the code (see §901.6 and related CCR Title 19 provisions) .

In this section

Code references

Grounded in the retrieved California Fire Code — click a citation to read the verbatim passage:

  • CFC § 1207.2 High relevance — show source text

    1207.2 Commissioning, decommissioning, operation and maintenance. Commissioning, decommissioning, operation and maintenance shall be conducted in accordance with this section.

    1207.2.1 Commissioning. Commissioning of newly installed ESS and existing ESS that have been retrofitted, replaced or previously decommissioned and are returning to service shall be conducted prior to the ESS being placed in service in accordance with a commissioning plan that has been approved prior to initiating commissioning. The commissioning plan shall include the following:

    1. A narrative description of the activities that will be accomplished during each phase of commissioning, including the personnel intended to accomplish each of the activities.
    2. A listing of the specific ESS and associated components, controls and safety-related devices to be tested, a description of the tests to be performed and the functions to be tested.
    3. Conditions under which all testing will be performed, which are representative of the conditions during normal operation of the system.
    4. Documentation of the owner’s project requirements and the basis of design necessary to understand the installation and operation of the ESS.
    5. Verification that required equipment and systems are installed in accordance with the approved plans and specifications.
    6. Integrated testing for all fire and safety systems.
    7. Testing for any required thermal management, ventilation or exhaust systems associated with the ESS installation.
    8. Preparation and delivery of operation and maintenance documentation.
    9. Training of facility operating and maintenance staff.
    10. Identification and documentation of the requirements for maintaining system performance to meet the original design intent during the operation phase.
    11. Identification and documentation of personnel who are qualified to service, maintain and decommission the ESS, and respond to incidents involving the ESS, including documentation that such service has been contracted for./p>
    12. A decommissioning plan for removing the ESS from service, and from the facility in which it is located. The plan shall include details on providing a safe, orderly shutdown of energy storage and safety systems with notification to the code officials prior to the actual decommissioning of the system. The decommissioning plan shall include contingencies for removing an intact operational ESS from service, and for removing an ESS from service that has been damaged by a fire or other event.

    Exceptions:

    1. Commissioning shall not be required for lead-acid and nickel-cadmium battery systems at facilities under the exclusive control of communications utilities that comply with NFPA 76 and operate at less than 50 VAC and 60 VDC. A decommissioning plan shall be provided and maintained where required by the fire code official.
    2. Lead-acid and nickel-cadmium battery systems less than 50 VAC, 60 VDC that are in telecommunications facilities for installations of communications equipment under the exclusive control of communications utilities, and are located outdoors or in building spaces or walk-in units used exclusively for such installations that are in compliance with NFPA 76, shall be permitted to have a commissioning plan in compliance with recognized industry practices in lieu of complying with Section 1207.2.1.
    3. Lead-acid and nickel-cadmium battery systems that are used for DC power for control of substations and control or safe shutdown of generating stations under the exclusive control of the electric utilities, and are located in building spaces or walk-in units used exclusively for such installations, shall be permitted to have a commissioning plan in compliance with applicable governmental laws and regulations in lieu of developing a commissioning plan in accordance with Section 1207.2.1. (Material based on NFPA 855 2023 Ed.)
  • CFC § 12-11 High relevance — show source text

    2025 CALIFORNIA FIRE CODE 12-11

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    ENERGY SYSTEMS

    1207.1.8 Fire remediation. Where a fire or other event has damaged the ESS and ignition or re-ignition of the ESS is possible, the system owner, agent or lessee shall take the following actions, at their expense, to mitigate the hazard or remove damaged equipment from the premises to a safe location.

    1207.1.8.1 Fire mitigation personnel. Where, in the opinion of the fire code official, it is essential for public safety that trained personnel be on-site to respond to possible ignition or re-ignition of a damaged ESS, the system owner, agent or lessee shall dispatch within 15 minutes one or more fire mitigation personnel to the premise, as required and approved, at their expense. These personnel shall remain on duty continuously after the fire department leaves the premise until the damaged energy storage equipment is removed from the premises, or earlier if the fire code official indicates the public safety hazard has been abated. (Material based on NFPA 855 2023 Ed.)

    1207.1.8.2 Duties. On-duty fire mitigation personnel shall have the following responsibilities:

    1. Keep a diligent watch for fires, obstructions to means of egress and other hazards.

    2. Immediately contact the fire department if their assistance is needed to mitigate any hazards or extinguish fires.

    3. Take prompt measures for remediation of hazards in accordance with the decommissioning plan per Section 1207.2.3.

    4. Take prompt measures to assist in the evacuation of the public from the structures. (Material based on NFPA 855 2023 Ed.)

