CBC · California Building Code
Structural steel and composite steel‑concrete design (AISC & seismic)
The CBC adopts AISC 360 for general steel, requires AISC 341 (and where applicable AISC 358) for seismic force‑resisting systems in higher seismic categories, and ties quality assurance and testing to the CBC special‑inspection provisions.
Last reviewed: July 5, 2026
Overview
This area of the CBC governs design, detailing, fabrication and erection of structural steel and composite steel‑concrete elements and sets the seismic requirements that control when seismic‑provisions and prequalified connections are required. The general design standard for structural steel and composite steel‑concrete is AISC 360 as adopted by CBC Section §2202.1 , with additional seismic provisions and modifications elsewhere in Chapter 22.
Seismic design rules direct when the more stringent AISC 341 seismic provisions (and AISC 358 prequalified connections) must be used — for example, structures in Seismic Design Categories D, E or F must be designed and detailed in accordance with AISC 341 per §2202.2.1.2; CBC also addresses when elements (struts, collectors, chords, foundation elements) must follow AISC 341 or when exceptions apply (§2202.2.2) . Quality assurance, special inspection and nondestructive testing requirements for seismic force‑resisting steel systems reference the AISC 341 quality‑assurance chapters and CBC special‑inspection sections (§1705.13.1 and §1705.14.1) . The code also contains California‑specific modifications to AISC provisions (see the AISC‑modification sections in Chapter 22 and the A‑appendices) and cross‑references to standards such as AISC 360, 341 and 358 listed in the referenced standards table .
In this section
Code references
Grounded in the retrieved California Building Code — click a citation to read the verbatim passage:
CBC § 2201A.5.1 High relevance — show source text
2201 A .5 Anchor rods. Anchor rods shall be set in accordance with the approved construction documents. The protrusion of the threaded ends through the connected material shall fully engage the threads of the nuts, but shall not be greater than the length of the threaded portion of the bolts. 2201A.5.1 Shear transfer at column base plate. Where the holes in column base plates are more than [1] / 8 inch (3 mm) larger than the anchor rods, as permitted by AISC 360, the anchor rods shall be designed for the induced bending stresses in combination with axial and shear stresses. Alternatively, shear lugs designed in accordance with ACI 318 Section 17.11 shall be permitted to transfer shear forces between column base plates and the supporting structure.
SECTION 2202 A —STRUCTURAL STEEL AND COMPOSITE STRUCTURAL STEEL AND CONCRETE
2202 A .1 General. The design, fabrication and erection of structural steel elements and composite structural steel and concrete elements in buildings, structures and portions thereof shall be in accordance with AISC 360.
Exceptions : [OSHPD 1 & 4]
2025 CALIFORNIA BUILDING CODE 22A-3
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
�
�
STEEL
1. For members designed based on tension, the slenderness ratio (L/r) shall not exceed 300, except for the design of hangers and bracing in accordance with NFPA 13 and for rod hangers in tension. 2. For members designed based on compression, the slenderness ratio (KL/r) shall not exceed 200, except for the design of hangers and bracing in accordance with NFPA 13.
2202 A .2 Seismic design. Where required, the seismic design, fabrication and erection of buildings, structures and portions thereof shall be in accordance with Section 2202 A .2.1 or 2202 A .2.2, as applicable.
2202 A .2.1 Structural steel seismic force-resisting systems and composite structural steel and concrete seismic force- resisting systems. The design, detailing, fabrication and erection of structural steel seismic force-resisting systems and composite structural steel and concrete seismic force-resisting systems shall be in accordance with the provisions of Section 2202 A .2.1.1 or 2202 A .2.1.2, as applicable. Seismic force-resisting systems of structural steel acting compositely with reinforced concrete shall be considered as an alternative system, except as permitted by:
[DSA-SS] Section 2202A.6.1.
[OSHPD 1 & 4] Section 2202A.4.1.
2202 A .2.1.1 Seismic Design Category B or C. Not permitted by DSA-SS and OSHPD.
CBC § 2202.2 High relevance — show source text
2202.2 Seismic design. Where required, the seismic design, fabrication and erection of buildings, structures and portions thereof shall be in accordance with Section 2202.2.1 or 2202.2.2, as applicable.
