Chapter XXV — UNIFORM CODES

San Marino Municipal Code § 2305.5 Hold-down connectors

San Marino Municipal Code · 2026-10 edition · updated 2026-10-03 · San Marino

Cite as: San Marino Municipal Code § 2305.5 · Text as of 2026-10-03

25.02.18: ADDITION OF SECTION 1705.13.2:

Notwithstanding the provisions of section 25.02.01 of this article, section 1613.7 is added to the Building Code to read as follows:

1705.13.2 ASCE 7, Section 12.11.2.2.3. Modify ASCE 7, Section 12.11.2.2.3 to read as follows:

Exceptions & meaning →

25.02.19: ADDITION OF SECTION 1613.8:

Notwithstanding the provisions of section 25.02.01 of this article, section 1613.8 is added to the Building Code to read as follows:

Exceptions & meaning →

1613.8 Suspended Ceilings.

Minimum design and installation standards for suspended ceilings shall be determined in accordance with the requirements of Section 2506.2.1 of this Code and this section.

1613.8.1 Scope. This part contains special requirements for suspended ceilings and lighting systems. Provisions of Section 13.5.6 of ASCE 7-10 shall apply except as modified herein.

1613.8.2 General. The suspended ceilings and lighting systems shall be limited to 6 feet (1828 mm) below the structural deck unless the lateral bracing is designed by a licensed engineer or architect.

1613.8.3 Sprinkler Heads. All sprinkler heads (drops) except fire-resistance-rated floor/ceiling or roof/ceiling assemblies, shall be designed to allow for free movement of the sprinkler pipes with oversize rings, sleeves or adaptors through the ceiling tile. Sprinkler heads and other penetrations shall have a 2 in. (50mm) oversize ring, sleeve, or adapter through the ceiling tile to allow for free movement of at least 1 in. (25mm) in all horizontal directions. Alternatively, a swing joint that can accommodate 1 in. (25 mm) of ceiling movement in all horizontal directions is permitted to be provided at the top of the sprinkler head extension.

Sprinkler heads penetrating fire-resistance-rated floor/ceiling or roof/ceiling assemblies shall comply with Section 714 of this Code.

1613.8.4 Special Requirements for Means of Egress. Suspended ceiling assemblies located along means of egress serving an occupant load of 30 or more shall comply with the following provisions.

1613.8.4.1 General. Ceiling suspension systems shall be connected and braced with vertical hangers attached directly to the structural deck along the means of egress serving an occupant load of 30 or more and at lobbies accessory to Group A Occupancies. Spacing of vertical hangers shall not exceed 2 feet (610 mm) on center along the entire length of the suspended ceiling assembly located along the means of egress or at the lobby.

1613.8.4.2 Assembly Device. All lay-in panels shall be secured to the suspension ceiling assembly with two hold-down clips minimum for each tile within a 4-foot (1219 mm) radius of the exit lights and exit signs.

1613.8.4.3 Emergency Systems. Independent supports and braces shall be provided for light fixtures required for exit illumination. Power supply for exit illumination shall comply with the requirements of Section 1006.3 of this Code.

1613.8.4.4 Supports for Appendage. Separate support from the structural deck shall be provided for all appendages such as light fixtures, air diffusers, exit signs, and similar elements.

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-25-1423-U, 9-26-2026)

25.02.20: AMENDMENT OF SECTIONS 1705.3 AND TABLE 1705.3:

Notwithstanding the provisions of section 25.02.01 of this article, section 1705.3 and table 1705.3 of the Building Code are amended to read as follows:

Exceptions & meaning →

1705.3 Concrete Construction.

The special inspections and verifications for concrete construction shall be as required by this section and Table 1705.3.

Exceptions: Special inspection shall not be required for:

Isolated spread concrete footings of buildings three stories or less above grade plane that are fully supported on earth or rock, where the structural design of the footing is based on a specified compressive strength, f c, no greater than 2,500 pounds per square inch (psi) (17.2 Mpa) regardless of the compressive strength specified in the construction documents or used in the footing construction.

  1. Continuous concrete footings supporting walls of buildings three stories or less in height that are fully supported on earth or rock where:

2.1. The footings support walls of light-frame construction;

2.2. The footings are designed in accordance with Table 1805.4.2; or

2.3.