    1207.2 Commissioning, decommissioning, operation and maintenance. Commissioning, decommissioning, operation and maintenance shall be conducted in accordance with this section.

    1207.2.1 Commissioning. Commissioning of newly installed ESS and existing ESS that have been retrofitted, replaced or previously decommissioned and are returning to service shall be conducted prior to the ESS being placed in service in accordance with a commissioning plan that has been approved prior to initiating commissioning. The commissioning plan shall include the following:

    1. A narrative description of the activities that will be accomplished during each phase of commissioning, including the personnel intended to accomplish each of the activities.
    2. A listing of the specific ESS and associated components, controls and safety-related devices to be tested, a description of the tests to be performed and the functions to be tested.
    3. Conditions under which all testing will be performed, which are representative of the conditions during normal operation of the system.
    4. Documentation of the owner’s project requirements and the basis of design necessary to understand the installation and operation of the ESS.
    5. Verification that required equipment and systems are installed in accordance with the approved plans and specifications.
    6. Integrated testing for all fire and safety systems.
    7. Testing for any required thermal management, ventilation or exhaust systems associated with the ESS installation.
    8. Preparation and delivery of operation and maintenance documentation.
    9. Training of facility operating and maintenance staff.
    10. Identification and documentation of the requirements for maintaining system performance to meet the original design intent during the operation phase.
    11. Identification and documentation of personnel who are qualified to service, maintain and decommission the ESS, and respond to incidents involving the ESS, including documentation that such service has been contracted for./p>
  • CFC § 1207.2.1.1 High relevance — show source text

    (Material based on NFPA 855 2023 Ed.)

    1207.2.1.1 Initial acceptance testing. During the commissioning process an ESS shall be evaluated for proper operation in accordance with the manufacturer’s instructions and the commissioning plan prior to final approval.

    12-12 2025 CALIFORNIA FIRE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    ENERGY SYSTEMS

    1207.2.1.2 Commissioning report. A report describing the results of the system commissioning, including the results of the initial acceptance testing required in Section 1207.2.1.1, shall be provided to the fire code official prior to final inspection and approval and maintained at an approved on-site location. (Material based on NFPA 855 2023 Ed.)

    1207.2.2 Operation and maintenance. An operation and maintenance manual shall be provided to both the ESS owner or their authorized agent and the ESS operator before the ESS is put into operation and shall include the following:

    1. Manufacturer’s operation manuals and maintenance manuals for the entire ESS, or for each component of the system requiring maintenance, that clearly identify the required routine maintenance actions.
    2. Name, address and phone number of a service agency that has been contracted to service the ESS and its associated safety systems.
    3. Maintenance and calibration information, including wiring diagrams, control drawings, schematics, system programming instructions and control sequence descriptions, for all energy storage control systems.
    4. Desired or field-determined control set points that are permanently recorded on control drawings at control devices or, for digital control systems, in system programming instructions.
    5. A schedule for inspecting and recalibrating all ESS controls.
    6. A service record log form that lists the schedule for all required servicing and maintenance actions and space for logging such actions that are completed over time and retained on-site.

    The ESS shall be operated and maintained in accordance with the manual and a copy of the manual shall be retained at an approved on-site location.

    1207.2.2.1 Ongoing inspection and testing. Systems that monitor and protect the ESS installation shall be inspected and tested in accordance with the manufacturer’s instructions and the operation and maintenance manual. Inspection and testing records shall be maintained in the operation and maintenance manual.

    1207.2.3 Decommissioning. The code official shall be notified prior to the decommissioning of an ESS. Decommissioning shall be performed in accordance with the decommissioning plan that includes the following:

    1. A narrative description of the activities to be accomplished for removing the ESS from service, and from the facility in which it is located.

    2. A listing of any contingencies for removing an intact operational ESS from service, and for removing an ESS from service that has been damaged by a fire or other event. (Material based on NFPA 855 2023 Ed.)