2202.2.1 Structural steel seismic force-resisting systems and composite structural steel and concrete seismic force-resist- ing systems. The design, detailing, fabrication and erection of structural steel seismic force-resisting systems and composite structural steel and concrete seismic force-resisting systems shall be in accordance with the provisions of Section 2202.2.1.1 or 2202.2.1.2, as applicable.
[ OSHPD 1R, 2 & 5 ] Seismic requirements for composite structural steel and concrete construction shall be considered as an alter- native system, except as permitted by Section 2202.4.1.
2202.2.1.1 Seismic Design Category B or C. Structures assigned to Seismic Design Category B or C shall be of any construction permitted in Section 2202. Where a response modification coefficient, R, in accordance with ASCE 7, Table 12.2-1, is used for the design of structures assigned to Seismic Design Category B or C, the structures shall be designed and detailed in accordance with the requirements of AISC 341. Beam-to-column moment connections in structural steel special moment frames and intermediate moment frames shall be prequalified in accordance with AISC 341, Section K1, qualified by testing in accordance with AISC 341, Section K2, or shall be prequalified in accordance with AISC 358.
Exception: The response modification coefficient, R, designated for “Steel systems not specifically detailed for seismic resistance, excluding cantilever column systems” in ASCE 7, Table 12.2-1, shall be permitted for structural steel systems designed and detailed in accordance with AISC 360, and need not be designed and detailed in accordance with AISC 341.
2202.2.1.2 Seismic Design Category D, E or F. Structures assigned to Seismic Design Category D, E or F shall be designed and detailed in accordance with AISC 341, except as permitted in ASCE 7, Table 15.4-1. Beam-to-column moment connections in structural steel special moment frames and intermediate moment frames shall be prequalified in accordance with AISC 341, Section K1, qualified by testing in accordance with AISC 341, Section K2, or shall be prequalified in accordance with AISC 358.
[OSHPD 1R, 2 & 5] All structural steel seismic force-resisting systems in ASCE 7 Table 15.4-1 shall be designed in accordance with AISC 341.
2202.2.2 Structural steel elements. The design, detailing, fabrication and erection of structural steel elements in seismic forceresisting systems other than those covered in Section 2202.2.1, including struts, collectors, chords and foundation elements, shall be in accordance with AISC 341 where either of the following applies:
- The structure is assigned to Seismic Design Category D, E or F, except as permitted in ASCE 7, Table 15.4-1.
- A response modification coefficient, R, greater than 3 in accordance with ASCE 7, Table 12.2-1, is used for the design of the structure assigned to Seismic Design Category B or C.
CBC § 2201.5 High relevance — show source text
2201.5 Anchor rods. Anchor rods shall be set in accordance with the approved construction documents. The protrusion of the threaded ends through the connected material shall fully engage the threads of the nuts, but shall not be greater than the length of the threaded portion of the bolts.
2025 CALIFORNIA BUILDING CODE 22-3
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
�
STEEL
2201.5.1 Shear transfer at column base plate. [OSHPD 1R, 2 & 5] Where the holes in column base plates are more than [1] / 8 inch (3 mm) larger than the anchor rods, as permitted by AISC 360, the anchor rods shall be designed for the induced bending stresses in combination with axial and shear stresses. Alternatively, shear lugs designed in accordance with ACI 318 Section 17.11 shall be permitted to transfer shear forces between column base plates and the supporting structure.
SECTION 2202—STRUCTURAL STEEL AND COMPOSITE STRUCTURAL STEEL AND CONCRETE
2202.1 General. The design, fabrication and erection of structural steel elements and composite structural steel and concrete elements in buildings, structures and portions thereof shall be in accordance with AISC 360.
Exceptions : [OSHPD 1R, 2 & 5] 1. For members designed based on tension, the slenderness ratio (L/r) shall not exceed 300, except for the design of hangers and bracing in accordance with NFPA 13 and for rod hangers in tension. 2. For members designed based on compression, the slenderness ratio (KL/r) shall not exceed 200, except for the design of hangers and bracing in accordance with NFPA 13.
2202.2 Seismic design. Where required, the seismic design, fabrication and erection of buildings, structures and portions thereof shall be in accordance with Section 2202.2.1 or 2202.2.2, as applicable.
2202.2.1 Structural steel seismic force-resisting systems and composite structural steel and concrete seismic force-resist- ing systems. The design, detailing, fabrication and erection of structural steel seismic force-resisting systems and composite structural steel and concrete seismic force-resisting systems shall be in accordance with the provisions of Section 2202.2.1.1 or 2202.2.1.2, as applicable.
