SECTION 3. METHOD OF
Internal Revenue Bulletin 2006-26 · 2026-10-03 edition · updated 2026-10-04 · United States
COMPUTATION
.01 In General . The Performance Rating Method (PRM) must be used to compute the percentage reduction in the total annual energy and power costs with respect to combined usage of a building’s heating, cooling, ventilation, hot water, and interior lighting systems as compared to a Reference Building that meets the minimum requirements of Standard 90.1–2001. .02 Performance Rating Method (PRM) . For purposes of this notice, the PRM includes the following computations:
(1) Reference Building Energy and Power Costs equal the sum of the energy and power costs for the following components of the Reference Building:
(a) Interior Lighting, (b) Heating, (c) Cooling, (d) Ventilation, and (e) Hot Water. (2) Proposed Building Energy and Power Costs equal the sum of the energy and power costs for the same components of the Proposed Building.
(3) Percentage Reduction in Energy and Power Costs is determined by—
(a) Subtracting Proposed Building Energy and Power Costs from Reference Building Energy and Power Costs; and
(b) Expressing the difference as a percentage of Reference Building Energy and Power Costs.
.03 Reference Building . For purposes of this notice, the Reference Building is a building that is located in the same climate zone as the taxpayer’s building and is otherwise comparable to the taxpayer’s building except that its interior lighting systems, heating, cooling, ventilation, and hot water systems, and building envelope meet the minimum requirements of Standard 90.1–2001. The energy performance of the Reference Building shall be determined by following the methods for baseline building performance in the PRM in Appendix G of Standard 90.1–2004. In calculating baseline building performance, the Reference Building shall use the following additional requirements from the 2005 California Title 24 Nonresidential Alternative Calculation Method (ACM) Approval Manual:
(1) Number of occupants, occupant sensible and latent heat loads, receptacle loads, and hot water loads from ACM Tables N2–2 for whole building values and Table N2–3 for building area values appropriate for mixed use buildings;
(2) Occupancy, HVAC, fans, infiltration, hot water, lighting, and equipment schedules from ACM Tables N2–4 through N2–9;
(3) Infiltration modeled following ACM Section 2.4.1.6;
(4) Luminaire power for interior lighting systems from the 2005 California Title 24 Nonresidential ACM Appendix NB or from manufacturers data.
.04 Proposed Building . (1) Energy Efficient Commercial Build- ing Property . In computing energy and power cost savings for purposes of section 2.02 (relating to energy efficient commercial building property), the Proposed Building is a building that contains the interior lighting systems, heating, cooling, ventilation, and hot water systems, and building envelope that have been incorporated, or that the taxpayer plans to incorporate, into the taxpayer’s building but that is otherwise identical to the Reference Building.
June 26, 2006 1177 2006–26 I.R.B.
.01 Building Square Footage . The sum of the floor areas of the conditioned spaces within the building, including basements, mezzanine, and intermediate-floored tiers, and penthouses with headroom height of 7.5 feet or greater. Building square footage is measured from the exterior faces of exterior walls or from the centerline of walls separating buildings, but excludes covered walkways, open roofed-over areas, porches and similar spaces, pipe trenches, exterior terraces or steps, chimneys, roof overhangs, and similar features.
.02 Building within the Scope of Stan- dard 90.1–2001 . A structure that—
(1) Is wholly or partially enclosed within exterior walls, or within exterior and party walls, and a roof, affording shelter to persons, animals, or property; and
(2) Is not a single-family house, a multifamily structure of three stories or fewer above grade, a manufactured house (mobile home), or a manufactured house (modular).
.03 Conditioned Space . Any enclosed space within the building qualifying as cooled space, heated space, or indirectly conditioned space defined as follows:
(1) Cooled Space . An enclosed space that is cooled by a cooling system whose sensible output capacity exceeds 5 Btu per hour per square foot of floor area.
(2) Heated Space . An enclosed space that is heated by a heating system whose output capacity relative to the floor area exceeds 5 Btu per hour per square foot of floor area.
