Skip to content

Earlier editions: 2026-09

Division 8 — BUILDING AND SAFETY›Chapter 1 — BUILDING CODE Revised 2/26›Article 2 — AMENDMENTS TO CALIFORNIA BUILDING CODE Revised 2/26

Torrance Municipal Code § 12.11 AMENDMENTS TO CALIFORNIA BUILDING CODE Revised 2/26

Torrance Municipal Code · 2026-10 edition · updated 2026-10-05 · Torrance

Cite as: Torrance Municipal Code § 12.11 · Text as of 2026-10-05

12.11.2.2.3 Wood diaphragms.

The anchorage of concrete or masonry structural walls to wood diaphragms shall be in accordance with AWC SDPWS 4.1.5.1 and this section. Continuous ties required by this section shall be in addition to the diaphragm sheathing. Anchorage shall not be accomplished by use of toenails or nails subject to withdrawal, nor shall wood ledgers or framing be used in cross-grain bending or cross-grain tension. The diaphragm sheathing shall not be considered effective for providing the ties or struts required by this section

For structures assigned to Seismic Design Category D, E or F, wood diaphragms supporting concrete or masonry walls shall comply with the following:

  1. The spacing of continuous ties shall not exceed 40 feet. Added chords of diaphragms may be used to form subdiaphragms to transmit the anchorage forces to the main continuous crossties.

  2. The maximum diaphragm shear used to determine the depth of the subdiaphragm shall not exceed 75% of the maximum diaphragm shear.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
▸Contents — Torrance Municipal Code

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.