15.44.010 - Adoption of the 2025 California Fire Code.

There is hereby adopted by reference that certain code known and designated as the California Code of Regulations, Title 24, Part 9, further described and referred to as the 2025 California Fire Code published by the California Building Standards Commission and based on the International Fire Code;, 2024 Edition, prepared by the International Code Council, including Appendix Chapters B and C, save and except such portions as are hereinafter deleted, modified, or amended by this chapter. Such code shall be and become the Morgan Hill Fire Code, regulating and governing the safeguarding of life and property from fire and explosion hazards arising from the storage, handling, and use of hazardous substances, materials, and devices, and from conditions hazardous to life or property in the occupancy of buildings and premises in the City of Morgan Hill.

One (1) copy of the code shall be kept on file at all times in the office of the city building official and the administrative offices of the Morgan Hill Fire Department for use and examination by the public.

(Ord. No. 2368 N.S., § 5, 11-19-2025)

15.44.015 - Adoption of appendix chapters.

The following Appendix Chapters from the 2025 California Fire Code are hereby adopted:

Appendix B: Fire Flow Requirements for Buildings.

Appendix C: Fire Hydrant Locations and Distribution.

Appendix D: Fire Apparatus Access Roads

(Ord. No. 2368 N.S., § 5, 11-19-2025)

15.44.020 - Short Title; International Fire Code and California Fire Code Defined.

This chapter shall be known as the "Fire Code" and may be cited as such. Whenever the phrase "International Fire Code" appears in this code or any ordinance of the city, such phrase shall be deemed and construed to refer to and apply to the International Fire Code, 2024 Edition, as adopted and amended by this chapter. Whenever the phrase "California Fire Code" appears in this code or any ordinance of the city, such phrase shall be deemed and construed to refer to and apply to the 2025 California Fire Code, as adopted and amended by this chapter. Sections amended or modified in this chapter shall refer to the sections of the California Fire Code unless otherwise specified.

15.44.030 - Establishment and duties of bureau of fire prevention.

The California Fire Code and International Fire Code shall be enforced by the bureau of fire prevention in the Morgan Hill Fire Department, which shall be operated under the supervision of the chief of the fire department.

(Ord. No. 2368 N.S., § 5, 11-19-2025)

15.44.040 - Modification of provisions by chief.

A.

The Chief of the Morgan Hill Fire Department shall have power to modify any of the provisions of the fire code upon application in writing by the owner or lessee, or their duly authorized agent, when there are practical difficulties in the way of carrying out the strict letter of the codes, provided that the spirit of the codes shall be observed, public safety secured, and substantial justice done.

B.

The particulars of such modification, when granted or allowed, and the decision of the chief shall be entered in the records of the fire department and a signed copy shall be furnished to the applicant for modification.

(Ord. No. 2368 N.S., § 5, 11-19-2025)

15.44.050 - Establishment of limits of districts.

A.

Storage of stationary tanks of flammable cryogenic fluids are to be prohibited. The limits referred to in Section 5806.2 of the 2025 California Fire Code, in which the storage of flammable cryogenic fluids in stationary containers is prohibited, are hereby established as to all locations of the City of Morgan Hill which are residential and congested commercial areas as determined by the fire code official.

B.

Storage of Class I and II liquids in outside aboveground tanks is prohibited. The limits referred to in Section 5704.2.9.6.1 of the 2025 California Fire Code, in which the storage of flammable or combustible liquids in aboveground tanks is prohibited, are hereby established as to all locations of the City of Morgan Hill that are residential or congested commercial areas as determined by the fire code official.

C.

Storage of Class I and II liquids in aboveground tanks is prohibited. The limits referred to in Section 5706.2.4.4 of the 2025 California Fire Code, in which the storage of flammable or combustible liquids in aboveground tanks is prohibited, are hereby established as to all locations of the City of Morgan Hill that are residential or other locations as determined by the fire code official.

D.

Storage of liquefied petroleum gases ("LPG") is prohibited. The limits referred to in Section 6104.2 of the 2025 California Fire Code, in which storage of liquefied petroleum gas is restricted, are hereby established as to all locations of the City of Morgan Hill that are residential or congested commercial areas as determined by the fire code official.

Exceptions: LPG may be used for industrial operations or when natural gas is not available or would not provide a viable substitute for LPG. Portable containers for temporary heating and/or cooking uses may be permitted if stored and handled in accordance with this code. Facilities in commercial areas for refueling portable or mobile LPG containers may be approved by the fire code official on a case by case basis.

(Ord. No. 2368 N.S., § 5, 11-19-2025)

15.44.060 - Additions, amendments, and deletions.

A.

In accordance with California Health and Safety Code Section 17958.7, certain modifications to the California Fire Code as set forth in this Chapter are reasonably necessary because of local climatic, geologic, or topographical conditions.

B.

Climatic Conditions. Santa Clara County and the City of Morgan Hill are located in a semi-arid Mediterranean type climate which predisposes all fuels to rapid ignition and spread of fire. Hot, dry winds, and low humidities, are common to all areas within the City of Morgan Hill and Santa Clara County in general. Winter rains promote the growth of grass and brush. This vegetation presents heavy dry fuel loads in the summer months. These conditions are conducive to the ready ignition, propagation and spread of grass, brush and structure fires. These conditions, which can cause small brush fires which spread quickly,

are a contributing factor to the high fire danger in the area, and create the need for an increased level of fire protection. This added protection will supplement normal fire department response available and provide immediate protection for life and safety of multiple occupancy occupants during fire occurrences.

C.

Topographic Conditions. The topography of Morgan Hill has hillside homes on each side of the city with long response times for safety equipment. The City foothills cause many problems for firefighters, including long response times, inadequate water supply and unlimited fuel. Fog, heavy rains, mudslides and earthquakes are other common occurrences which negatively affect the ability of the city's public safety resources to respond to emergency situations. The City is in a Category D seismic activity classification. Many traffic corridors such as Highway 101 and Monterey Road, Southern Pacific Railroad, related bridges, underpasses and crossings are subject to obstruction in the event of an earthquake, traffic accident, hazardous material spill or other disaster.

D.

Geographic Conditions.

1.

Santa Clara County and the City of Morgan Hill are located within the seismically active San Francisco Bay region. The significant earthquakes in the region are generally associated with the crustal movements along well-defined, active fault zones. The nearest known active faults are the San Andreas Fault, approximately 12 miles southwest of Morgan Hill, and the Calaveras Fault, approximately 1 mile northeast. Both faults have produced major earthquakes in the past, and have estimated maximum credible Richter magnitudes of 8.3 and 7.3, respectively. The Sargent-Berrocal Fault, a potentially active fault, lies approximately 10 miles away and has an estimated maximum credible Richter magnitude of 7.3. The Coyote Creek Fault is located in Morgan Hill and is classified as potentially active as well. In addition, several unnamed faults traverse the western slopes of the upland areas.

2.

Regional planning for reoccurrence is recommended by the State of California, Department of Conservation. The October 17, 1989, Santa Cruz earthquake resulted in only one major San Francisco fire in the Marina district, but when combined with the 34 other fires and over 500 responses, the department was taxed to its full capabilities. The Marina fire was difficult to contain because mains supplying water to the district burst during the earthquake. If more fires had been ignited by the earthquake, it would have been difficult for the fire department to contain them. Experts predict a major earthquake in our area within the next 50 years. This situation creates the need for both additional fire protection measures and automatic on-site fire protection for building occupants since a multitude of fires may result from breakage of gas lines and electric lines as a result of an earthquake.

3.

Traffic and circulation congestion presently existing in the City of Morgan Hill often places fire department response time to fire occurrences at risk. This condition will be exacerbated by any major disaster,

including any earthquake where damage to the highway system will occur. This condition makes the need for additional on-site protection for property occupants necessary.

4.

The City of Morgan Hill is located in an area subject to a climatic condition of high winds and low humidity. This combination of events creates an environment which is conducive to rapidly spreading fires. Control of such fires requires rapid response. Obstacles generated by a strong wind, such as fallen trees, street lights and utility poles greatly impact the response time to reach an incident scene.

5.