    1207.3 Equipment. ESS equipment shall be in accordance with Sections 1207.3.1 through 1207.3.9.

    1207.3.1 Energy storage system listings. ESS shall be listed in accordance with UL 9540.

  • CFC § 5-26 High relevance — show source text

    5-26 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL MANDATORY MEASURES

    dance with this section by trained personnel with experience on projects of comparable size and complexity. For I-occupancies that are not regulated by OSHPD or for I-occupancies and L-occupancies that are not regulated by the California Energy Code Section 100.0 Scope, all requirements in Sections 5.410.2 through 5.410.2.6 shall apply.

    Note: For energy-related systems under the scope (Section 100) of the California Energy Code, including heating, ventilation, air conditioning (HVAC) systems and controls, indoor lighting systems and controls, as well as water heating systems and controls, refer to California Energy Code Section 120.8 for commissioning requirements.

    Commissioning requirements shall include:

    1. Owner’s or owner representative’s project requirements.
    2. Basis of design.
    3. Commissioning measures shown in the construction documents.
    4. Commissioning plan.
    5. Functional performance testing.
    6. Documentation and training.
    7. Commissioning report.

    Exceptions:

    1. Unconditioned warehouses of any size.

    2. Areas less than 10,000 square feet used for offices or other conditioned accessory spaces within unconditioned warehouses.

    3. Tenant improvements less than 10,000 square feet as described in Section 303.1.1.

    4. Open parking garages of any size, or open parking garage areas, of any size, within a structure.

    Note: For the purposes of this section, unconditioned shall mean a building, area or room which does not provide heating and/or air conditioning.

    Informational Note:

    1. Functional performance testing for heating, ventilation, air conditioning systems and lighting controls must be performed in compliance with the California Energy Code.

    5.410.2.1 Owner’s or Owner representative’s Project Requirements (OPR). [N] The expectations and requirements of the building appropriate to its phase shall be documented before the design phase of the project begins. This documentation shall include the following:

    1. Environmental and sustainability goals.
    2. Building sustainable goals.
    3. Indoor environmental quality requirements.
    4. Project program, including facility functions and hours of operation, and need for after hours operation.
    5. Equipment and systems expectations.
    6. Building occupant and operation and maintenance (O&M) personnel expectations.

    5.410.2.2 Basis of Design (BOD). [N] A written explanation of how the design of the building systems meets the OPR shall be completed at the design phase of the building project. The Basis of Design document shall cover the following systems:

    1. Renewable energy systems.

    2. Landscape irrigation systems.

    3. Water reuse systems.

    5.410.2.3 Commissioning plan. [N] Prior to permit issuance a commissioning plan shall be completed to document how the project will be commissioned. The commissioning plan shall include the following:

    1. General project information.
    2. Commissioning goals.
    3. Systems to be commissioned. Plans to test systems and components shall include: a. An explanation of the original design intent. b. Equipment and systems to be tested, including the extent of tests.

    c. Functions to be tested.

    d. Conditions under which the test shall be performed. e. Measurable criteria for acceptable performance. 4. Commissioning team information. 5. Commissioning process activities, schedules and responsibilities. Plans for the completion of commissioning shall be included.

  • CFC § 1207.2.2.1 High relevance — show source text
    1. Desired or field-determined control set points that are permanently recorded on control drawings at control devices or, for digital control systems, in system programming instructions.
    2. A schedule for inspecting and recalibrating all ESS controls.
    3. A service record log form that lists the schedule for all required servicing and maintenance actions and space for logging such actions that are completed over time and retained on-site.

    The ESS shall be operated and maintained in accordance with the manual and a copy of the manual shall be retained at an approved on-site location.

    1207.2.2.1 Ongoing inspection and testing. Systems that monitor and protect the ESS installation shall be inspected and tested in accordance with the manufacturer’s instructions and the operation and maintenance manual. Inspection and testing records shall be maintained in the operation and maintenance manual.

    1207.2.3 Decommissioning. The code official shall be notified prior to the decommissioning of an ESS. Decommissioning shall be performed in accordance with the decommissioning plan that includes the following:

    1. A narrative description of the activities to be accomplished for removing the ESS from service, and from the facility in which it is located.

    2. A listing of any contingencies for removing an intact operational ESS from service, and for removing an ESS from service that has been damaged by a fire or other event. (Material based on NFPA 855 2023 Ed.)

