Earlier editions: 2026-09
Title 9 — BUILDING REGULATIONS
Tracy Municipal Code Ch. 9.06 Fire Protection and Prevention
Tracy Municipal Code · 2026-10 edition · updated 2026-10-04 · Tracy
Cite as: Tracy Municipal Code Chapter 9.06 · Text as of 2026-10-04
Footnotes:
--- (2) ---
Editor's note— Section 3 of Ord. No. 1192, adopted Jan. 21, 2014, amended ch. 9.06, which consisted of §§ 9.06.010—9.06.080, in its entirety to read as herein set out. Former §§ 9.06.010—9.06.080 derived from Ord. 1116, 2008; and Ord. No. 1176, adopted Nov. 20, 2012.
9.06.010 - Reference to chapter.¶
This chapter 9.06 of the Tracy Municipal Code may be referred to as the "City Fire Code" and is adopted pursuant to Government Code section 50022.2. For the purpose of clarity, the term "Code" when used alone, shall refer to the Tracy Municipal Code.
(Ord. No. 1192, § 3, 1-21-2014; Ord. No. 1274, § 3, 11-19-2019; Ord. No. 1335, § 4, 12-6-2022)
9.06.020 - Purpose of chapter.¶
The purpose of this chapter is to provide regulations governing the safeguarding of life and property from fire and explosion hazards arising from the storage, handling and use of hazardous substances, materials and devices, and from conditions hazardous to life or property in the occupancy of new and existing buildings and premises as herein provided and to provide safety to fire fighters and emergency responders during emergency operations; providing for the issuance of permits and collection of fees therefor; and to provide minimum standards to safeguard life or limb, health or property, and public welfare by regulating the design, construction and quality of materials for all buildings or structures in the City.
(Ord. No. 1192, § 3, 1-21-2014; Ord. No. 1274, § 3, 11-19-2019; Ord. No. 1335, § 4, 12-6-2022)
9.06.030 - Adoption by reference of the California Fire Code.¶
The City hereby adopts by reference the code entitled "2025 California Fire Code" including appendices B, BB, C, CC, D, F, H, L, N, O, and P, copyrighted by the International Code Council and the California Building Standards Commission (hereinafter "California Fire Code"), as amended by this chapter. The California Fire Code is on file with the City Clerk and is available for inspection and copying in accordance with Government Code Section 50022.6.
(Ord. No. 1192, § 3, 1-21-2014; Ord. No. 1228, § 5, 1-17-2017; Ord. No. 1274, § 4, 11-19-2019; Ord. No. 1335, § 5, 12-6-2022; Ord. No. 1367, § 3, 12-2-2025)
9.06.040 - Authority having jurisdiction.¶
The South San Joaquin County Fire Authority shall be the Authority Having Jurisdiction for all fire protection matters within the City of Tracy. This shall include the enforcement of building standards adopted by the State Fire Marshal as stated in the California Fire Code, Division I, California Administration, Section 1.11 and the implementation, administration and enforcement of the provisions of the City Fire Code.
(Ord. No. 1304, § 1, 2-16-2021; Ord. No. 1335, § 4, 12-6-2022)
Editor's note— Ord. No. 1304, § 1, adopted February 16, 2021 added § 9.06.040 and renumbered subsequent sections.
9.06.050 - Penalty provisions.¶
The California Fire Code subsection 110.4 is amended to read as follows:
110.4 Violations Penalties. Violations of this Chapter shall be enforced by the City of Tracy and the South San Joaquin County Fire Authority in accordance with the provisions of City of Tracy Municipal Code Section 9.02.050.
(Ord. No. 1192, § 3, 1-21-2014; Ord. No. 1274, § 4, 11-19-2019; Ord. No. 1304, § 1, 2-16-2021; Ord. No. 1335, § 4, 12-6-2022)
9.06.060 - Appeals.¶
Any person aggrieved by any decision of the fire code official, may appeal to the Board of Appeals, by filing a written notice of appeal with the City Clerk within thirty (30) days from the date the decision or action was taken.