The structural design of the footing is based on a specified compressive strength, f c, no greater than 2,500 pounds per square inch (psi) (17.2 Mpa), regardless of the compressive strength specified in the construction documents or used in the footing construction.

  1. Nonstructural concrete slabs supported directly on the ground, including prestressed slabs on grade, where the effective prestress in the concrete is less than 150 psi (1.03 Mpa).

  2. Concrete patios, driveways and sidewalks, on grade.

TABLE 1705.3

REQUIRED VERIFICATION AND INSPECTION OF CONCRETE CONSTRUCTION

[Figure]

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-25-1423-U, 9-26-2026)

25.02.21: AMENDMENT OF SECTION 1705.12:

Notwithstanding the provisions of section 25.02.01 of this article, section 1705.13 of the Building Code is amended to read as follows:

1705.13 Special inspections for seismic resistance. Special inspections itemized in Sections 1705.13.1 through 1705.13.9, unless exempted by the exceptions of Section 1704.2, are required for the following:

  1. The seismic force-resisting systems in structures assigned to Seismic Design Category C, D, E or F in accordance with Sections 1705.13.1.1 through 1705.13.1.2, as applicable.

  2. Designated seismic systems in structures assigned to Seismic Design Category C, D, E or F in accordance with Section 1705.13.4.

  3. Architectural, mechanical and electrical components in accordance with Sections 1705.13.5.

  4. Storage racks in structures assigned to Seismic Design Category D, E or F in accordance with Section 1705.13.7.

  5. Seismic isolation systems in accordance with Section 1705.13.8.

Exception: Special inspections itemized in Sections 1705.13.1 through 1705.13.9 are not required for structures designed and constructed in accordance with one of the following:

  1. The structure consists of light-frame construction; the design spectral response acceleration at short periods, SDS, as determined in Section 1613.2.4, does not exceed 0.5; and the building height of the structure does not exceed 35 feet (10 668 mm).

  2. The seismic force-resisting system of the structure consists of reinforced masonry or reinforced concrete; the design spectral response acceleration at short periods, SDS, as determined in Section 1613.2.4, does not exceed 0.5; and the building height of the structure does not exceed 25 feet (7620 mm).

  3. The structure is a detached one- or two-family dwelling not exceeding two stories above grade plane, is not assigned to Seismic Design Category D, E or F and does not have any of the following horizontal or vertical irregularities in accordance with Section 12.3 of ASCE 7:

  • 3.1 Torsional or extreme torsional irregularity.

  • 3.2 Nonparallel systems irregularity.

  • 3.3 Stiffness-soft story or stiffness-extreme soft story irregularity.

  • 3.4 Discontinuity in lateral strength-weak story irregularity.

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-22-1400, 1-11-2023; Ord. O-25-1423-U, 9-26-2026)

Exceptions & meaning →

25.02.22: ADDITION OF SECTION 2304.10.4:

Notwithstanding the provisions of section 25.02.01 of this article, section 2304.10.4 is added to, and chapter 35 of the Building Code is amended, to read as follows:

General. The vertical load-bearing capacity, torsional moment capacity and deflection characteristics of joist hangers shall be determined in accordance with ASTM D 1761 and ASTM D 7147 as specified below using lumber having a specific gravity of 0.49 or greater, but not greater than 0.55, as determined in accordance with AWC NDS for the joist and headers.

Exception: The joist length shall not be required to exceed 24 inches (610 mm).

2304.10.4.1 Vertical load capacity for joist hangers. The vertical load-bearing capacity for the joist hanger shall be determined by testing a minimum of three joist hanger assemblies as specified in ASTM D 1761 or ASTM D 7147. If the ultimate vertical load for any one of the tests varies more than 20 percent from the average ultimate vertical load, at least three additional tests shall be conducted. The allowable vertical load-bearing of the joist hanger shall be the lowest value determined from the following:

  1. The lowest ultimate vertical load for a single hanger from any test divided by three (where three tests are conducted and each ultimate vertical load does not vary more than 20 percent from the average ultimate vertical load).

  2. The average ultimate vertical load for a single hanger from all tests divided by three (where six or more tests are conducted).

  3. The average from all tests of the vertical loads that produce a vertical movement of the joist with respect to the header of 1/8 inch (3.2 mm).