    1207.3 Equipment. ESS equipment shall be in accordance with Sections 1207.3.1 through 1207.3.9.

    1207.3.1 Energy storage system listings. ESS shall be listed in accordance with UL 9540.

    Exceptions:

    1. Lead-acid and nickel-cadmium battery systems less than 50 VAC, 60 VDC in telecommunications facilities for installations of communications equipment under the exclusive control of communications utilities located outdoors or in building spaces used exclusively for such installations that are in compliance with NFPA 76.
    2. Lead-acid and nickel-cadmium battery systems that are used for DC power for control of substations and control or safe shutdown of generating stations under the exclusive control of the electric utility, and located outdoors or in building spaces used exclusively for such installations.
    3. Lead-acid battery systems in uninterruptable power supplies listed and labeled in accordance with UL 1778 and utilized for standby power applications.

    (Material based on NFPA 855 2023 Ed.)

    1207.3.2 Equipment listing. Chargers, inverters and energy storage management systems shall be covered as part of the UL 9540 listing or shall be listed separately.

    1207.3.3 Utility interactive systems. Inverters shall be listed and labeled in accordance with UL 1741. Only inverters listed and labeled for utility interactive system use and identified as interactive shall be allowed to operate in parallel with the electric utility power system to supply power to common loads.

    1207.3.4 Energy storage management system. Where required by the ESS listing, an approved energy storage management system that monitors and balances cell voltages, currents and temperatures within the manufacturer’s specifications shall be provided. The system shall disconnect electrical connections to the ESS or otherwise place it in a safe condition if potentially hazardous temperatures or other conditions such as short circuits, over voltage or under voltage are detected. (Material based on NFPA 855 2023 Ed.)

    1207.3.5 Enclosures. Enclosures of ESS shall be of noncombustible construction. (Material based on NFPA 855 2023 Ed.)

  • CFC § 12-2 High relevance — show source text

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    12-2 2025 CALIFORNIA FIRE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    12 ENERGY SYSTEMS

    User notes:

    About this chapter: Chapter 12 was added to address the current energy systems found in this code, and is provided for the introduction of a wide range of systems to generate and store energy in, on and adjacent to buildings and facilities. The expansion of such energy systems is related to meeting today’s energy, environmental and economic challenges. Ensuring appropriate criteria to address the safety of such systems in building and fire codes is an important part of protecting the public at large, building occupants and emergency responders. More specifically, this chapter addresses standby and emergency power, portable generators, photovoltaic systems, fuel cell energy systems and energy storage systems.

    SECTION 1201—GENERAL

    1201.1 Scope. The provisions of this chapter shall apply to the installation, operation, maintenance, repair, retrofitting, testing, commissioning and decommissioning of energy systems used for generating or storing energy, including but not limited to energy storage systems under the exclusive control of an electric utility or lawfully designated agency. It shall not apply to equipment associated with the generation, control, transformation, transmission, or distribution of energy installations that is under the exclusive control of an electric utility or lawfully designated agency. Energy storage systems regulated by Section 1207 shall comply with this chapter, as appropriate, and NFPA 855.

    1201.2 Electrical wiring and equipment. Electrical wiring and equipment used in connection with energy systems shall be installed and maintained in accordance with this chapter, Section 603 and the California Electrical Code.

    1201.3 Mixed system installation. Where mixed systems are approved, the aggregate nameplate kWh energy of all energy storage systems in a fire area shall not exceed the maximum quantity specified for any of the energy systems in this chapter. Where required by the fire code official, a hazard mitigation analysis shall be provided and approved in accordance with Section 104.2.2 to evaluate any potential adverse interaction between the various energy systems and technologies.

    SECTION 1202—DEFINITIONS

    1202.1 Definitions. The following terms are defined in Chapter 2:

    BATTERY SYSTEM, STATIONARY STORAGE.

    BATTERY TYPES.

    CAPACITOR ENERGY STORAGE SYSTEM.

    CRITICAL CIRCUIT.

    EMERGENCY POWER SYSTEM.

    ENERGY STORAGE MANAGEMENT SYSTEMS.

    ENERGY STORAGE SYSTEM (ESS).

    ENERGY STORAGE SYSTEM, ELECTROCHEMICAL.

    ENERGY STORAGE SYSTEM, MOBILE.

    ENERGY STORAGE SYSTEM, WALK-IN UNIT.

    ENERGY STORAGE SYSTEM CABINET.

    ENERGY STORAGE SYSTEM COMMISSIONING.

    ENERGY STORAGE SYSTEM DECOMMISSIONING.

    FUEL CELL POWER SYSTEM, STATIONARY.

    PORTABLE GENERATOR.