(Ord. No. 1192, § 3, 1-21-2014; Ord. No. 1274, § 3, 11-19-2019; Ord. No. 1304, § 1, 2-16-2021; Ord. No. 1335, § 4, 12-6-2022)
9.06.070 - Amendments to the California Fire Code.¶
The City of Tracy hereby makes the following local amendments to the California Fire Code:
CHAPTER 1
Section 103.1 is amended to read as follows:
Section 103.1 Creation of agency.
The South San Joaquin County Fire Authority is hereby created and the official in charge thereof shall be known as the fire code official. The function of the agency shall be the implementation, administration and enforcement of the provisions of this Code.
Section 103.2, Appointment, is hereby repealed in its entirety as it purports to give vested employment rights different than currently exists for the fire code official.
Section 105.2.3 is amended to read as follows:
Section 105.2.3 Time limitation of application.
An application for a permit for any proposed work shall be deemed to have been abandoned 180 days after the date of filing, unless such application has been pursued in good faith or a permit has been issued; except that the fire code official is authorized to grant one or more extensions of time for additional periods not exceeding 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. However, at the discretion of the fire code official, an application shall not be extended more than two times if this Code or any other pertinent code, law or ordinance has been adopted subsequent to the date of application.
A new application shall be submitted, and corresponding fees shall be paid when an application for a permit has expired.
Section 105.3.2 is amended to read as follows:
Section 105.3.2 Extensions.
Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 12 months after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The building official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. However, at the discretion of the building official, a permit shall not be extended more than two times if this Code or any other pertinent code, law or ordinance has been adopted subsequent to the date of application. A new permit shall be obtained, and corresponding fees shall be paid when a permit has expired."
Section 105.5.5 is amended to read as follows:
105.5.5 Carnivals, Fairs, Festivals, and Exhibitions. A permit is required to operate a carnival, fair, festival, or exhibition.
Section 105 is amended by adding subsections 105.5.60 through 105.5.63 to read as follows:
Section 105.5.60 Christmas tree lots, haunted house or corn maze. An operational permit is required to operate a temporary or permanent operation.
105.5.61 Emergency Responder Radio Coverage. An operational permit is required for facilities with Emergency Responder Radio Coverage Systems.
105.5.62 Indoor Growing Operation. An operational permit is required to operate an indoor growing operation.
Exception: Agricultural Greenhouses in an agricultural zone.
105.5.63 Retail Cannabis Operation. An operational permit is required to operate a retail cannabis operation.
Section 106 is amended by adding subsection 106.2.1.1 to read as follows:
106.2.1.1 Detail Page. An 8 ½" x 11" document and an electronically submitted "detail" page for emergency responder data files shall be submitted to and approved by the fire authority before final inspection. Detail page shall include a site plan showing:
a. Property, site layout
b. Roads, fire access lanes, and building access points
c. Premises identification (Address, building identification, suites, room numbers, etc.)
d. Fire Hydrant and Fire Department Connection (FDC) locations
e. Knox product locations
f. Fire alarm control locations
g. Fire riser locations
h. Hose valve locations
i. "Main Electrical" and "Main Gas Disconnect" locations
j. Hazardous materials storage
Section 108 is amended by adding subsection 108.7 to read as follows:
108.7 Reinspection Fee. A reinspection fee may be assessed for each inspection, test, or reinspection when such portion of work for which an inspection is requested is not complete or when corrections requested to be inspected are not made. This section is not to be interpreted as requiring reinspection fees the first time an inspection or test is rejected for failure to comply with the requirements of the code, but as controlling the practice of requesting inspections/tests before the job is ready for such inspection or test. Reinspection fees may be assessed when the approved plans are not readily available to the inspector, for failure to provide access on the date for which the inspection/test is requested, failure for those individuals conducting the test to show up at the scheduled time or deviating from the approved plans. The fee shall be equal to all incurred costs for inspection and administrative staff at the fully burdened rate.
CHAPTER 2
Section 202 subsection FALSE ALARM is amended to read as follows:
FALSE ALARM shall mean the giving, signaling or transmission to any public fire station or company or to any officer or employee thereof, whether by telephone, spoken word or otherwise, information to the effect that there is a fire, medical emergency, rescue request, or other need for emergency service at or near the place indicated by the person giving, signaling, or transmitting such information, and there is found to be no need for emergency services.