  4. The sum of the allowable design loads for nails or other fasteners utilized to secure the joist hanger to the wood members and allowable bearing loads that contribute to the capacity of the hanger.

  5. The allowable design load for the wood members forming the connection.

Amend the Reference Standards in Chapter 35 for ASTM as follows:

D 1761-88(2000) 1 Test Method for Mechanical Fasteners in Wood 1711.1.1 1711.1.2 1711.1.3
D 7147-05 Standard Specification for Testing and Establishing Allowable Loads of Joist Hangers 1711.1.1 1711.1.2

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-22-1400, 1-11-2023; Ord. O-25-1423-U, 9-26-2026)

Exceptions & meaning →

25.02.23: AMENDMENT OF SECTION 1807.1.4:

Notwithstanding the provisions of section 25.02.01 of this article, section 1807.1.4 of the Building Code is amended to read as follows:

1807.1.4 Permanent wood foundation systems. Permanent wood foundation systems shall be designed and installed in accordance with AF&PA PWF. Lumber and plywood shall be treated in accordance with AWPA Ul (Commodity Specification A, Use Category 4B and Section 5.2) and shall be identified in accordance with Section 2303.1.8.1. Permanent wood foundation systems shall not be used for structures assigned to Seismic Design Category D, E or F.

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-22-1400, 1-11-2023; Ord. O-25-1423-U, 9-26-2026)

Exceptions & meaning →

25.02.24: AMENDMENT OF SECTION 1807.1.6:

Notwithstanding the provisions of section 25.02.01 of this article, section 1807.1.6 of the Building Code is amended to read as follows:

1807.1.6 Prescriptive design of concrete and masonry foundation walls. Concrete and masonry foundation walls that are laterally supported at the top and bottom shall be permitted to be designed and constructed in accordance with this section. Prescriptive design of foundation walls shall not be used for structures assigned to Seismic Design Category D, E or F.

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-22-1400, 1-11-2023; Ord. O-25-1423-U, 9-26-2026)

Exceptions & meaning →

25.02.25: AMENDMENT OF SECTION 1809.3:

Notwithstanding the provisions of section 25.02.01 of this article, section 1809.3 of the Building Code is amended to read as follows:

Exceptions & meaning →

1809.3 Stepped footings.

The top surface of footings shall be level. The bottom surface of footings shall be permitted to have a slope not exceeding one unit vertical in 10 units horizontal (10-percent slope). Footings shall be stepped where it is necessary to change the elevation of the top surface of the footing or where the surface of the ground slopes more than one unit vertical in 10 units horizontal (10-percent slope).

For structures assigned to Seismic Design Category D, E or F, the stepping requirement shall also apply to the top surface of grade beams supporting walls. Footings shall be reinforced with four No. 4 rebar. Two bars shall be place at the top and bottom of the footings as shown in Figure 1809.3.

[Figure]

FIGURE 1809.3

STEPPED FOOTING

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-22-1400, 1-11-2023; Ord. O-25-1423-U, 9-26-2026)

25.02.26: AMENDMENT OF SECTION 1809.7 AND TABLE 1809.7:

Notwithstanding the provisions of section 25.02.01 of this article, section 1809.7 and table 1809.7 of the Building Code are amended to read as follows:

Exceptions & meaning →

1809.7 Prescriptive footings for light-frame construction.

Where a specific design is not provided, concrete or masonry-unit footings supporting walls of light-frame construction shall be permitted to be designed in accordance with Table 1809.7. Prescriptive footings in Table 1809.7 shall not exceed one story above grade plane for structures assigned to Seismic Design Category D, E or F.

TABLE 1809.7

PRESCRIPTIVE FOOTINGS SUPPORTING WALLS OF LIGHT-FRAME CONSTRUCTION a, b, c, d, e

NUMBER OF FLOORS SUPPORTED BY THE FOOTING f WIDTH OF FOOTING (inches) THICKNESS OF FOOTING (inches)
1 12 6
2 15 6
3 18 8 g

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm

a. Depth of footings shall be in accordance with Section 1809.4.

b. The ground under the floor shall be permitted to be excavated to the elevation of the top of the footing.

c. Not Adopted.

d. See Section 1908 for additional requirements for concrete footings of structures assigned to Seismic Design Category C, D, E or F.

e. For thickness of foundation walls, see Section 1807.1.6.

f. Footings shall be permitted to support a roof addition to the stipulated number of floors. Footings supporting roof only shall be as required for supporting one floor.

g. Plain concrete footings for Group R-3 occupancies shall be permitted to be 6 inches thick.

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-22-1400, 1-11-2023; Ord. O-25-1423-U, 9-26-2026)

25.02.27: AMENDMENT OF SECTION 1809.12:

Notwithstanding the provisions of section 25.02.01 of this article, section 1809.12 of the Building Code is amended to read as follows:

Exceptions & meaning →

1809.12 Timber footings.

Timber footings shall be permitted for buildings of Type V construction and as otherwise approved by the building official. Such footings shall be treated in accordance with AWPA Ul (Commodity Specification A, Use Category 4B). Treated timbers are not required where placed entirely below permanent water level, or where used as capping for wood piles that project above the water level over submerged or marsh lands. The compressive stresses perpendicular to grain in untreated timber footing supported upon treated piles shall not exceed 70 percent of the allowable stresses for the species and grade of timber as specified in the AF&PA NDS. Timber footings shall not be used in structures assigned to Seismic Design Category D, E or F.

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-22-1400, 1-11-2023; Ord. O-25-1423-U, 9-26-2026)

25.02.28: AMENDMENT OF SECTION 1810.3.2.4:

Notwithstanding the provisions of section 25.02.01 of this article, section 1810.3.2.4 of the Building Code is amended to read as follows:

1810.3.2.4 Timber. Timber deep foundation elements shall be designed as piles or poles in accordance with AF&PA NDS. Round timber elements shall conform to ASTM D 25. Sawn timber elements shall conform to DOC PS-20. Timber shall not be used in structures assigned to Seismic Design Category D, E or F.

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-22-1400, 1-11-2023; Ord. O-25-1423-U, 9-26-2026)

Exceptions & meaning →

25.02.29: AMENDMENT OF SECTION 1905.1.3:

Notwithstanding the provisions of section 25.02.01 of this article, section 1905.1.3 of the Building Code is amended to read as follows:

1905.1.3 ACI 318, Section 18.5. Modify ACI 318, Section 18.5, by renumbering Section 18.5.2.2 to become new Sections 18.5.2.2, 18.5.2.3, 18.5.2.4 and 18.5.2.5 to read as follows:

Exceptions & meaning →

25.02.30: AMENDMENT OF SECTION 1905.1.8:

Notwithstanding the provisions of section 25.02.01 of this article, section 1905.1.7 of the Building Code is amended to read as follows:

1905.1.7 ACI 318, Section 14.1.4. Delete ACI 318, Section 14.1.4, and replace with the following:

Exceptions & meaning →

1905.1 General.

The text of ACI 318 shall be modified as indicated in Sections 1905.1 through 1905.1.8

1905.1.9 ACI 318, Section 21.6.4. Modify ACI 318, Section 21.6.4, by adding Section 21.6.4.8 and 12.6.4.9 as follows:

Exceptions & meaning →

25.02.32: AMENDMENT OF SECTION 2304.10.2:

Notwithstanding the provisions of section 25.02.01 of this article, section 2304.10.1 of the Building Code is amended to read as follows:

2304.10.2 Fastener requirements. Connections for wood members shall be designed in accordance with the appropriate methodology in Section 2302.1. The number and size of fasteners connecting wood members shall not be less than that set forth in Table 2304.10.2. Staple fasteners in Table 2304.10.2 shall not be used to resist or transfer seismic forces in structures assigned to Seismic Design Category D, E or F.

Exception: Staples may be used to resist or transfer seismic forces when the allowable shear values are substantiated by cyclic testing and approved by the building official.

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-22-1400, 1-11-2023; Ord. O-25-1423-U, 9-26-2026)

Exceptions & meaning →

25.02.33: AMENDMENT OF SECTION 2304.12.2.8:

Notwithstanding the provisions of section 25.02.01 of this article, section 2304.12.5 of the Building Code is amended to read as follows:

2304.12.2.8 Wood used in retaining walls and cribs. Wood installed in retaining or crib walls shall be preservative treated in accordance with AWPA Ul (Commodity Specifications A or F) for soil and fresh water use. Wood shall not be used in retaining or crib walls for structures assigned to Seismic Design Category D, E or F.