    STANDBY POWER SYSTEM.

    SECTION 1203—EMERGENCY AND STANDBY POWER SYSTEMS

    1203.1 General. Emergency power systems and standby power systems required by this code or the California Building Code shall comply with Sections 1203.1.1 through 1203.1.9.

    1203.1.1 Stationary generators. Stationary emergency and standby power generators required by this code shall be listed in accordance with UL 2200.

    2025 CALIFORNIA FIRE CODE 12-3

  • CFC § 1207.2.1. Medium relevance — show source text

    A decommissioning plan for removing the ESS from service, and from the facility in which it is located. The plan shall include details on providing a safe, orderly shutdown of energy storage and safety systems with notification to the code officials prior to the actual decommissioning of the system. The decommissioning plan shall include contingencies for removing an intact operational ESS from service, and for removing an ESS from service that has been damaged by a fire or other event.

    Exceptions:

    1. Commissioning shall not be required for lead-acid and nickel-cadmium battery systems at facilities under the exclusive control of communications utilities that comply with NFPA 76 and operate at less than 50 VAC and 60 VDC. A decommissioning plan shall be provided and maintained where required by the fire code official.
    2. Lead-acid and nickel-cadmium battery systems less than 50 VAC, 60 VDC that are in telecommunications facilities for installations of communications equipment under the exclusive control of communications utilities, and are located outdoors or in building spaces or walk-in units used exclusively for such installations that are in compliance with NFPA 76, shall be permitted to have a commissioning plan in compliance with recognized industry practices in lieu of complying with Section 1207.2.1.
    3. Lead-acid and nickel-cadmium battery systems that are used for DC power for control of substations and control or safe shutdown of generating stations under the exclusive control of the electric utilities, and are located in building spaces or walk-in units used exclusively for such installations, shall be permitted to have a commissioning plan in compliance with applicable governmental laws and regulations in lieu of developing a commissioning plan in accordance with Section 1207.2.1. (Material based on NFPA 855 2023 Ed.)

    1207.2.1.1 Initial acceptance testing. During the commissioning process an ESS shall be evaluated for proper operation in accordance with the manufacturer’s instructions and the commissioning plan prior to final approval.

    12-12 2025 CALIFORNIA FIRE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    ENERGY SYSTEMS

    1207.2.1.2 Commissioning report. A report describing the results of the system commissioning, including the results of the initial acceptance testing required in Section 1207.2.1.1, shall be provided to the fire code official prior to final inspection and approval and maintained at an approved on-site location. (Material based on NFPA 855 2023 Ed.)

    1207.2.2 Operation and maintenance. An operation and maintenance manual shall be provided to both the ESS owner or their authorized agent and the ESS operator before the ESS is put into operation and shall include the following:

    1. Manufacturer’s operation manuals and maintenance manuals for the entire ESS, or for each component of the system requiring maintenance, that clearly identify the required routine maintenance actions.
    2. Name, address and phone number of a service agency that has been contracted to service the ESS and its associated safety systems.
    3. Maintenance and calibration information, including wiring diagrams, control drawings, schematics, system programming instructions and control sequence descriptions, for all energy storage control systems.
    4. Desired or field-determined control set points that are permanently recorded on control drawings at control devices or, for digital control systems, in system programming instructions.
    5. A schedule for inspecting and recalibrating all ESS controls.
  • CFC § 907.2.3 Medium relevance — show source text

    Early Suppression Fast-Response Sprinkler (ESFR) (see Automatic Sprinklers) Education Occupancy (Group E) 203 Alarms and detection 907.2.3 Means of egress Aisles 1018.2, 1018.5 Corridors 1020.3, 1020.2 Locking 1010.2.12, 1010.2.7 Panic hardware 1010.2.8

    Stairways, exit access 1019 Travel distance 1017.2, 1006.3.3,

    1006.2.1

    Sprinklers 903.2.3 Egress (see Means of Egress) Electrical Equipment 603 Aviation facilities 2006.14 Dust-producing machines 5906.5.5 Signs 603.4.1, 1207.4.8 Work space and clearance 603.4 Workstations in HPM facilities

    2703.7.2

    2025 CALIFORNIA FIRE CODE INDEX-5

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    INDEX

    Energy Storage System (ESS) 202, 1207 Cabinets 1207.4.10, 1207.4.8, 1207.6.3 Commissioning, decommissioning, operation and maintenance 202, 1207.2