CHAPTER 3
Chapter 3 of the 2022 California Fire Code is adopted in its entirety as amended below:
Section 315.7.2 is amended to read as follows:
315.7.2 Distance to lot line. Where pallets, palletized packing boxes, bin boxes or other combustibles are piled or stored adjacent to a property line, the distance from such storage or pile shall not be less than 20 feet to the property line.
Section 315.7.3 is amended to read as follows:
315.7.3 Storage height. Pallets, palletized packing boxes, bin boxes and other combustible materials shall be stored or piled with due regard to stability but in no case greater than 12 feet in height.
Exception: Bin boxes may be stacked to a maximum height of 20 feet.
Section 315 is amended by adding section 315.7.8 to read as follows:
Section 315.7.8 Outside storage of pallets, palletized packing boxes, bin boxes and other combustibles.
Section 315.7.8.1 Operational permit required.
An operational permit shall be obtained to store pallets, palletized packing boxes, bin boxes and other combustible materials more than 2500 cubic feet.
Section 315.7.8.2 Proximity to other combustible yard storage
Pallets, palletized packing boxes and bin boxes shall be stored within the limitations to other combustible yard storage as per Table 315.7.8.3 (a). The distance of stacked pallets, palletized packing boxes or bin boxes adjacent to buildings on the same lot shall comply with Table 315.7.8.3 (b).
Table 315.7.8.3 (a)
Minimum distance of piled storage to other combustible yard storage
| # of Pallets Bins or boxes | Min. Ft. |
|---|---|
| <50 | 20 Feet |
| 50-200 | 30 Feet |
| >200 | 50 Feet |
Table 315.7.8.3 (b)
Minimum distance of piled or combustible storage to buildings
| Building Wall Construction | # of Pallets, Bins or Boxes | # of Pallets, Bins or Boxes | # of Pallets, Bins or Boxes |
|---|---|---|---|
| <50 | 50-200 | >200 | |
| Masonry without openings | 0 ft. | 0 ft. | 15 ft. |
| Wood or metal With outside sprinklers | 10 ft. | 20 ft | 30 ft. |
| Wood, Metal or Masonry W/ |
20 ft. | 30 ft. | 50 ft. |
Section 315.7.8.3 Fire access
Fire access driveways between and around pallets, palletized packing boxes, bin boxes or other combustibles shall be a minimum of 20 feet in width and maintained free from accumulation of rubbish, weeds, machinery, equipment, or other obstructions that may block access or add to the fire hazard. Driveways shall be spaced to establish a maximum grid of storage not to exceed 50 feet by 50 feet and no pile shall exceed 2500 square feet in dimension or more than 50 feet in any one dimension. An approved turning radius around such piles shall be maintained at all times.
Section 315.7.8.4 Fencing
Outside storage of pallets, palletized packing boxes, bin boxes or other combustibles operating under a permit shall be enclosed by a suitable fence not less than 6 feet in height.
Section 315.7.8.5 Water Supply
An approved water supply and hydrants capable of supplying the required fire flow shall be provided within 400 feet or all portions of the storage area in accordance with section 507 of the 2025 California Fire Code or NFPA 1142 (where municipal water supplies are not available).
Section 320.1 is amended to read as follows:
320.1 General
The storage of batteries shall comply with Section 320.
CHAPTER 4
Section 401.5 is amended by adding subsection 401.5.1 Cost to read as follows:
Section 401.5.1 Cost recovery.
All costs incurred by the City to any response to a false alarm will be charged to that person, property owner, firm or corporation causing the transmission of the false alarm.
Section 403.10.6 is amended as follows:
403.10.6 Lithium-Ion and Lithium Metal Batteries. An approved fire safety and evacuation plan in accordance with Section 404 shall be prepared and maintained for occupancies that involve activities for the research and development, testing, manufacturing, handling or storage of lithium-ion batteries or lithium metal batteries, or the repair or servicing of vehicles powered by lithium-ion batteries or lithium metal batteries.
CHAPTER 5
Section 503.6 is amended to read as follows:
Section 503.6 Security gates.