The City of Morgan Hill is located in the middle of a seismically active area. The viability of the public water system would be questionable at best after a major seismic event. A severe seismic event has the potential to negatively impact any rescue or fire suppression activities because it is likely to create obstacles similar to those indicated under the high wind section above. With the probability of strong aftershocks, there exists a need to provide increased protection for anyone on upper floors.

6.

The City of Morgan Hill is located approximately sixteen (16) miles from the ocean. The City's typical ground water level is between ten (10) and twenty (20) feet. This condition makes the City more prone to subsidence issues than most inland communities.

(Ord. No. 2368 N.S., § 5, 11-19-2025)

15.44.070 - Scope and general requirements.

A.

Section 101.1 of the 2025 California Fire Code is hereby amended to read in its entirety:

[A] I01.1 Title. These regulations shall be known as the Fire Code of Morgan Hill, hereinafter referred to as "this code."

(Ord. No. 2368 N.S., § 5, 11-19-2025)

15.44.80 - Chapter 2—Definitions.

A.

The following definitions in Section 202 of the 2025 California Fire Code is hereby added to read:

CORROSIVE LIQUID. Corrosive liquid is

1)

any liquid which, when in contact with living tissue, will cause destruction or reversible alteration of such tissue by chemical action; or

any liquid having a pH of 2 or less or 12.5 or more; or

3)

any liquid classified as corrosive by the U.S. Department of Transportation; or

4)

any material exhibiting the characteristics of corrosivity in accordance with Title 22, California Code of Regulations §66261.22.

MODERATELY TOXIC GAS. A chemical or substance that has a median lethal concentration (LC50) in air more than 2000 parts per million but not more than 5000 parts per million by volume of gas or vapor, when administered by continuous inhalation for an hour, or less if death occurs within one hour, to albino rats weighing between 200 and 300 grams each.

HEALTH HAZARD-OTHER. A hazardous material which affects target organs of the body, including but not limited to, those materials which produce liver damage, kidney damage, damage to the nervous system, act on the blood to decrease hemoglobin function, deprive the body tissue of oxygen or affect reproductive capabilities, including mutations (chromosomal damage), sensitizers or teratogens (effect on fetuses).

SECONDARY CONTAINMENT. Secondary containment is that level of containment that is external to and separate from primary containment and is capable of safely and securely containing the material, without discharge, for a period of time reasonably necessary to ensure detection and remedy of the primary containment failure.

SPILL CONTROL. That level of containment that is external to and separate from the primary containment and is capable of safely and securely containing the contents of the largest container and prevents the materials from spreading to other parts of the room.

WORKSTATION. A defined space or an independent principal piece of equipment using flammable or unstable (Class 3 or 4 as ranked by NFPA 704) hazardous materials where a specific function, laboratory procedure or research activity occurs. Approved or listed hazardous materials storage cabinets, flammable liquid storage cabinets, or gas cabinets serving a workstation are included as part of the workstation. A workstation is allowed to contain ventilation equipment, fire protection devices, detection devices, electrical devices and other processing and scientific equipment.

(Ord. No. 2368 N.S., § 5, 11-19-2025)

15.44.90 - Chapter 5—Fire Service Features.

A.

Section 503.1 of the 2025 California Fire Code is hereby amended to read in its entirety:

503.1 Where required. Fire apparatus access roads shall be provided and maintained in accordance with Sections 503.1.1 through 503.1.3 and in accordance with Appendix D and comply with the Fire Department Standard Details and Specifications.

B.

Section 503.2.1 of the 2025 California Fire Code is hereby amended to read in its entirety:

503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 20 feet (6096 mm) for engines, and 26 feet (7925 mm) for aerial fire apparatus exclusive of shoulders, except for approved gates or barricades in accordance with Sections 503.5.1 and 503.6. The unobstructed vertical clearance shall be a minimum of 13 feet 6 inches (4115 mm), or as determined by the fire code official.

C.

Section 503.2.4 of the 2025 California Fire Code is hereby amended to read in its entirety:

503.2.4 Turning radius. The required turning radius of a fire apparatus access road shall be a minimum of 30 feet (9144 mm) inside, and a minimum of 50 feet (15240 mm) outside.

D.

