23.28.010 ADOPTION.¶
(a) The 2016 California Fire Code (CFC), California Code of Regulations, Title 24, Part 9, adopting the 2015 International Fire Code of the International Code Council with necessary California amendments, together with the non-building standards reproduced therein except otherwise provided by this chapter, are adopted by reference as the Fire Code of City of San Mateo. This Code including all amendments thereto, shall hereafter be called the "Fire Code," and/or this "Code" and are adopted as and for the rules, regulations, and standards within the City as to all matters therein, except otherwise provided.
(b) 2016 California Fire Code Section 103.2, Appointment is not adopted.
(c) The Appendix Chapters A, D, E, F, I and J contained in the 2016 California Fire Code are not adopted unless adopted by the State.
(d) No section of the Fire Prevention Code shall impose a mandatory duty of enforcement on the City, or on any officer, official, agent, employee, board, council, or commission thereof. Instead, if any section purports to impose a mandatory duty of enforcement, said section shall be deemed to invest the City, and the appropriate officer, official, agent, employee, board, council, or commission with discretion to enforce the section, or not to enforce it.
(e) A copy of the Fire Code, as defined herein, shall be kept on file in the office of the City Clerk.
23.28.020 APPLICABILITY.¶
(a) All sections of this chapter shall apply to all buildings, structures and portions thereof, and to all appurtenances and fixtures thereto, and anything connected with, or by, or in, or on, any premises or building.
(b) Whenever any provision of this chapter or in any other law, ordinance, or resolution of any kind, impose overlapping or contradictory regulations, or contain any restrictions covering the same subject matter, the provision that is more restrictive or imposes higher standards or requirements shall govern.
23.28.030 TITLE—AMENDED.¶
Section 101.1 "Title" is amended to read as shown below:
These regulations shall be known as the 2016 California Fire Code, and with amendments adopted by the City of San Mateo, will be referred to herein as this "Code," and/or "Fire Code."
23.28.040 POLICY MANUAL—AMENDED.¶
Section 101 "Scope and General Requirements" is amended to add subsection 101.6 "Policy Manual" to read as shown below:
The Bureau of Fire Protection and Life Safety Policy Manual shall serve as a supplemental instruction and interpretation manual for the Fire Code and is hereby incorporated by reference. The Fire Marshal is responsible for amending this manual as necessary to maintain current instructions and interpretations.
23.28.050 BOARD OF APPEALS—NOT ADOPTED.¶
Section 108 "Board of Appeals" is not adopted. All decisions and determinations of the Fire Chief decisions or determinations made by the building official relative to the application and interpretations of these codes are final and not subject to appeal.
23.28.060 GENERAL DEFINITIONS—AMENDED.¶
Section 202 is amended to include the following additional definitions as shown below:
All Weather Driving Surface. A roadway designed to carry the imposed weight loads of fire apparatus (Minimum load of 68,000 pounds) and a minimum surface finish of one layer of asphalt or concrete or road pavers. Driveway. Access road from the public way to a structure that is used for public vehicular access, including fire and emergency vehicles. Midrise. A building with four or more stories and/or occupied floors more than 40 feet above the lowest level of exit discharge.
23.28.090 BUILDINGS AND FACILITIES—AMENDED.¶
Section 503.1.1 "Buildings and Facilities" is amended to read as shown below:
Every building and facility shall be accessible to Fire Department apparatus by way of all-weather access roadways prior to combustible construction. The fire apparatus access roads shall comply with the requirements of this section and extend to within 150′ of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. The access road shall have a minimum unobstructed width of 20′ and shall be required to have a minimum "first lift" of pavement applied which shall support the imposed load of a fire apparatus which is a minimum 68,000 pounds. The developer shall be required to provide the Fire Chief with a site plan showing the location, width, grades, and cross section of the proposed access roads to be used during construction. Building construction permits shall not be issued and combustible construction shall not be allowed on the site until the site plan is reviewed and approved and stamped by the Fire Department. Exceptions:
- The Fire Chief is authorized to increase the dimension of 150 feet where any of the following conditions occur:
1.1.¶
1.2.¶
1.3. There are not more than two Group R-3 or Group U occupancies.¶
- Where approved by the Fire Chief, fire apparatus access roads shall be permitted to be exempted or modified for solar photovoltaic power generation facilities.