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-22-1400, 1-11-2023; Ord. O-25-1423-U, 9-26-2026)

Exceptions & meaning →

25.02.34: ADDITION OF SECTION 2305.4:

Notwithstanding the provisions of section 25.02.01 of this article, section 2305.4 is added to the Building Code to read as follows:

Exceptions & meaning →

2305.4 Quality of Nails.

I23n Seismic Design Category D, E or F, mechanically driven nails used in wood structural panel shear walls shall meet the same dimensions as that required for hand-driven nails, including diameter, minimum length and minimum head diameter. Clipped head or box nails are not permitted in new construction. The allowable design value for clipped head nails in existing construction may be taken at no more than the nail-head-area ratio of that of the same size hand-driven nails.

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-22-1400, 1-11-2023; Ord. O-25-1423-U, 9-26-2026)

25.02.35: ADDITION OF SECTION 2305.5:

Notwithstanding the provisions of section 25.02.01 of this article, section 2305.5 is added to the Building Code to read as follows:

Exceptions & meaning →

2305.5 Hold-down connectors.

In Seismic Design Category D, E or F, hold-down connectors shall be designed to resist shear wall overturning moments using approved cyclic load values or 75 percent of the allowable seismic load values that do not consider cyclic loading of the product. Connector bolts into wood framing shall require steel plate washers on the post on the opposite side of the anchorage device. Plate size shall be a minimum of 0.229 inch by 3 inches by 3 inches (5.82 mm by 76 mm by 76 mm) in size. Hold-down connectors shall be tightened to finger tight plus one half (1/2) wrench turn just prior to covering the wall framing.

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-22-1400, 1-11-2023; Ord. O-25-1423-U, 9-26-2026)

25.02.36: AMENDMENT OF SECTION 2306.2:

Notwithstanding the provisions of section 25.02.01 of this article, section 2306.2 of the Building Code is amended to read as follows:

Exceptions & meaning →

2306.2 Wood-frame diaphragms.

Wood-frame diaphragms shall be designed and constructed in accordance with AF&PA SDPWS. Where panels are fastened to framing members with staples, requirements and limitations of AF&PA SDPWS shall be met and the allowable shear values set forth in Table 2306.2(1) or 2306.2(2) shall only be permitted for structures assigned to Seismic Design Category A, B, or C.

Exception: Allowable shear values where panels are fastened to framing members with staples may be used if such values are substantiated by cyclic testing and approved by the building official.

The allowable shear values in Tables 2306.2(1) and 2306.2(2) are permitted to be increased 40 percent for wind design.

Exception: [DSA-SS, DSA-SS/CC and OSHPD 1, 2 &4] Wood structural panel diaphragms using staples as fasteners are not permitted by DSA and OSHPD.

Wood structural panel diaphragms used to resist seismic forces in structures assigned to Seismic Design Category D, E or F shall be applied directly to the framing members.

Exception: Wood structural panel diaphragms are permitted to be fastened over solid lumber planking or laminated decking, provided the panel joints and lumber planking or laminated decking joints do not coincide.

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-22-1400, 1-11-2023; Ord. O-25-1423-U, 9-26-2026)

25.02.37: AMENDMENT OF SECTION 2306.3 AND ADDITION OF SECTION 2307.2:

Notwithstanding the provisions of section 25.02.01 of this article, section 2306.3 is amended and section 2307.2 is added to the Building Code to read as follows:

2306.3 Wood-frame shear walls.

Wood-frame shear walls shall be designed and constructed in accordance with AF&PA SDPWS. For structures assigned to Seismic Design Category D, E, or F, application of Tables 4.3A and 4.3B of AWC SDPWS shall include the following:

  1. Wood structural panel thickness for shear walls shall not be less than 3/8 inch thick and studs shall not be spaced at more than 16 inches on center.

  2. The maximum nominal unit shear capacities for 3/8 inch wood structural panels resisting seismic forces in structures assigned to Seismic Design Category D, E or F is 400 pounds per linear foot (plf).

Exception: Other nominal unit shear capacities may be permitted if such values are substantiated by cyclic testing and approved by the building official.