(3) Indirectly Conditioned Space . An enclosed space (other than a heated space or a cooled space) that is heated or cooled indirectly by being connected to adjacent space(s) and that satisfies either of the following conditions:
(a) The space’s surface area that is adjacent to heated or cooled space multiplied by the weighted average U-factor of such adjacent surface area exceeds the space’s surface area adjoining the outdoors, unconditioned spaces, and semi-heated spaces ( e.g., corridors) multiplied by the weighted average U-factor of such adjoining surface area; or
(b) The air from heated or cooled spaces is intentionally transferred (naturally or mechanically) into the space at a rate exceeding 3 air changes per hour (ACH).
.01 The name, address, and telephone number of the qualified individual.
.02 The address of the building to which the certification applies.
.03 One of the following statements by the qualified individual:
(1) Statement for energy efficient commercial building property: The interior lighting systems, heating, cooling, ventilation and hot water systems, and building envelope that have been, or are planned to be, incorporated into the building will reduce the total annual energy and power costs with respect to combined usage of the building’s heating, cooling, ventilation, hot water, and interior lighting systems by 50 percent or more as compared to a Reference Building that meets the minimum requirements of Standard 90.1–2001.
(2) Statement for energy efficient lighting property that satisfies the requirements of the permanent rule of section 2.03(1)(a) of this notice: The interior lighting systems that have been, or are planned to be, incorporated into the building will reduce the total annual energy and power costs with respect to combined usage of the building’s heating, cooling, ventilation, hot water, and interior lighting systems by 16 2 /3 percent or more as compared to a Reference Building that meets the minimum requirements of Standard 90.1–2001.
(3) Statement for energy efficient lighting property that satisfies the requirements of the interim rule of section 2.03(1)(b) of this notice: The interior lighting systems that have been, or are planned to be, incorporated into the building satisfy the requirements of the interim rule of section 2.03(1)(b) of Notice 2006–52. (4) Statement for energy efficient heating, cooling, ventilation, and hot water property: The heating, cooling, ventilation, and hot water systems that have been, or are planned to be incorporated into the building will reduce the total annual energy and power costs with respect to combined usage of the building’s heating, cooling, ventilation, hot water, and interior lighting systems by 16 2 /3 percent or more as compared to a Reference Building that meets the minimum requirements of Standard 90.1–2001.
(5) Statement for energy efficient building envelope property: The building envelope that has been, or is planned to be, incorporated into the building will reduce the total annual energy and power costs with
respect to combined usage of the building’s heating, cooling, ventilation, hot water, and interior lighting systems by 16 2 /3 percent or more as compared to a Reference Building that meets the minimum requirements of Standard 90.1–2001.
.04 A statement by the qualified individual that the amount of such reduction has been determined under the rules of Notice 2006–52.
.05 A statement by the qualified individual that field inspections of the building performed by a qualified individual after the property has been placed in service have confirmed that the building has met, or will meet, the energy-saving targets contained in the design plans and specifications, and that the field inspections were performed in accordance with any inspection and testing procedures that (1) have been prescribed by the National Renewable Energy Laboratory (NREL) as Energy Savings Modeling and Inspection Guidelines for Commercial Building Federal Tax Deductions and (2) are in effect at the time the certification is given.
.06 A statement that the building owner has received an explanation of the energy efficiency features of the building and its projected annual energy costs;
.07 A statement that qualified computer software was used to calculate energy and power consumption and costs and identification of the qualified computer software used (see section 6 of this notice).
.08 A list identifying the components of the interior lighting systems, heating, cooling, ventilation, and hot water systems, and building envelope installed on or in the building, the energy efficiency features of the building, and its projected annual energy costs.
.09 A declaration, applicable to the certification and any accompanying documents, signed by the qualified individual, in the following form:
“Under penalties of perjury, I declare that I have examined this certification, including accompanying documents, and to the best of my knowledge and belief, the facts presented in support of this certification are true, correct, and complete.”