12.8-5 and 12.8-6.

b) Stiffness properties of non-prestressed concrete elements shall not exceed 0.5 times gross-section properties. c) Foundation flexibility shall be considered, using recommendations provided by the Geotechnical Engineer of Record that are defined in the Seismic Design Criteria. d) The analysis shall account for P-delta effects.

Commentary: ASCE/SEI 7-16 requires the consideration of the minimum base shear of Eq. 12.8-5 and 12.8-6 for checking design story drifts relative to allowable story drifts. However, the consensus of SEAONC’s AB-083 Task Group for this Administrative Bulletin, approved by the SEAONC Board, is that UBC Formula 30-7 (equivalent to ASCE/SEI 7-16 Eq. 12.8-6) need not be applied to the check of drift limits for tall buildings designed according to this bulletin, because the MCER-level Evaluation of Section 4.3 includes a check of drift for site-specific ground motions. Such ground motions are required to take account of near-fault and directivity effects. The consensus of the task group is that this is an appropriate and more explicit way of addressing the intended purpose of applying Formula 30-7 to the check of drift limits. Actual concrete stiffness properties may vary significantly from the value of 0.5 times gross-section properties referenced for the code-level check of story drift limits. This assumption is specified to provide a consistent requirement for minimum building stiffness. This requirement is intended to lead to earthquake serviceability performance related to story drift that is at least comparable to that expected of prescriptively-designed tall buildings designed to the San Francisco Building Code. For the deformation compatibility evaluation of critical non-structural elements, such as exterior curtain wall and cladding systems and egress stairways, the drift ratio demand shall be calculated using the minimum base shear limitations of ASCE/SEI 7-16 Eq. 12.8-5 and 12.8-6. In lieu of this requirement, these critical non-structural elements may be designed for drift ratios at the MCER-level .

Exceptions & meaning →

Get a plain-English answer with a citation back to this text.

Ask AI about this code
▸Contents — San Francisco County Municipal Code

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.