The installation of security gates across a fire apparatus access road shall require, prior to installation, approval by the fire code official. Where security gates are installed, they shall have an approved means of emergency operation. The security gates and the emergency operation shall be maintained operational at all times. All electrically operated automatic gates across fire apparatus access roads shall be equipped with traffic preempting optical signal receivers compatible with the emitters utilized by the Fire Department, which will activate the gate and override all command functions of the gate controller. Knox Switches shall be provided at automatic gates. The traffic preemptive optical signal receiver and key switch shall be provided on both sides of an automatic access gate where an exit loop is not provided. The automatic gate shall have a battery backup or manual mechanical disconnect readily accessible to emergency personnel in case of power failure. All gates must meet Fire Department standards deemed necessary by the fire code official for rapid, reliable access. Electric gate operators, where provided, shall be listed in accordance with UL 325.
Gates intended for automatic operation shall be designed, constructed, and installed to comply with the requirements of ASTM F 2200. All manual gates shall be equipped with a Knox-Box containing a key to the gate, or an approved Knox-Padlock.
Section 505.1 is amended to read as follows:
Section 505.1 Address Identification.
New and existing buildings shall be provided and maintained with approved address identification. The identification shall comply with all of the following:
Not less than 4" high with a 1/2" stroke width. For Commercial Buildings, the size shall be a minimum of 24" high with a 6" stroke width.
Located minimum of 6' above grade.
Illuminated at night. Illumination shall be either internally or externally at an intensity of 5.0 foot-candles.
Numbers shall contrast with the background.
Numbers shall be placed on a portion of the building that is both legible and visible from the street that fronts the property.
Numbers shall not be placed on a moveable door and shall not be obstructed from view from the street.
Addresses shall be Arabic numbers or alphabetical letters and conventional in form.
Additionally, where access is by means of a private road and/or the building address cannot be viewed from the public way, a monument, pole, or other approved sign or means shall be used to identify the structure. Where required by the fire code official, address numbers/figures shall be provided in additional approved locations to facilitate emergency response.
Multiple tenant spaces serviced by vehicular access to the rear of the building through any driveway, alleyway, or parking lot shall have numbers or addresses placed prior to occupancy on all new and existing buildings as to be plainly visible and legible from the rear access way.
Multiple tenant spaces serviced by rear access through a corridor, exit court, or exit yard shall have approved numbers or addresses displayed on the rear of the tenant space.
Multiple tenant spaces that front on interior walkways or pedestrian malls shall have approved numbers or addresses placed over the entrance door in all new and existing buildings. An illuminated annunciator or directory board shall be required at every entrance where deemed necessary by the fire code official.
Section 506.1 is amended to read as follows:
Section 506.1 Where required.
Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life safety or firefighting purposes, the fire code official is authorized to require a key box in which all keys necessary for entering any portion of the property, building or area shall be contained.
The key box shall be manufactured by Knox (listed in accordance with UL 1037) and as a minimum size, shall be a Knox-Box 3200 series box with exterior dimensions of 5"x4"x3 ¾". Larger boxes will be required dependent upon the number of keys to be set within the box. The Knox-Box shall be installed at a height of 72" above finished grade in an accessible location approved by the fire code official. Keys within the box shall be permanently and readily identified.
Section 506 is amended by adding subsection 506.3 to read as follows:
Section 506.3 Hazardous materials management plan box.
When a facility stores or uses hazardous materials, the fire code official may require the installation of a secured box manufactured by KNOX and located at the facilities primary entrance or fire control room. The plan box shall contain up-to-date hazardous materials inventory sheets (HMIS) of all the hazardous materials stored or used within the facility, hazardous materials management plan (HMMP) and contact information of the company liaison to the fire department. The plan box shall be waterproof and of sufficient size to contain HMMP and HMIS information without the need to fold the documentation.
Section 509 is amended by adding subsection 509.3 to read as follows:
509.3 Fire Control Room. All new buildings protected with an automatic fire extinguishing system shall be provided with a Fire Control Room in which shall contain system control valves and where practical, fire alarm panel, smoke exhaust controls and all other equipment (excluding fire pump) as designated by the fire code official. If the electrical power equipment is not located within the Fire Control Room, then, it shall be in a room immediately adjacent thereto or as approved by the fire code official. The fire control room shall be located to be directly accessible from the exterior of the building and provided with a durable and permanent sign on the exterior of the access door to identify the space as the fire control room.