23.28.100 FIRE LANE DESIGNATION—ADDED.¶
Section 503.3 "Marking" is amended to include subsection 503.3.1 "Fire Lane Designation" to read as shown below:
Designation of fire lanes shall be by one of the following means:
(a) By a white sign measuring at least twelve inches by eighteen inches (12″ x 18″) posted immediately adjacent thereto and clearly visible. It should clearly state in red letters not less than one inch (1″) in height, that the space is a fire lane and parking is prohibited. Fire lane signs shall be spaced at a minimum of 50 feet apart.
(b) By outlining and hash marking the area in contrasting colors clearly marking it with the words "Fire Lane - No Parking."
(c) By identifying the space with a red curb upon which the words "Fire Lane - No Parking" are stenciled every 15 feet.
Both sides of fire lanes shall be red curbed when the fire lane is twenty (20) feet to twenty-eight (28) feet in width.
At least one side of a fire lane shall be red curbed and stenciled when the fire lane is over twenty-eight (28) and up to thirty-six (36) feet in width.
Curbs need not be painted red nor stenciled when the fire lane is more than thirty-six (36) feet in width.
23.28.110 ADDRESS IDENTIFICATION.¶
Section 505.l "Address Identification" is amended to read as shown below:
New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. Address numbers shall be Arabic numerals or alphabet letters. Said numbers shall be either internally or externally illuminated in all new construction. Numbers shall be as follows:
(a) Minimum of one-half inch (1/2″) stroke by six inches (6″) high.
(b) When the structure is thirty-six (36) to fifty (50) feet from the street or fire department access a minimum of one-half inch (1/2″) stroke by nine inches (9″) high is required.
(c) When the structure is more than fifty (50) feet from the street or fire apparatus access, a minimum of one inch (1″) stroke by twelve inches (12″) high is required.
23.28.120 ADDRESS IDENTIFICATION—MULTI-TENANT BUILDINGS—ADDED.¶
Section 505.l is amended to include subsection 505.1.1 "Multi-Tenant Building" to read as shown below:
Numbers or letters shall be designated on all occupancies within a building. Size shall be one-half inch (1/2″) stroke by four inches (4″) high and on a contrasting background. Directional address numbers or letters shall be provided. Said addresses or numbers shall visible from the street posted at a minimum. height of 5 feet, 6 inches (5′ 6″) above the finished floor, shall be visible from the street and shall be either internally or externally illuminated in all new construction.
23.28.130 ADDRESS IDENTIFICATION—REAR ADDRESSING—ADDED.¶
Section 505.1 is amended to include subsection 55.1.2 "Rear Addressing" to read as shown below:
When required by the chief, approved numbers or addresses shall be placed on all new and existing buildings in such a position as to be plainly visible and legible from the fire apparatus road at the back of a property or where rear parking lots or alleys provide an acceptable vehicular access. Number stroke and size shall comply with Section 505.1.
23.28.140 KEY BOX CONTENTS REQUIREMENTS—ADDED.¶
Section 506.1.1 "Locks" is amended to include subsection 506.1.1.1 "Key box contents requirements" to read as shown below:
The keys provided shall be a master key to all spaces including multi-tenant spaces. Additional keys shall be included for card access, elevator control, fire alarm control panels, and fire sprinkler control valve access. If the business/operation is required to have a Hazardous Material Inventory Statement (HMIS), the HMIS shall be included in the key box. Exceptions:
Multi-tenant spaces which provide a key box for each tenant and installed per Section 506.1. Electronic card keys and codes may not be utilized as a substitute for manual keys.
When electronic locks release upon loss of electrical power or fire alarm activation a manual key need not be provided.
23.28.145 GATES—ADDED.¶
Section 506.1.1 "Locks" is amended to include subsection 506.1.1.2 "Gates" to read as shown below:
Where a new gate or barrier is installed on a fire access roadway, the fire department shall have emergency access. Gates or barriers shall have a wireless option for motorized gates or an approved key switch. Exception: R-3 occupancies
23.28.150 RECORDS REPORTING—ADDED.¶
Section 901.6.2 "Records" is amended to include subsection 901.6.2.2 "Records Reporting" to read as shown below:
Fire detection, alarm and extinguishing systems, shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Non-required fire protection systems and equipment shall be inspected, tested, and maintained or removed. All inspection, testing and maintenance reports shall be forwarded to the Fire Department using electronic media. No paper (hard copy) reports shall be permitted.