    Fire remediation 1207.1.8 Hazard mitigation analysis 1207.1.6 Large-scale fire test 1207.1.7 Mobile ESS 202, 1207.1, 1207.1.2,

    1207.10 Residential (R-3 and R-4) 1207.11 Stationary ESS 202, 1207 Walk-in units 202, 1207.1.7, 1207.4.12, 1207.4.6, 1207.4.8, 1207.4.9, 1207.5.2, 1207.5.2.1, 1207.5.4, 1207.5.5, 1207.5.6, 1207.6.1, 1207.6.3, 1207.9.4 Energy Systems Chapter 12, 1201.1, 1201.2 Electrical energy storage systems 1201.3, 1207 Emergency and standby power systems 1203

    Permits 105.5.14, 105.6.10, 105.6.21,

    105.6.6 Portable generators 1204, 3309 Solar and photovoltaic systems 1205 Stationary fuel cell power systems 1206 Entry, Right of 104.4 Equipment, Fueled 313 Equipment Platform Defined 202

    Guards required 1015.2 Escalator Openings (see Floor Openings and Shafts) Escape Openings 1031 ESFR Sprinklers (see Automatic Sprinklers) Ethylene Gas 2503

    Generators 2506

  • CFC § 707.1 Medium relevance — show source text

    Maintenance 707.1 Drainage Control 2903.10, 2905.3, 5004.2.2.6, 5705.3.8.1, 5706.2.6, 5706.4.9 Drains Dip-tank bottom 2405.3.2 Exhaust duct sprinkler system 2703.10.4.4.3 HPM liquids 2705.2.3.3 Magazines 5604.6.1 Outdoor cryogenic fluid storage containers 5504.3.1.1.5

    Portable containers 5504.3.1.2.3 Draperies 807.2, 1032.6 Drilling, Well 5706.3 Dry Cleaning Chapter 21 Classifications 2103.1

    Defined 202

    Fire protection 2108 Permit 105.5.13 Requirements, general 2104 Requirements, operating 2105 Solvent or liquid classifications 202 Spotting and pretreating 2106 Systems 2107 Dry Cleaning Plant 202 Dry Cleaning Room 202 Dry-Chemical Extinguishing Agent Defined 202 Drying Apparatus 2404.8.1.2 Drying Ovens (see Industrial Ovens) Drying Rooms 914.10 Duct Smoke Detectors 907.3.1

    Dumpsters 304.3 Dust Collection 3703.5, 5906.5.3 Dust Explosion Hazards Chapter 22, 2803 Explosion venting 2803.2.1

    Early Suppression Fast-Response Sprinkler (ESFR) (see Automatic Sprinklers) Education Occupancy (Group E) 203 Alarms and detection 907.2.3 Means of egress Aisles 1018.2, 1018.5 Corridors 1020.3, 1020.2 Locking 1010.2.12, 1010.2.7 Panic hardware 1010.2.8

    Stairways, exit access 1019 Travel distance 1017.2, 1006.3.3,

    1006.2.1

    Sprinklers 903.2.3 Egress (see Means of Egress) Electrical Equipment 603 Aviation facilities 2006.14 Dust-producing machines 5906.5.5 Signs 603.4.1, 1207.4.8 Work space and clearance 603.4 Workstations in HPM facilities

    2703.7.2

    2025 CALIFORNIA FIRE CODE INDEX-5

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    INDEX

    Energy Storage System (ESS) 202, 1207 Cabinets 1207.4.10, 1207.4.8, 1207.6.3 Commissioning, decommissioning, operation and maintenance 202, 1207.2

    Fire remediation 1207.1.8 Hazard mitigation analysis 1207.1.6 Large-scale fire test 1207.1.7 Mobile ESS 202, 1207.1, 1207.1.2,

  • CFC § 901.5.1 Medium relevance — show source text

    901.5.1 Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire protection and life safety systems have been tested and approved.

    901.6 Inspection, testing and maintenance. Fire protection and life safety systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection and life safety systems and equipment shall be inspected, tested and maintained or removed in accordance with Section 901.8.

    All fire alarm systems, fire detection systems, automatic sprinkler or extinguishing systems, communication systems, and all other equipment, material or systems required by these regulations shall be maintained in an operable condition at all times in accordance with this code and California Code of Regulations, Title 19, Division 1. Upon disruption or diminishment of the fire protective qualities of such equipment, material or systems, immediate action shall be instituted to affect a reestablishment of such equipment, material or systems to their original normal and operational condition.