[ OSHPD 1R, 2 & 5 ] Seismic requirements for composite structural steel and concrete construction shall be considered as an alter- native system, except as permitted by Section 2202.4.1.
2202.2.1.1 Seismic Design Category B or C. Structures assigned to Seismic Design Category B or C shall be of any construction permitted in Section 2202. Where a response modification coefficient, R, in accordance with ASCE 7, Table 12.2-1, is used for the design of structures assigned to Seismic Design Category B or C, the structures shall be designed and detailed in accordance with the requirements of AISC 341. Beam-to-column moment connections in structural steel special moment frames and intermediate moment frames shall be prequalified in accordance with AISC 341, Section K1, qualified by testing in accordance with AISC 341, Section K2, or shall be prequalified in accordance with AISC 358.
CBC § 2.1 High relevance — show source text
�
�
STEEL
1. For members designed based on tension, the slenderness ratio (L/r) shall not exceed 300, except for the design of hangers and bracing in accordance with NFPA 13 and for rod hangers in tension. 2. For members designed based on compression, the slenderness ratio (KL/r) shall not exceed 200, except for the design of hangers and bracing in accordance with NFPA 13.
2202 A .2 Seismic design. Where required, the seismic design, fabrication and erection of buildings, structures and portions thereof shall be in accordance with Section 2202 A .2.1 or 2202 A .2.2, as applicable.
2202 A .2.1 Structural steel seismic force-resisting systems and composite structural steel and concrete seismic force- resisting systems. The design, detailing, fabrication and erection of structural steel seismic force-resisting systems and composite structural steel and concrete seismic force-resisting systems shall be in accordance with the provisions of Section 2202 A .2.1.1 or 2202 A .2.1.2, as applicable. Seismic force-resisting systems of structural steel acting compositely with reinforced concrete shall be considered as an alternative system, except as permitted by:
[DSA-SS] Section 2202A.6.1.
[OSHPD 1 & 4] Section 2202A.4.1.
2202 A .2.1.1 Seismic Design Category B or C. Not permitted by DSA-SS and OSHPD.
2202 A .2.1.2 Seismic Design Category D, E or F. Structures assigned to Seismic Design Category D, E or F shall be designed and detailed in accordance with AISC 341. Beam-to-column moment connections in structural steel special moment frames and intermediate moment frames shall be prequalified in accordance with AISC 341, Section K1, qualified by testing in accordance with AISC 341, Section K2, or shall be prequalified in accordance with AISC 358.
2202 A .2.2 Structural steel elements. The design, detailing, fabrication and erection of structural steel elements in seismic forceresisting systems, including struts, collectors, chords and foundation elements, shall be in accordance with AISC 341.
2202A.3 Modifications to AISC 341. [OSHPD 1 and 4]
2202A.3.1 Section A4. Modify Section A4.1 Item (c) by adding the following:
(c) Locations and dimensions of protected zones. The fabricator shall permanently mark protected zones of structural elements in the seismic force-resisting system in the building that are designated on the construction documents. If these markings are obscured during construction, such as after the application of fire protection, the owner’s designated representative shall re-mark the protected zones as they are designated on the construction documents. [OSHPD 1 & 4] Primers or paints used to mark protected zones on steel surfaces, which are to receive sprayed fire-resistance material, shall comply with California Building Code Section 704.13.3.2.
CBC § 1705.12.2 High relevance — show source text
1705.12.2 Cold-formed steel light-frame construction. Periodic special inspection is required for welding operations of elements of the main windforce-resisting system. Periodic special inspection is required for screw attachment, bolting, anchoring and other fastening of elements of the main windforce-resisting system, including shear walls, braces, diaphragms, collectors (drag struts) and hold-downs.
Exception: Special inspections are not required for cold-formed steel light-frame shear walls and diaphragms, including screwing, bolting, anchoring and other fastening to components of the windforce-resisting system, where either of the following applies:
- The sheathing is gypsum board or fiberboard.
- The sheathing is wood structural panel or steel sheets on only one side of the shear wall, shear panel or diaphragm assembly and the specified fastener spacing at the panel or sheet edges is more than 4 inches (102 mm) on center (o.c.).