23.28.160 AUTOMATIC SPRINKLER SYSTEMS—WHERE REQUIRED—AMENDED.¶
Section 903.2 "Automatic Sprinkler Systems—Where Required" is amended to read as shown below:
Approved automatic sprinkler systems shall be installed throughout all new buildings unless the structure does not require a building permit. Exception: Detached Group U occupancies or carports less than 400 square feet.
23.28.170 NFPA 13R SPRINKLER SYSTEMS—AMENDED.¶
Section 903.3.1.2 "NFPA 13R sprinkler systems" is amended to read as shown below:
Automatic sprinkler systems in Group R occupancies shall be installed throughout in accordance with NFPA 13 as amended in Chapter 80. Exception:
- R-3 occupancies shall have an automatic sprinkler system installed in accordance with NFPA 13D.
23.28.180 AUTOMATIC SPRINKLER SYSTEMS—EXISTING BUILDINGS AND STRUCTURES—ADDED.¶
Section 903.2 "Where required" is amended to included subsection 903.2.20 "Automatic Sprinkler Systems—Additions, Alterations, or repairs" to read as shown below:
Proposed addition, alterations or repairs in existing non-sprinklered buildings over a three-year period exceeding 50% of the original gross floor area square footage shall require the entire building to be installed with an automatic fire sprinkler system. Buildings in existence as of January 1, 2017 shall install an automatic fire sprinkler system in existing buildings and structures, as follows;
(a) Any additions that increase the existing gross floor area by more than 50% require the entire building to be installed with an automatic fire sprinkler system.
(b) Any combination of additions, alterations and/or repairs to more than 50% of the existing gross building area requires the entire existing building to be installed with an automatic fire sprinkler system.
(c) Any alteration and/or repair within a building that contains an automatic fire sprinkler system shall have the automatic fire sprinkler system extended/modified to the area of proposed work.
(d) Any change in use or occupancy creating a more hazardous fire/life safety condition, as determined by the Fire Chief requires that an automatic fire sprinkler system be installed.
Exceptions:
Seismic or accessibility improvements.
Any exemption otherwise allowable under the Fire Code, as adopted by the City of San Mateo at the discretion of the Fire Chief.
Exterior improvements and work not requiring permits as provided in the Building Code.
Detached Group U occupancies or detached carports less than 400 square feet.
Work requiring only a mechanical, electrical, plumbing and/or demolition permit.
Group R-3.1 occupancies.
23.28.190 FIRE CONTROL ROOM—ADDED.¶
Section 903.4 "Sprinkler system supervisions and alarms" is amended to add subsection 903.4.4 "Fire Control Room" to read as shown below:
An approved fire control room shall be provided for all new buildings or occupancies with a change of use, requiring protection by an automatic fire sprinkler system. The room shall only contain all main system control valves, fire alarm control panels and other fire equipment required by the Fire Chief. Fire control rooms shall be located within the building at a location approved by the Fire Chief, and shall be provided with a means to access the room directly from the exterior. Durable signage shall be provided on the exterior side of the access door to identify the fire control room. Fire Control Rooms shall not be less than 35 square feet. Exceptions:
Group R, Division 3 Occupancies.
Occupancies with a fire pump shall have a fire control room that is a minimum of 200 square feet.
In high-rise buildings, the fire control room shall not be less than 200 square feet.
23.28.200 STANDPIPE SYSTEMS—REQUIRED INSTALLATIONS—AMENDED.¶
Section 905.3 "Required installations" is amended to read as shown below:
Standpipe systems shall be installed throughout buildings two or more stories and in basements and as required in Sections 905.3.1 through 905.3.11.2. Standpipe systems shall be combined with automatic sprinkler system and provided 2 1/2″ caps fitted with 1 1/2″ reducers. The Fire Chief shall determine the requirements for additional outlets.
23.28.210 FIRE ALARM CERTIFICATION—ADDED.¶
Section 907.1 "General" is amended to add subsection 907.1.6 "Fire Alarm Certification" to read as shown below:
Commercial fire alarm systems shall be certified by an approved certifying agency.
