Chapter 80 — REFERENCED STANDARDS
§ 5.1
Sonoma County Municipal Code · 2026-09 edition · updated 2026-09-27 · Sonoma County
5.1.1.2 A supply of at least three sprinklers shall be maintained on the premises so…¶
promptly replaced.
(116)
California Fire Code, NFPA, Section 13D-16, Section 5.1.1.2.1 is added to read:
5.1.1.2.1 The sprinklers shall correspond to the types and temperature ratings of the…¶
sprinkler of all types and ratings installed.
(117)
California Fire Code, NFPA, Section 13D-16, Section 5.1.1.2.2 is added to read:
5.1.1.2.2 The sprinklers shall be kept in a mounted and accessible cabinet located…¶
maximum ceiling temperatures specified in Table 5.1.1.6.1 for each of the sprinklers within the cabinet.
(118)
California Fire Code, NFPA, Section 13D-16, Section 5.1.1.3 is added to read:
5.1.1.3 One sprinkler wrench as specified by the sprinkler manufacture shall be…¶
removal and installation of sprinklers in the system.
(119)
California Fire Code, NFPA, Section 13D-16, Section 6.2.3.4 is added to read: