San Francisco Fire Code § 507.6 Other Water Supplies
San Francisco Fire Code · 2026-08 edition · updated 2026-10-23 · San Francisco
Cite as: San Francisco Fire Code § 507.6 · Text as of 2026-10-23
Water tanks or pools within, on or about any building premises shall be connected with approved 6-inch (152 mm) pipe leading from the bottom of the tank to a point designated by the fire code official. Piping for tanks located at or below grade shall be designed and installed for drafting by Fire Department apparatus.
Exceptions:
Industrial process water tanks.
Tanks or pools with a capacity of less than 75,000 gallons (94.6 m3) 1.
Tanks or pools used to supply automatic fire sprinkler systems.
Water tanks or pools installed in R3 Occupancies.
CODIFICATION NOTE
- So in Ord. 39-26.