1705.12.3 Wind-resisting components. Periodic special inspection is required for fastening of the following systems and components:
- Roof covering, roof deck and roof framing connections.
- Exterior wall covering and wall connections to roof and floor diaphragms and framing.
1705.13 Special inspections for seismic resistance. Special inspections for seismic resistance shall be required as specified in Sections 1705.13.1 through 1705.13.9, unless exempted by the exceptions of Section 1704.2.
Exception: The special inspections specified in Sections 1705.13.1 through 1705.13.9 are not required for structures designed and constructed in accordance with one of the following:
- The structure consists of light-frame construction; the design spectral response acceleration at short periods, S DS, as determined in Section 1613.2.4, does not exceed 0.5; and the building height of the structure does not exceed 35 feet (10 668 mm).
- The seismic force-resisting system of the structure consists of reinforced masonry or reinforced concrete; the design spectral response acceleration at short periods, S DS, as determined in Section 1613.2.4, does not exceed 0.5; and the building height of the structure does not exceed 25 feet (7620 mm).
- The structure is a detached one- or two-family dwelling not exceeding two stories above grade plane and does not have any of the following horizontal or vertical irregularities in accordance with Section 12.3 of ASCE 7: 3.1. Torsional or extreme torsional irregularity. 3.2. Nonparallel systems irregularity. 3.3. Stiffness-soft story or stiffness-extreme soft story irregularity. 3.4. Discontinuity in lateral strength-weak story irregularity.
1705.13.1 Structural steel. Special inspections for seismic resistance shall be in accordance with Section 1705.13.1.1 or 1705.13.1.2, as applicable.
1705.13.1.1 Seismic force-resisting systems. Special inspections of structural steel in the seismic force-resisting systems in buildings and structures assigned to Seismic Design Category B, C, D, E or F shall be performed in accordance with the quality assurance requirements of AISC 341. [OSHPD 1R, 2 & 5] and this code.
CBC § 2210.1.1.1 High relevance — show source text
2210.1.1.1 Structural steel. The design, fabrication and erection of structural steel shall be in accordance with Section 2202.
2210.1.1.2 Cold-formed steel. The design of cold-formed carbon and low-alloy steel structural members shall be in accordance with Section 2204.
2210.1.1.3 Steel joists. The design of steel joists shall be in accordance with Section 2207.
2210.1.1.4 Steel cable. The design, fabrication and erection of steel cables, including related connections, shall be in accordance with Section 2214.
2210.2 Seismic design. Where required, the seismic design, fabrication and erection of the structural steel seismic force-resisting system shall be in accordance with Section 2202.2.1 or 2202.2.2, as applicable.
SECTION 2211—INDUSTRIAL BOLTLESS STEEL SHELVING
2211.1 General. The design, testing and utilization of industrial boltless steel shelving shall be in accordance with MHI ANSI/MH 28.2. Where required by ASCE 7, the seismic design of industrial boltless steel shelving shall be in accordance with Chapter 15 of ASCE 7.
SECTION 2212—INDUSTRIAL STEEL WORK PLATFORMS
2212.1 General. The design, testing and utilization of industrial steel work platforms shall be in accordance with MHI ANSI/MH 28.3. Where required by ASCE 7, the seismic design of industrial steel work platforms shall be in accordance with Chapter 15 of ASCE 7.
SECTION 2213—STAIRS, LADDERS AND GUARDING FOR STEEL STORAGE RACKS AND INDUSTRIAL STEEL WORK PLATFORMS
2213.1 General. The design and installation of stairs, ladders and guarding serving steel storage racks and industrial steel work platforms shall be in accordance with MHI ANSI/MH 32.1.
SECTION 2214—STEEL CABLE STRUCTURES
2214.1 General. The design, fabrication and erection including related connections, and protective coatings of steel cables for buildings shall be in accordance with ASCE 19.
[OSHPD 1R, 2 & 5] Steel cables with glass or polymer fabric material acting as a tensile membrane structure shall be considered as an alternative system.
SECTION 2215 — ADDITIONAL REQUIREMENTS FOR COMMUNITY COLLEGES [DSA-SS/CC]
2215.1 General.
2215.1.1 Shear transfer at column base plate. Where the holes in column base plates are more than [1] / 8 inch (3 mm) larger than the anchor rods, as permitted by AISC 360, the anchor rods shall be designed for the induced bending stresses in combination with axial and shear stresses. Alternatively, shear lugs designed in accordance with ACI 318 Section 17.11 shall be permitted to transfer shear forces between column base plates and the supporting structure.