    [California Code of Regulations, Title 19, Division 1, §1.14] Maintenance.

    Every fire alarm system or device, sprinkler system, fire extinguisher, fire hose, fire-resistive assembly or any other fire safety assembly, device, material or equipment installed and retained in service in any building or structure subject to California Code of Regulations, Title 19, Division 1 regulations shall be maintained in an operable condition at all times in accordance with California Code of Regula- tions, Title 19, Division 1 regulations and with their intended use.

    [California Code of Regulations, Title 19, Division 1, §3.24] Maintenance of Equipment.

    All fire alarm systems, fire detection systems, automatic sprinkler or extinguishing systems, communication systems, and all other equip- ment, material or systems required by California Code of Regulations, Title 19, Division 1 shall be maintained in an operable condition at all times. Upon disruption or diminishment of the fire protective qualities of such equipment, material or systems, immediate action shall be instituted to affect a reestablishment of such equipment material or systems to their original normal and operational condition.

    [California Code of Regulations, Title 19, Division 1, §904(a)] Required Inspection, Testing and Maintenance Frequencies.

    (a) All automatic fire extinguishing systems, including systems installed as an alternate to other building requirements, shall be inspected, tested and maintained in accordance with the following frequencies. Local authorities may require more frequent inspec- tion, testing and maintenance and additional procedures.

    [California Code of Regulations, Title 19, Division 1, §904(a)(1)] Required Inspection, Testing and Maintenance Frequencies.

    (1) Water-based fire protection systems shall be inspected, tested and maintained in accordance with the frequencies required by NFPA 25 (2011 edition) including Annexes A, B, C, D and G as amended by the State of California. (Published as NFPA 25, 2013 Califor- nia Edition.)

    [California Code of Regulations, Title 19, Division 1, §904(b)] Required Inspection, Testing and Maintenance Frequencies.

    (b) When proof of the installation date of standpipe systems or automatic fire sprinkler systems cannot be furnished, such systems shall receive initial testing and maintenance by July 1, 1985.

    [California Code of Regulations, Title 19, Division 1, §904.2(a)] Testing and Maintenance Requirements.

  • CFC § 1203.1.2 Medium relevance — show source text


    Title 19, Division 1]|||||||||||||||||||||||| |Chapter / Section|||||||||||||||||||||||| |1203.1.2|||X||||||||||||||||||||| |1203.1.3.1|||X||||||||||||||||||||| |1203.1.5.1|||X||||||||||||||||||||| |1203.2.11|||X||||||||||||||||||||| |1205.2.4|||X||||||||||||||||||||| |1205.3.4|||X||||||||||||||||||||| |1207.11.3|||X||||||||||||||||||||| |1207.11.4|||X||||||||||||||||||||| |Table 1207.11.4|||X|||||||||||||||||||||

    • The California Code of Regulations (CCR), Title 19, Division 1 provisions that are found in the California Fire Code are a reprint from the current CCR, Title 19, Division 1 text for the code user’s convenience only. The scope, applicability and appeals procedures of CCR, Title 19, Division I remain the same. The state agency does not adopt sections identified by the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.

    2025 CALIFORNIA FIRE CODE 12-1

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    12-2 2025 CALIFORNIA FIRE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    12 ENERGY SYSTEMS

    User notes:

    About this chapter: Chapter 12 was added to address the current energy systems found in this code, and is provided for the introduction of a wide range of systems to generate and store energy in, on and adjacent to buildings and facilities. The expansion of such energy systems is related to meeting today’s energy, environmental and economic challenges. Ensuring appropriate criteria to address the safety of such systems in building and fire codes is an important part of protecting the public at large, building occupants and emergency responders. More specifically, this chapter addresses standby and emergency power, portable generators, photovoltaic systems, fuel cell energy systems and energy storage systems.

    SECTION 1201—GENERAL

    1201.1 Scope. The provisions of this chapter shall apply to the installation, operation, maintenance, repair, retrofitting, testing, commissioning and decommissioning of energy systems used for generating or storing energy, including but not limited to energy storage systems under the exclusive control of an electric utility or lawfully designated agency. It shall not apply to equipment associated with the generation, control, transformation, transmission, or distribution of energy installations that is under the exclusive control of an electric utility or lawfully designated agency. Energy storage systems regulated by Section 1207 shall comply with this chapter, as appropriate, and NFPA 855.