CHAPTER 6
Section 603 is amended by adding subsection 603.1.3 to read as follows:
603.1.3 Main Disconnects. The main electrical service to any commercial building shall be accessible for emergency shut off from the outside of the building. This may be accomplished by providing one (1) main disconnect, a Knox disconnect or shunt trip device. If, out of necessity, there is more than one main service disconnect, these disconnects shall be in close proximity to each other as approved by the fire code official. If a generator system activates automatically when a shunt trip or main disconnect shuts down, a control to stop the generator must be located with the main disconnect or shunt trip. Shunt trips, main disconnects and generator controls shall be identified by signs approved by the fire code official.
EXCEPTION:
- Fire Control Room with a marked door that is directly accessible from the outside of the building.
CHAPTER 9
Section 901 is amended by adding subsection 901.6.3.2 to read as follows:
901.6.3.2 Records Reporting. Fire detection, alarm, and extinguishing systems shall be maintained in an operative condition at all times and shall be replaced or repaired when they become defective. Non-required fire protection systems and equipment shall be inspected, tested, and maintained or removed. All inspection, testing and maintenance reports shall be forwarded to the Fire Authority using electronic media to the designated third party as selected by the Fire Authority. Paper (hard copy) reports are not permitted.
Section 903 is amended by adding subsection 903.2.20 to read as follows:
Section 903.2.22 Automatic fire sprinklers.
In addition to the requirements specified in Section 903 of this Code, an automatic fire sprinkler system shall be installed throughout and maintained in operable condition in the following buildings:
Every building hereafter constructed in which the total area of the building is greater than 6,000 square feet including overhangs.
Every building hereafter constructed of three or more stories in height as defined in the building code.
Every building hereafter remodeled or improved within a three-year period when the cost of improvements (alterations and/or structural repairs to the building) requiring permits exceeds a valuation threshold as specified below and the total area of the building exceeds 6,000 square feet.
The calculation is determined using a valuation threshold of $100,000 based on the 1985 "ENR US20 Cities" Average Construction Cost Index of 4195 adjusted by area cost factors. The city will annually update the valuation threshold to a current amount based on the increase in the index since the last figure used.
Every building hereafter changed in occupancy classification and the total area is greater than 6,000 square feet, and the proposed use is deemed to be more hazardous based on risk analysis by the fire code official.
Every building hereafter in which square footage is increased by 50% or more within a three-year period and the total square footage of the building exceeds 6000 square feet. If the additional square footage added to a building creates a total that exceeds the minimum code requirement for sprinklers for that occupancy type, then automatic sprinklers shall be required.
(Exception) Minor additions; not greater than 500 square feet in area to existing non-sprinklered buildings and the purpose of the addition is for accessory storage or disabled access upgrades.
Section 903.3.6 is amended to read as follows:
903.3.6 Hose threads. Fire hose threads and fittings used in connection with automatic sprinkler systems shall be "National Hose" (NH).
Section 912.2.1 is amended to read as follows:
912.2.1 Location. With respect to hydrants, driveways, buildings and landscaping, fire department connections shall be so located that fire apparatus and hose connected to supply the system will not obstruct access to the buildings for other fire apparatus. The location of fire department connections shall be approved by the fire code official. Fire department connections shall be within one hundred (100) feet of a fire hydrant.
Section 912.5 is amended to read as follows:
Section 912.5 Signs.
A metal sign with raised letters at least 1 inch (25 mm) in size shall be mounted on all fire department connections serving automatic sprinklers, standpipes, or fire pump connections. Such signs shall read: AUTOMATIC SPRINKLERS or STANDPIPES or TEST CONNECTION or a combination thereof as applicable. Where the fire department connection serves a portion of a building or a specific building among multiple buildings a sign shall be provided to reflect the appropriate building or portion of a building served.
Section 913 is amended by adding the following text to the end of the section:
Section 913.7 Meters and testing devices.
Where fire pumps are provided, they shall have a test loop installed in accordance with the applicable portions of NFPA 20 Section 4.21.2.