2215.2 Modifications to AISC 341.
2215.2.1 Section B5. Modify exception of Section B5.2(a) as follows:
CBC § 2215.2 High relevance — show source text
2215.2 Modifications to AISC 341.
2215.2.1 Section B5. Modify exception of Section B5.2(a) as follows:
Exception: The forces specified in this section need not be applied to truss diaphragms designed as a part of a three-dimensional system in which the seismic force-resisting system types consist of ordinary moment frames, ordinary concentrically braced frames, ordinary cantilever column systems, special cantilever column systems, or combinations thereof, and where each diagonal bracing member resists no more than 30 percent of the diaphragm shear at each line of resistance and where the truss diagonal members conform to Sections F1.4b and F1.5 and the connections conform to Section F1.6.
2215.2.2 Section D2. Modify Section D2.6c(b)(2) as follows:
(2) The moment calculated using the load combinations of the applicable building code, including the amplified seismic load, provided the connection or other mechanism within the column base is designed to have the ductility necessary to accommodate the column base rotation resulting from the design story drift.
2215.3 Seismic requirements for composite structural steel and concrete construction. In addition to the requirements of Section 2202.2.1, steel and concrete ConXtech ConXL composite special moment frame with the approved moment connections in accordance with AISC 358 Chapter 10 shall be permitted provided: 1. Beams are provided with reduced beam sections (RBS);
2025 CALIFORNIA BUILDING CODE 22-9
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
STEEL
2. Web extension to beam web two-sided fillet welds are sized to develop expected strength of the beam web and shall not be less than a [1] / 4 -inch fillet weld; and 3. The built-up box column wall thickness shall not be less than 1.25 inches and the HSS column wall thickness shall not be less than [1] / 2 inch.
2215.4 Steel joists.
2215.4.1 Design approval. Joist and joist girder design calculations and profiles with member sizes and connection details, and joist placement plans shall be provided to the enforcement agency and approved prior to joist fabrication, in accordance with Title 24, Part 1. Joist and joist girder design calculations and profiles with member sizes and connection details shall bear the signature and stamp or seal of the registered engineer or licensed architect responsible for the joist design. Alterations to the approved joist and joist girder design calculations and profiles with member sizes and connection details, or to fabricated joists are subject to the approval of the enforcement agency.
2215.4.2 Joist chord bracing. The chords of all joists shall be laterally supported at all points where the chords change direction.
2215.5 Cold-formed steel light-frame construction.
2215.5.1 Trusses.
2215.5.1.1 Analysis submittals. Complete engineering analysis and truss design drawings shall accompany the construction documents submitted to the enforcement agency for approval. When load testing is required the test report shall be submitted with the truss design drawings and engineering analysis to the enforcement agency.
CBC § 2.1.2 Medium relevance — show source text
2202 A .2.1.2 Seismic Design Category D, E or F. Structures assigned to Seismic Design Category D, E or F shall be designed and detailed in accordance with AISC 341. Beam-to-column moment connections in structural steel special moment frames and intermediate moment frames shall be prequalified in accordance with AISC 341, Section K1, qualified by testing in accordance with AISC 341, Section K2, or shall be prequalified in accordance with AISC 358.
2202 A .2.2 Structural steel elements. The design, detailing, fabrication and erection of structural steel elements in seismic forceresisting systems, including struts, collectors, chords and foundation elements, shall be in accordance with AISC 341.
2202A.3 Modifications to AISC 341. [OSHPD 1 and 4]
2202A.3.1 Section A4. Modify Section A4.1 Item (c) by adding the following:
(c) Locations and dimensions of protected zones. The fabricator shall permanently mark protected zones of structural elements in the seismic force-resisting system in the building that are designated on the construction documents. If these markings are obscured during construction, such as after the application of fire protection, the owner’s designated representative shall re-mark the protected zones as they are designated on the construction documents. [OSHPD 1 & 4] Primers or paints used to mark protected zones on steel surfaces, which are to receive sprayed fire-resistance material, shall comply with California Building Code Section 704.13.3.2.
