Title 9 — CONSTRUCTION CODES AND FIRE CODE›Division 6 — FIRE PROTECTION›Chapter 1 — COUNTY FIRE CODE
§ 2808.7
San Diego County Municipal Code · 2026-09 edition · updated 2026-10-02 · San Diego County
Sec. 2808.7.1 Public water supply. The operator shall provide and maintain approved…¶
as required by the fire code official. Water lines may be approved aboveground lines supplied from a reliable water supply with adequate protection against impact and fire flow reaction. Hydrant spacing shall be at 400-foot intervals along primary fire access roadways. Fire flow at each hydrant shall be least 1000 gallons per minute at 20 psi. Duration of the required fireflow shall be as determined by the fire code official.
Sec. 2808.7.2 Private water supply. Above-ground water storage tanks may be installed…¶
code official where public water supply is not adequate to meet fire flow requirements. Volume and duration of the required fireflow shall be as determined by the fire code official.
Get a plain-English answer with a citation back to this text.
Ask AI about this code