Section 913.2 is amended to read as follows:
The fire pump, driver and controller shall be protected in accordance with NFPA 20 against possible interruption of service through damage caused by explosion, fire, flood, earthquake, rodents, insects, windstorm, freezing, vandalism and other adverse conditions. The fire pump, driver and controller shall be diesel driven or it shall be electric with a diesel emergency generator backup as a secondary power source.
CHAPTER 11
Chapter 11 of the 2025 California Fire Code is partially adopted with adopted sections listed below (sections adopted by the State Fire Marshal remain unchanged unless modified below):
Section 1103.2 amended to read as follows:
Section 1103.2 Emergency responder radio coverage in existing buildings.
Existing buildings that do not have approved radio coverage for emergency responders within the building based upon the existing coverage levels of the public safety communication systems of the jurisdiction shall be equipped with such coverage when any of the following conditions apply:
Where the use or occupancy group of the building has been changed and the use or occupancy is more hazardous.
Where the addition of metal racking systems, equipment, or interior walls utilizing metal, masonry or concrete materials that interfere with emergency responder radio coverage within the building as noted below:
a. Where multiple tenant spaces exist within a single structure, only the tenant space where improvements are made that trigger radio coverage shall have radio coverage. The improvements made to provide adequate radio coverage shall be designed, however, to have the capability to expand indoor radio coverage to all other areas of the building by adding cable and antennas if needed for subsequent improvements in these other areas of the building. Survivability of the cable pathway and "junction" locations between tenant spaces shall be addressed.
b. New metal racks (including required aisle and flue space) or equipment installed that increase existing metal racks (including required aisle and flue space) or equipment by 40% or greater of tenant spaces up to 100,000 square feet, 35% or greater of tenant spaces up to 400,000 square feet and 25% or greater of tenant spaces greater than 400,000 square feet shall require radio coverage.
c. New metal racks (including required aisles and flue spaces) or equipment that cover 30% or greater area of the tenant space where no such improvements previously existed shall require radio coverage in tenant spaces up to 100,000 square feet; 25% or greater of tenant spaces up to 400,000 square feet and 20% or greater of tenant spaces greater than 400,000 square feet.
d. New masonry or concrete walls and elevated floor/ceilings and metal-framed walls or floor/ceilings installed that increase existing masonry or concrete walls and elevated floor/ceilings and metal-framed walls and floor/ceilings (area calculation) by 40% or greater of tenant spaces up to 100,000 square feet, 35% or greater of tenant spaces up to 400,000 square feet and 25% or greater of tenant spaces more than 400,000 square feet shall require radio coverage.
e. New masonry or concrete walls and elevated floor/ceilings and metal-framed walls or floor/ceilings installed that cover 30% or greater area of the tenant space (area calculation) where no such improvements previously existed shall require radio coverage in tenant spaces up to 100,000 square feet, 25% or greater of tenant spaces up to 400,000 square feet and 20% or greater of tenant spaces more than 400,000 square feet.
- Every building hereafter in which square footage of the building is increased by 50% or more within a three-year period and the total square footage of the building exceeds 10,000 square feet. Exception: 1). Group R Division 3 Occupancies and buildings constructed entirely of structural members made of wood.
CHAPTER 25
Chapter 25 of the 2025 California Fire Code is adopted in its entirety without amendment.
CHAPTER 26
Chapter 26 of the 2025 California Fire Code is adopted in its entirety without amendment.
CHAPTER 32
Chapter 32 of the 2025 California Fire Code is adopted in its entirety as amended below:
Table 3203.8 - Examples of Commodity Classification, Product Category: Batteries. Product: Lithium-ion Classification: High-hazard.
CHAPTER 57
Chapter 57 of the 2025 California Fire Code is adopted in its entirety as amended below:
That the geographic limits referred to in Chapter 57 of the 2025 California Fire Code are hereby established as follows:
Section 5704.2.9.6.1 is amended to include the geographical areas such storage is prohibited:
Section 5704.2.9.6.1 Locations where above-ground tanks are prohibited. Storage of class I and 2 liquids in above-ground tanks is prohibited in all zoning districts except districts zoned for commercial, industrial, or agricultural use.
Exception: Above ground tanks located at public safety facilities.