2202A.3.2 Section I2. [OSHPD 1 & 4] Replace Section I2.1 Item (d) as follows:
(d) Decking attachments that penetrate the beam flange shall not be placed on beam flanges within the protected zone, except power-actuated fasteners up to 0.18 inch in diameter are permitted, provided that the penetration is less than 85 percent of beam flange thickness.
2202A.4 Modifications to AISC 358. [OSHPD 1 and 4]
2202A.4.1 Modifications to AISC 358 Chapter 10. [OSHPD 1 and 4] Steel and concrete ConXtech ConXL composite special moment frame connections shall be permitted, provided: 1. Beams are provided with reduced beam sections (RBS); 2. Web extension to beam web two-sided fillet welds are sized to develop expected strength of the beam web and shall not be less than a [1] / 4 inch fillet weld; and 3. The built-up box column wall thickness shall not be less than 1.25 inches and the HSS column wall thickness shall not be less than [1] / 2 inch.
2202A.4.2 Modifications to AISC 358 Chapter 11 Welded Moment Connection. The welded side plate steel moment connection shall be permitted, provided: 1. The beams shall consist of either rolled or built-up wide flange sections. 2. The biaxial dual-strong axis and column minor axis configurations of the moment connection shall be considered as an alternative system. 3. For SMF and IMF systems, U-shaped cover plates shall be used and the hinge-to-hinge span to beam depth, L h _/d,
CBC § 506.6 Medium relevance — show source text
506.6T—17: Visual Shotcrete Core Quality Evaluation
1908.1, 1908A.1, 1909.4
548.15-20: Specification for Crack Repair by Epoxy Injection
1911.2, 1911A.2
550.5—18: Code Requirements for the Design of Precast Concrete Diaphragms for Earthquake Motions
Table 1705.3
ITG—7-09: Specification for Tolerances for Precast Concrete
1901.7.2
AISC American Institute of Steel, 130 East Randolph Street, Suite 2000, Chicago, IL 60601-6219
ANSI/AISC 341—22: Seismic Provisions for Structural Steel Buildings 1705.13.1.1, 1705.13.1.2, 1705.14.1.1, 1705.14.1.2, Table 1705A.2.1, 1810.3.5.3.1, 2202.2.1.1, 2202.2.1.2, 2202.2.2, 2202A.5, 2205.3,
2215.2
ANSI/AISC 358—22: Prequalified Connections for Special and Intermediate Steel Moment Frames for Seismic Applications Table 1705A.2.1, 2202.2.1, 2202.2.1.2, 2202.3, 2202A.3, 2202A.6, 2215.3, 2205A, 2205.4, 2206A.2, 2206.2.1
ANSI/AISC 360—22: Specification for Structural Steel Buildings 722.5.2.2.1, 1604.3.3, 1705.2.1, 1705A.2.1, Table 1705A.2.1, 1705A.2.5, 2201A.5.1, 2202.1, 2202.2.1.1, 2204.4, 2204A.4, 2215.1.1, 2215A.1.2, 2215A.2.1
ANSI/AISC 370—21: Specification for Structural Stainless Steel Buildings 1705.2.2, 1705.2.2, Table 1705A.2.1, 1705A.2.2, 2203.1
AISI American Iron and Steel Institute, 25 Massachusetts Avenue, NW Suite 800, Washington, DC 20001
AISI S100—16(2020) w/S2—20: North American Specification for the Design of Cold-Formed Steel Structural Members, 2016 Edition (Reaffirmed 2020), with Supplement 2, 2020 Edition
1604.3.3, 1905.7.2, 2204, 2204.2.2, 2204A.1
AISI S202—20: Code of Standard Practice for Cold-formed Steel Structural Framing, 2020 Edition
2206.1.3.1, 2206.1.3.1
CBC § 501A.3 Medium relevance — show source text
501 A .2 Fire-resistance ratings. Fire-resistance ratings shall comply with the California Building Standards Code.
501A.3 Prescriptive compliance provisions. Alterations, additions and changes of occupancy to the following categories of existing buildings and structures shall comply with the provisions of this section.