  1. Where shear design values using allow stress design (ASD) exceed 350 plf or load and resistance factor design (LRFD) exceed 500 plf, all framing members receiving edge nailing from abutting panels shall not be less than a single 3-inch nominal member, or two 2-inch nominal members fastened together in accordance with Section 2306.1 to transfer the design shear value between framing members. Wood structural panel joint and sill plate nailing shall be staggered at all panel edges. See Section 4.3.6.1 and 4.3.6.4.3 of AF&PA SDPWS for sill plate size and anchorage requirements.

  2. Nails shall be placed not less than 1/2 inch in from the panel edges and not less than 3/8 inch from the edge of the connecting members for shear greater than 350 plf using ASD or 500 plf using LRFD. Nails shall be placed not less than 3/8 inch from panel edges and not less than 1/4 inch from the edge of the connecting members for shears of 350 plf or less using ASD or 500 plf or less using LRFD.

  3. Table 4.3B application is not allowed for structures assigned to Seismic Design Category D, E, or F.

For structures assigned to Seismic Design Category D, application of Table 4.3C of AF&PA SDPWS shall not be used below the top level in a multi-level building for structures.

Where panels are fastened to framing members with staples, requirements and limitations of AF&PA SDPWS shall be met and the allowable shear values set forth in Table 2306.3(1), 2306.3(2) or 2306.3(3) shall only be permitted for structures assigned to Seismic Design Category A, B, or C.

Exception: Allowable shear values where panels are fastened to framing members with staples may be used if such values are substantiated by cyclic testing and approved by the building official.

The allowable shear values in Tables 2306.3(1) and 2306.3(2) are permitted to be increased 40 percent for wind design. Panels complying with ANSI/APA PRP-210 shall be permitted to use design values for Plywood Siding in the AF&PA SDPWS.

Exception: [DSA-SS 7DSA-SS/CC and OSHPD 1, 2 &4] Wood structural panel shear walls using staples as fasteners are not permitted by DSA and OSHPD.

2307.2 Wood-frame shear walls.

Wood-frame shear walls shall be designed and constructed in accordance with Section 2306.3 as applicable.

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-22-1400, 1-11-2023; Ord. O-25-1423-U, 9-26-2026)

25.02.38: ADDITION OF SECTION 2308.3.2:

Notwithstanding the provisions of Section 25.02.01 of this Article, Section 2308.3.2 is added to the Building Code to read as follows:

2308.3.2 Braced wall line support. Braced wall lines shall be supported by continuous foundations.

Exception: For structures with a maximum plan dimension not over 50 feet (15240 mm), continuous foundations are required at exterior walls only for structures assigned to Seismic Design Category A, B, or C.

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-22-1400, 1-11-2023; Ord. O-25-1423-U, 9-26-2026)

Exceptions & meaning →

25.02.39: AMENDMENT OF SECTIONS 2308.6.5 AND 2308.6.5.1:

Notwithstanding the provisions of section 25.02.01 of this article, sections 2308.6.5 and 2308.6.5.1, of the Building Code are amended to read as follows:

2308.6.5 Alternative bracing. Any bracing required by Section 2308.6.5 is permitted to be replaced by the following:

  1. In one-story buildings, each panel shall have a length of not less than 2 feet 8 inches (813 mm) and a height of not more than 10 feet (3048 mm). Each panel shall be sheathed on one face with 3/8-inch-minimum-thickness (9.5 mm) wood structural panel sheathing nailed with 8d common or galvanized box nails in accordance with Table 2304.10.1 and blocked at wood structural panel edges. For structures assigned to Seismic Design Category D or E, each panel shall be sheathed on one face with 15/32-inch-minimum-thickness (11.9 mm) wood structural panel sheathing nailed with 8d common nails spaced 3 inches on panel edges, 3 inches at intermediate supports. Two anchor bolts installed in accordance with Section 2308.3.1 shall be provided in each panel. Anchor bolts shall be placed at each panel outside quarter points. Each panel end stud shall have a tie-down device fastened to the foundation, capable of providing an approved uplift capacity of not less than 1,800 pounds (8006 N). The tie-down device shall be installed in accordance with the manufacturer's recommendations. The panels shall be supported directly on a foundation or on floor framing supported directly on a foundation that is continuous across the entire length of the braced wall line. This foundation shall be reinforced with not less than one No. 4 bar top and bottom.