Section 5706.2.4.4 is amended to include the geographical areas such storage is prohibited:
Section 5706.2.4.4. Locations where above-ground tanks are prohibited. Locations where above-ground tanks are prohibited. Storage of class I and 2 liquids in above-ground tanks is prohibited in all zoning districts except districts zoned for commercial, industrial, or agricultural use.
CHAPTER 58
Chapter 58 of the 2025 California Fire Code is adopted in its entirety as amended below:
That the geographic limits referred to in Chapter 58 of the 2025 California Fire Code are hereby established as follows:
5806.2 Limitations. The storage of flammable cryogenic fluids in stationary containers outside of buildings is prohibited in any area which is zoned for other than industrial use.
CHAPTER 61
Section 6104.2 of the 2025 California Fire Code is amended to include the geographical areas restricting the storage of liquefied petroleum gas:
6104.2 Maximum capacity within established limits. The storage of liquefied petroleum gases prohibited in any central business district and in all zoning districts except districts zoned for commercial, industrial, rural, or agricultural uses.
APPENDIX B
Section B105.2 is amended by adding the following text to the end of the section: Exception:
- A maximum reduction in required fire-flow of up to 50 percent, as approved by the fire code official, is allowed when the building is provided with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2 as opposed to the 75% reduction values given for minimum fire flows in Table B1105.2. A reduction in required fire-flow of up to 75 percent, as approved by the fire code official, is allowed for warehouse buildings of Type I, Type II, and Type Ill construction provided with ESFR automatic fire sprinkler systems. The resulting fire-flow for any of these reductions shall not be less than 1500 gallons per minute for the prescribed duration according to Table B105.1(2). Reduction of fire-flow applies to the fire hydrants requirements as specified in Appendix C.
APPENDIX BB
Section BB105.1 and Exception is amended to read as follows:
Section BB105.1 The minimum fire-flow and flow duration for school buildings shall be as specified in Table B8105.1.
Exception: A reduction in required fire flow of up to 50 percent is allowed when the building is provided with an approved automatic sprinkler system. When a reduction in fire flow is used, fire flow shall not be less than 1500 gallons per minute for the prescribed duration as specified in Table B8105.1. Reduction of fire-flow applies to the fire hydrants requirements as specified in Appendix CC.
APPENDIX C
Appendix C is amended by adding section C106 to read as follows:
Section C106 Hydrant type. The fire code official shall approve the type of fire hydrants to be installed in the public right of way or on private property prior to any such installation.
Table C102.1 Number and Distribution of Fire Hydrants, footnote "b" is repealed and amended to read as follows:
Table C102.1 footnote "b"
b. Where streets are provided with median dividers that make access to hydrants difficult, cause time delay, or create undue hazard or both, or where arterial streets are provided with four or more traffic lanes, hydrant spacing shall average 500 feet on each side of the street and be arranged on an alternating basis.
APPENDIX CC
Appendix CC is amended by adding section CC106 to read as follows:
Section CC106 Hydrant type. The fire code official shall approve the type of fire hydrants to be installed in the public right of way or on private property prior to any such installation.
Table CC105.1 Number and Distribution of Fire Hydrants, footnote "b" is repealed and amended to read as follows:
Table CC105.1 footnote "b"
b. Where streets are provided with median dividers that make access to hydrants difficult, cause time delay, or create undue hazard or both, or where arterial streets are provided with four or more traffic lanes, hydrant spacing shall average 500 feet on each side of the street and be arranged on an alternating basis.
(Ord. No. 1192, § 3, 1-21-2014; Ord. No. 1228, § 5, 1-17-2017; Ord. No. 1274, § 4, 11-19-2019; Ord. No. 1304, § 1, 2-16-2021; Ord. No. 1335, § 5, 12-6-2022; Ord. No. 1367, § 3, 12-2-2025)
9.06.080 - State fire maps.¶
The City of Tracy adopts the Local Responsibility Area Fire Hazard Severity Zones map for the City of Tracy - San Joaquin County as identified by the State Fire Marshal, dated February 24, 2025. A copy of the adopted map can be obtained from the City Clerk's office during regular business hours.
(Ord. No. 1355, § 3, 6-3-2025)
Get a plain-English answer with a citation back to this text.
Ask AI about this code