501A.3.1 Prescriptive compliance provisions for SPC-4D using the California Building Code, 1980 (CBC 1980). Nonconforming buildings shall satisfy the following requirements: 1. The California Building Code, 1980 (CBC 1980), as used in this chapter, consists of the Uniform Building Code, 1979 (UBC 1979) along with requirements contained in: a) California Code of Regulations, Title 24- Building Standards, dated February 2, 1980 (Revision record for Register 80, No. 5). b) California Code of Regulations, Title 22 – Social Security, dated October 13, 1979 (Revision Record for Register 79, No 41). c) California Code of Regulations, Title 17 – Public Health, dated October 13, 1979 (Revision Record for Register 79, No 41-B). 2. All existing structural elements of Seismic Force Resisting System (SFRS) shall satisfy the detailing requirements in the CBC 1980 or demonstrate that the level of seismic performance is equivalent to that given in the CBC 1980, as determined by the building official. 3. A continuous load path or paths with adequate strength and stiffness to transfer all the forces from the point of origin to final point of resistance shall be justified by analysis. 4. Site data report in accordance with the CBC 1980 shall establish that seismically induced differential settlement does not exceed 1 ″ in 40 ′ .
5. Adjacent buildings shall satisfy the SPC building separation requirements in accordance with the California Administrative Code, Chapter 6 Section 3.4. 6. The addition of new structural elements or strengthening of existing structural elements for retrofit of nonconforming build- ings to SPC-4D shall comply with the following: a) The seismic demand (forces or displacements) shall be in accordance with the CBC 1980; b) Capacity, detailing and connections for new structural elements shall satisfy the requirements in the CBC 2025 for new construction; and c) The strengthening of existing structural elements shall use capacities determined in accordance with the CBC 2025 for new construction consistent with the detailing and connections used in the strengthened member. 7. All construction, quality assurance and quality control shall be in accordance with the new construction provisions of CBC 2025.
8. Elements not part of the Seismic Force-Resisting System (SFRS), including those identified in the California Administrative Code Chapter 6, Article 10, shall be evaluated using seismic forces and the requirements of the CBC 1980. 9. Any column or wall that forms part of two or more intersecting SFRS and is subjected to axial load due to seismic forces acting along either principal plan axis equaling or exceeding 20 percent of the axial design strength of the column or wall shall be _evaluated for the most critical load effect due to application of seismic force in any direction.
CBC § 0.0015 Medium relevance — show source text
Exception: Where concrete slabs with continuous reinforcement having an area not less than 0.0015 times the concrete area in each of two orthogonal directions are present and are either monolithic with or equivalently bonded to beams, girders or columns, the longitudinal reinforcing or prestressing steel passing through the column reinforcement shall have a nominal tensile strength of one-third of the required one-way vertical strength of the connection of the floor or roof system to the column in each direction of beam or slab reinforcement passing through the column.
1616.2.2 Structural steel, open web steel joist or joist girder, or composite steel and concrete frame structures. Frame structures constructed with a structural steel frame or a frame composed of open web steel joists, joist girders with or without other structural steel elements or a frame composed of composite steel or composite steel joists and reinforced concrete elements shall conform to the requirements of this section.
1616.2.2.1 Columns. Each column splice shall have the minimum design strength in tension to transfer the design dead and live load tributary to the column between the splice and the splice or base immediately below.
1616.2.2.2 Beams. End connections of all beams and girders shall have a minimum nominal axial tensile strength equal to the required vertical shear strength for allowable stress design (ASD) or two-thirds of the required shear strength for load and resistance factor design (LRFD) but not less than 10 kips (45 kN). For the purpose of this section, the shear force and the axial tensile force need not be considered to act simultaneously.
Exception: Where beams, girders, open web joist and joist girders support a concrete slab or concrete slab on metal deck that is attached to the beam or girder with not less than [3] / 8 -inch-diameter (9.5 mm) headed shear studs, at a spacing of not more than 12 inches (305 mm) on center, averaged over the length of the member, or other attachment having equivalent shear strength, and the slab contains continuous distributed reinforcement in each of two orthogonal directions with an area not less than 0.0015 times the concrete area, the nominal axial tension strength of the end connection shall be permitted to be taken as half the required vertical shear strength for ASD or one-third of the required shear strength for LRFD, but not less than 10 kips (45 kN).
16-36 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
STRUCTURAL DESIGN
1616.3 Bearing wall structures. Bearing wall structures shall have vertical ties in all load-bearing walls and longitudinal ties, transverse ties and perimeter ties at each floor level in accordance with this section and as shown in Figure 1616.3.