    1201.2 Electrical wiring and equipment. Electrical wiring and equipment used in connection with energy systems shall be installed and maintained in accordance with this chapter, Section 603 and the California Electrical Code.

  • CFC § 904.2 Medium relevance — show source text

    [California Code of Regulations, Title 19, Division 1, §904(a)] Required Inspection, Testing and Maintenance Frequencies.

    (a) All automatic fire extinguishing systems, including systems installed as an alternate to other building requirements, shall be inspected, tested and maintained in accordance with the following frequencies. Local authorities may require more frequent inspec- tion, testing and maintenance and additional procedures.

    [California Code of Regulations, Title 19, Division 1, §904(a)(1)] Required Inspection, Testing and Maintenance Frequencies.

    (1) Water-based fire protection systems shall be inspected, tested and maintained in accordance with the frequencies required by NFPA 25 (2011 edition) including Annexes A, B, C, D and G as amended by the State of California. (Published as NFPA 25, 2013 Califor- nia Edition.)

    [California Code of Regulations, Title 19, Division 1, §904(b)] Required Inspection, Testing and Maintenance Frequencies.

    (b) When proof of the installation date of standpipe systems or automatic fire sprinkler systems cannot be furnished, such systems shall receive initial testing and maintenance by July 1, 1985.

    [California Code of Regulations, Title 19, Division 1, §904.2(a)] Testing and Maintenance Requirements.

    (a) All testing and maintenance on automatic fire extinguishing systems in accordance with Health & Safety Code Section 13195 shall be performed by those licensed in accordance with Health and Safety Code Section 13196.5.

    Exceptions:

    (1) The State Fire Marshal may waive, in writing, licensing of fire departments which conduct fire sprinkler and standpipe system testing and maintenance.

    (2) Service on fire alarm systems and industrial systems as specified in Health and Safety Code Sections 13196.5(b) and (c) may be conducted without a license.

    (3) Testing and maintenance on automatic fire extinguishing systems exempted in writing by the State Fire Marshal, when the building owner or occupant has the staff and equipment to conduct testing and maintenance.

    9-8 2025 CALIFORNIA FIRE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FIRE PROTECTION AND LIFE SAFETY SYSTEMS

    [California Code of Regulations, Title 19, Division 1, §904.2(b)] Testing and Maintenance Requirements.

    (b) Any testing and maintenance of automatic fire extinguishing systems shall be performed in accordance with these requirements.

    Exceptions:

    (1) The State Fire Marshal may waive, in writing, the requirement that testing and maintenance be performed in accordance with these requirements when a licensee can demonstrate that a system cannot functionally be tested and maintained in accor- dance with the California Code of Regulations, Title 19, Division 1, Chapter 5.

    (2) If at any time a licensee encounters a specialized or modified system which cannot be tested and maintained in accordance with California Code of Regulations, Title 19, Division 1, Chapter 5, the licensee shall contact the State Fire Marshal and test and maintain the system as directed.

    (A) The intent of this section is to cover automatic fire extinguishing systems as originally designed, installed and approved by the Authority Having Jurisdiction. It is not, however, intended to require that such systems be upgraded to current adopted standards.

    [California Code of Regulations, Title 19, Division 1, §904.2(h)] Testing and Maintenance Requirements.

Frequently asked questions

When is commissioning required under the CFC?

Commissioning is required for newly installed ESS and for existing ESS that are retrofitted, replaced or returning to service after decommissioning; it must be performed prior to placing the ESS into service in accordance with an approved commissioning plan (§1207.2.1) .

What must a decommissioning plan include and who must be notified?

A decommissioning plan must describe the activities for removing the ESS from service and the facility, and list contingencies for removing intact or fire‑damaged systems; the code official must be notified prior to decommissioning (§1207.2.3) .

Where are O&M and inspection/testing obligations found?

Operation and maintenance manual requirements (including manuals, service contacts, calibration schedules and service logs) are specified in §1207.2.2, with ongoing inspection and testing of monitoring/protection systems required per §1207.2.2.1; broader inspection/testing frequencies and maintenance expectations appear in Chapter 9 and CCR Title 19 references (e.g., §901.6 and Title 19 maintenance/testing rules) .

More in California Fire Code

Ask about the CFC

Get cited, plain-English answers on the California Fire Code for your project — any code section, any scenario.

Start Free Trial

Related in the CFC