Where the continuous foundation is required to have a depth greater than 12 inches (305 mm), a minimum 12-inch by 12-inch (305 mm by 305 mm) continuous footing or turned down slab edge is permitted at door openings in the braced wall line. This continuous footing or turned down slab edge shall be reinforced with not less than one No. 4 bar top and bottom. This reinforcement shall be lapped 15 inches (381 mm) with the reinforcement required in the continuous foundation located directly under the braced wall line.

  1. In the first story of two-story buildings, each wall panel shall be braced in accordance with Section 2308.6.5.1, Item 1, except that the wood

structural panel sheathing shall be provided on both faces, three anchor bolts shall be placed at one-quarter points, and tie-down device uplift capacity shall not be less than 3,000 pounds (13 344 N).

2308.6.5.1 Alternate bracing wall panel adjacent to a door or window opening. Any bracing required by Section 2308.6.5 is permitted to be replaced by the following when used adjacent to a door or window opening with a full-length header:

  1. In one-story buildings, each panel shall have a length of not less than 16 inches (406 mm) and a height of not more than 10 feet (3048 mm). Each panel shall be sheathed on one face with a single layer of 3/8 inch (9.5 mm) minimum thickness wood structural panel sheathing nailed with 8d common or galvanized box nails in accordance with Figure 2308.6.1. For structures assigned to Seismic Design Category D or E, each panel shall be sheathed on one face with 15/32-inch-minimum-thickness (11.9 mm) wood structural panel sheathing nailed with 8d common nails spaced 3 inches on panel edges, 3 inches at intermediate supports and in accordance with Figure 2308.9.3.2. The wood structural panel sheathing shall extend up over the solid sawn or glued-laminated header and shall be nailed in accordance with Figure 2308.8.3.1. A built-up header consisting of at least two 2 x 12s and fastened in accordance with Item 24 of Table 2304.9.1 shall be permitted to be used. A spacer, if used, shall be placed on the side of the built-up beam opposite the wood structural panel sheathing. The header shall extend between the inside faces of the first full-length outer studs of each panel. The clear span of the header between the inner studs of each panel shall be not less than 6 feet (1829 mm) and not more than 18 feet (5486 mm) in length. A strap with an uplift capacity of not less than 1,000 pounds (4,400 N) shall fasten the header to the inner studs opposite the sheathing. One anchor bolt not less than 5/8 inch (15.9 mm) diameter and installed in accordance with Section 2308.6 shall be provided in the center of each sill plate. The studs at each end of the panel shall have a tie-down device fastened to the foundation with an uplift capacity of not less than 4,200 pounds (18 480 N).

Where a panel is located on one side of the opening, the header shall extend between the inside face of the first full-length stud of the panel and the bearing studs at the other end of the opening. A strap with an uplift capacity of not less than 1,000 pounds (4400 N) shall fasten the header to the bearing studs. The bearing studs shall also have a tie-down device fastened to the foundation with an uplift capacity of not less than 1,000 pounds (4400 N).

The tie-down devices shall be an embedded strap type, installed in accordance with the manufacturer's recommendations. The panels shall be supported directly on a foundation that is continuous across the entire length of the braced wall line. This foundation shall be reinforced with not less than one No. 4 bar top and bottom.

Where the continuous foundation is required to have a depth greater than 12 inches (305 mm), a minimum 12-inch by 12-inch (305 mm by 305 mm) continuous footing or turned down slab edge is permitted at door openings in the braced wall line. This continuous footing or turned down slab edge shall be reinforced with not less than one No. 4 bar top and bottom. This reinforcement shall be lapped not less than 15 inches (381 mm) with the reinforcement required in the continuous foundation located directly under the braced wall line.

  1. In the first story of two-story buildings, each wall panel shall be braced in accordance with Item 1 above, except that each panel shall have a length of not less than 24 inches (610 mm).