FIGURE 1616.3—LONGITUDINAL, PERIMETER, TRANSVERSE AND VERTICAL TIES
1616.3.1 Concrete wall structures. Precast bearing wall structures constructed solely of reinforced or prestressed concrete, or combinations of these shall conform to the requirements of Sections 16.2.4 and 16.2.5 of ACI 318.
1616.3.2 Other bearing wall structures. Ties in bearing wall structures other than those covered in Section 1616.3.1 shall conform to this section.
CBC § 1705.13.7 Medium relevance — show source text
TABLE 1705.13.7—REQUIRED INSPECTIONS OF STORAGE RACK SYSTEMS Col2 Col3 Col4 Col5 TYPE CONTINUOUS
INSPECTIONPERIODIC
INSPECTIONREFERENCED
STANDARDIBC REFERENCE 1. Materials used, to verify compliance with one or more of the
material test reports in accordance with the approved
construction documents.— X — — 2. Fabricated storage rack elements. — X — Section 1704.2.5 3. Storage rack anchorage installation. — X ANSI/MH16.1
Section 7.3.2— 4. Completed storage rack system, to indicate compliance with
the approved construction documents.— X — — 1705.13.8 Seismic isolation systems. Periodic special inspection shall be provided for seismic isolation systems in seismically isolated structures assigned to Seismic Design Category B, C, D, E or F during the fabrication and installation of isolator units and energy dissipation devices.
1705.13.9 Cold-formed steel special bolted moment frames. Periodic special inspection shall be provided for the installation of cold-formed steel special bolted moment frames in the seismic force-resisting systems of structures assigned to Seismic Design Category D, E or F.
1705.14 Testing for seismic resistance. Testing for seismic resistance shall be required as specified in Sections 1705.14.1 through 1705.14.4, unless exempted from special inspections by the exceptions of Section 1704.2.
1705.14.1 Structural steel. Nondestructive testing for seismic resistance shall be in accordance with Section 1705.14.1.1 or 1705.14.1.2, as applicable.
1705.14.1.1 Seismic force-resisting systems. Nondestructive testing of structural steel in the seismic force-resisting systems in buildings and structures assigned to Seismic Design Category B, C, D, E or F shall be performed in accordance with the quality assurance requirements of AISC 341. [OSHPD 1R, 2 & 5] and this code.
Exceptions: [OSHPD 1R, 2 & 5] Not permitted by OSHPD.
- In buildings and structures assigned to Seismic Design Category B or C, nondestructive testing is not required for structural steel seismic force-resisting systems where the response modification coefficient, R, designated for “Steel systems not specifically detailed for seismic resistance, excluding cantilever column systems” in ASCE 7, Table 12.2-1, has been used for design and detailing.
- In structures assigned to Seismic Design Category D, E, or F, nondestructive testing is not required for structural steel seismic force-resisting systems where design and detailing in accordance with AISC 360 is permitted by ASCE 7, Table 15.4-1.
Frequently asked questions
When does the CBC require use of AISC 341 (seismic provisions)?
AISC 341 is required for structures assigned to Seismic Design Categories D, E or F and for seismic force‑resisting systems and certain elements when the conditions in §2202.2.1.2 and §2202.2.2 are met; ASCE 7 tables also identify where AISC 341 is mandated or where AISC 360 detailing is permitted .
Are special inspections and nondestructive testing required for seismic steel work?
Yes — special inspections of structural steel in seismic force‑resisting systems and nondestructive testing are required in accordance with the AISC 341 quality‑assurance provisions and the CBC special inspections/testing sections (§1705.13.1 and §1705.14.1), with limited exceptions for lower seismic demands or where ASCE 7 allows alternate detailing .
Does the CBC adopt AISC 360 for general steel and address composite connections?
Yes — CBC §2202.1 adopts AISC 360 for general structural steel and composite steel‑concrete design, and the code includes provisions and specific modifications for composite moment connections (including references to AISC 358) in the Chapter 22 sections and appendices .
More in California Building Code
- Administration & Permits
- Energy Efficiency
- Existing Buildings
- Occupancy Classification & Use
- Hazardous Materials & Occupancies
- Types of Construction
- Fire-Resistance & Fire Safety
- Interior Finishes
- Means of Egress
- Accessibility
- Exterior Walls
- Roofing & Roof Assemblies
- Structural Design
- Special Inspections & Tests
- Foundations & Soils
- Concrete
- Masonry
- Steel
- Wood
- Elevators & Conveying Systems