23.28.220 MIDRISE SMOKE CONTROL SYSTEMS—ADDED.¶
Section 909.1 is amended to add subsection 909.1.1 "Midrise Smoke Control Systems" to read as shown below:
The requirements of this section are intended to establish basic requirements for controlling the movement of smoke within a midrise building (smoke management system). Additional requirements for high-rise buildings shall be as specified in the CBC. This section shall apply to all buildings housing A, B, E, I and R and occupancies which meet any of the following conditions:
(a) Four (4) or more stories in height.
(b) Having occupied floors located more than 40 feet above grade at the lowest floor level of exit discharge.
Exceptions:
- Open parking garages.
23.28.230 CONVENIENCE STAIRWAYS—ADDED.¶
Section 1009.3 "Stairway" is amended to add subsection 1009.3.1 "Convenience Stairways" to read as shown below:
Convenience stairways (in buildings four or more stories in height) that are not required as exits shall be limited to connect only two (2) floors.
23.28.240 APPENDIX C, NUMBER AND DISTRIBUTION OF FIRE HYDRANTS—AMENDED.¶
Table C102.1 of Appendix C is amended to read as follows:
TABLE NO. C102.1 NUMBER AND DISTRIBUTION OF FIRE HYDRANTS
| FIRE FLOW REQUIREMENT (gpm)c | MINIMUM NUMBER OF HYDRANTS | AVERAGE SPACING BETWEEN HYDRANTS a,b,d, e (Ft.) | MAXIMUM DISTANCE FROM HYDRANT TO ANY POINT ON STREET OR ROADWAY FRONTAGE (Ft.) |
|---|---|---|---|
| 1750 or less | 1 | 250 | 150 |
| 2000 - 2250 | 2 | 250 | 150 |
| 2500 - 3250 | 3 | 250 | 150 |
| 3500 - 4250 | 4 | 250 | 150 |
| 4500 - 5250 | 5 | 250 | 150 |
| 5500 - 5750 | 6 | 250 | 150 |
| 6000 - 6250 | 6 | 250 | 150 |
| 6500 - 7250 | 7 | 250 | 150 |
| 7500 or more | 8 or more | 200 | 120 |
Footnotes to Table C102.1 are amended to read as follows:
a. Reduce by 100 feet for dead-end streets or roadways.
b. Hydrants shall be required on both sides of the street whenever one or more of the following conditions exist:
i. Street has a median center divider that makes access to hydrants difficult, causes a time delay or creates an undue hazard;
ii. There are four or more lanes of traffic;
iii. Width of the street is in excess of 88 feet; or
iv. The existing street will be widened or will have a raised median center divider installed in the future pursuant to the General Plan Roadway Improvement Plans for the City of San Mateo.
c. One hydrant for each 1,000 gpm or fraction thereof.
d. Where new water mains are extended along streets where hydrants are not needed for protection of structures or similar fire problems, fire hydrants should be provided every 1,000 feet of street to provide for transportation hazards. In addition, there shall be at least one hydrant at each intersection.
e. Average spacing between hydrants may be extended to 500 feet on streets serving one- and two-family dwellings.
23.28.250 VIOLATIONS.¶
It is unlawful to violate or fail to comply with any provisions of this code, or violate or fail to comply with any order made under this code or to build in violation of any detailed statement of specification or plans submitted and approved under this code, or any certificate or permit issued under this code.
23.28.260 FIRE AND LIFE SAFETY INSPECTIONS.¶
Inspections by the Fire Department shall periodically be made of buildings and structures that are used for residential or non-residential purposes as follows:
(a) The time and frequency of inspections shall be determined by the Fire Chief. No buildings shall be inspected for a fee more than annually except for re-inspections to assure that code corrections have been made or hazards have been corrected.
(b) A fee for inspections shall be established in the adopted City Fee Schedule to offset costs of the 2016 California Fire Code regulatory inspection program and shall be collected upon inspection from each property subject to this chapter. Revenues shall be used for the inspection and enforcement program.
(c) All properties shall be subject to inspection fees.
(d) Nothing in this section is intended to prevent inspections of property under nuisance abatement or other laws.