(Ord. 0-19-1357, 11-13-2019; Ord. O-25-1423-U, 9-26-2026)

Exceptions & meaning →

25.02.40: AMENDMENT OF TABLE 2308.10.1:

Notwithstanding the provisions of section 25.02.01 of this article, table 2308.6.1 of the Building Code is amended to read as follows:

TABLE 2308.10.1WALL BRACING IN SEISMIC DESIGN CATEGORIES D AND E(Minimum Percentage of Wall Bracing per each Braced Wall Linea)

CONDITION SHEATHING TYPEb SDS < 0.50 0.50 < SDS < 0.75 0.75 < SDS < 1.00 SDS > 1.00
One Story G-Pc 43 59 75 100
One Story S-wD 21 32 37 48

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

a. Minimum length of panel bracing of one face of the wall for S-W sheathing shall be at least 4'-0" long or both faces of the wall for G-P sheathing shall be at least 8'-0" long; h/w ratio shall not exceed 2:1. For S-W panel bracing of the same material on two faces of the wall, the minimum length is permitted to be one-half the tabulated value but the h/w ratio shall not exceed 2:1 and design for uplift is required. The 2:1 h/w ratio limitation does not apply to alternate braced wall panels constructed in accordance with Section 2308.10.2. Wall framing to which sheathing used for bracing is applied shall be nominal 2 inch wide [actual 11/2 inch (38 mm)] or larger members and spaced a maximum of 16 inches on center. Braced wall panel construction types shall not be mixed within a braced wall line.

b. G-P = gypsum board, portland cement plaster or gypsum sheathing boards; S-W = wood structural panels;

c. Nailing as specified below shall occur at all pane! edges at studs, at top and bottom plates and, where occurring, at blocking:

For 1/2-inch gypsum board, 5d (0.113 inch diameter) cooler nails at 7 inches on center; For 5/8-inch gypsum board, No. 11 gage (0.120 inch diameter) cooler nails at 7 inches on center; For gypsum sheathing board, 1-3/4 inches long by 7/16-inch head, diamond point galvanized nails at 4 inches on center;

For gypsum lath, No. 13 gage (0.092 inch) by 1-1/8 inches long, 19/64-inch head, plasterboard at 5 inches on center;

For Portland cement plaster, No. 11 gage (0.120 inch) by 11/2 inches long, 7/16- inch head at 6 inches on center;

d. S-W sheathing shall be a minimum of 15/32" thick nailed with 8d common placed 3/8 inches from panel edges and spaced not more than 6 inches on center and 12 inches on center along intermediate framing members.

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-22-1400, 1-11-2023; Ord. O-25-1423-U, 9-26-2026)

Exceptions & meaning →

25.02.41: AMENDMENT OF SECTION 2308.6.9:

Notwithstanding the provisions of section 25.02.01 of this article, section 2308.6.9 of the Building Code is amended to read as follows:

2308.6.9 Attachment of sheathing. Fastening of braced wall panel sheathing shall not be less than that prescribed in Table 2308.6.1 and 2304.10.1. Wall sheathing shall not be attached to framing members by adhesives. Staple fasteners in Table 2304.10.1 shall not be used to resist or transfer seismic forces in structures assigned to Seismic Design Category D, E or F.

Exception: Staples may be used to resist or transfer seismic forces when the allowable shear values are substantiated by cyclic testing and approved by the building official.

All braced wall panels shall extend to the roof sheathing and shall be attached to parallel roof rafters or blocking above with framing clips (18 gauge minimum) spaced at maximum 24 inches (6096 mm) on center with four 8d nails per leg (total eight 8d nails per clip). Braced wall panels shall be laterally braced at each top corner and at maximum 24 inches (6096 mm) intervals along the top plate of discontinuous vertical framing.

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-22-1400, 1-11-2023 ; Ord. O-25-1423-U, 9-26-2026)

Exceptions & meaning →

25.02.42: ADDITION OF SECTION 3109.2.1:

Notwithstanding the provisions of section 25.02.01 of this article, section 3109.2.1 is added to the Building Code to read as follows:

3109.2.1 Driveway Gates. Driveway gates serving as part of the required pool barrier shall comply with the following:

  1. Driveway gates, if operated manually, shall have a spring-loaded, self-closing, self-latching mechanism installed in accordance with the same procedure required in the City Building Code for pedestrian gates.

  2. Driveway gates may be equipped with an electric gate-operating device provided that it is approved by a recognized Electrical Testing Agency.

  3. Electric gate-operating devices shall be provided with a safety mechanism to interrupt and recycle the device, should the gate become blocked.

  4. Electric gate-operating devices shall be provided with a time delay closing device, which is set and maintained to activate a maximum of 30 seconds after the gate has been opened.

(Ord. 0-19-1357, 11-13-2019; amd. Ord. O-22-1400, 1-11-2023 ; Ord. O-25-1423-U, 9-26-2026)