Section 503.2.7 of the 2025 California Fire Code is hereby amended to read in its entirety:

503.2.7 Grade. The maximum grade of a fire apparatus access road shall not exceed 15-percent, unless approved by the fire code official

E.

Section 503.5 of the 2025 California Fire Code is hereby amended to read in its entirety:

503.5 Required gates or barricades. The fire code official is authorized to require the installation and maintenance of gates or other approved barricades across fire apparatus access roads, trails, or other accessways, not including the public streets, alleys, or highways. The minimum width shall be 12 feet (4268 mm) for single-family dwellings and 20 feet (6096 mm) for all others. Electric gate operators, where provided shall be listed in accordance with UL 325. Gates intended for automatic operation shall be designed, constructed, and installed to comply with the requirements of ASTM F2200

F.

Section 503.6 of the 2025 California Fire Code is hereby amended to read in its entirety:

503.6 Security gates. The installation of security gates across a fire apparatus access road shall be approved by the fire code official. Where security gates are installed, they shall have an approved means of emergency operation. The security gates and the emergency operation shall be maintained operational at all times. Electric gate operators, where provided, shall be listed in accordance with UL 325. Gates intended for automatic operation shall be designed, constructed and installed to comply with the requirements of ASTM F2200. The minimum width shall be 12 feet (4268 mm) for single-family dwellings and 20 feet (6096 mm) for all others.

(Ord. No. 2368 N.S., § 5, 11-19-2025)

15.44.100 - Chapter 9—Fire Protection Systems.

A.

Section 903.2 of the 2025 California Fire Code is hereby amended to read in its entirety:

903.2 Where required. Approved automatic sprinkler systems in new and existing buildings and structures shall be provided in the locations described in this Section or in Sections 903.2.1 through 903.2.12 and Sections 903.2.14 through 903.2.21, whichever is the more restrictive. For the purposes of this section, firewalls and fire barriers used to separate building areas shall be constructed in accordance with the California Building Code and shall be without openings or penetrations.

1.

An automatic sprinkler system shall be provided throughout all new buildings and structures, other than Group R occupancies, greater than 1,200 square feet of building area.

Exceptions:

a.

Group S-2 or U occupancies, including photovoltaic support structures, used exclusively for vehicle parking which meet all of the followings:

i.

Noncombustible construction;

ii.

Maximum building areas not to exceed 5,000 square feet;

iii.

Structure is open on three (3) or more sides; and

iv.

Minimum of 10 feet separation from property line and existing buildings, or similar structures, unless area is separated by fire walls.

2.

An automatic sprinkler system shall be installed throughout all new buildings with a Group R fire area.

Exception:

a.

Accessory Dwelling Unit (ADU), provided that all of the following are met:

i.

The unit meets the definition of an Accessory Dwelling Unit as defined in the Government Code Section 65852.2.

ii.

The existing primary residence does not have automatic fire sprinklers.

iii.

The accessory detached dwelling unit does not exceed 1,200 square feet in size.

iv.

The unit is on the same lot as the primary residence.

v.

The unit meets all apparatus access and water supply requirements of Chapter 5 and Appendix B of the 2025 California Fire Code

3.

An automatic sprinkler system shall be provided throughout existing Group A, B, E, F, I L, M, R, S and U buildings and structures, when additions are made that increase the building area by more than 1,200 square feet or where the resulting area exceeds 3,600 square feet.

4.

An automatic sprinkler system shall be provided throughout all new basements regardless of size and throughout existing basements that are expanded by more than 50%.

5.

Any change in the character of occupancy or in use of any building which, in the opinion of the City fire code official or building official, would place the building into a more hazardous division of the same occupancy group or into a different group of occupancies and constitutes a greater degree of life safety[1 ] or increased fire risk[2 ] , shall require the installation of an approved fire automatic fire sprinkler system.

1 Life Safety—Increased occupant load, public assembly areas, public meeting areas, churches, indoor amusement attractions, buildings with complex exiting systems due to increased occupant loads, large schools/daycare facilities, large residential care facilities with non ambulatory.

2 Fire Risks—High-piled combustible storage, woodworking operations, hazardous operations using hazardous materials, increased fuel loads (storage of moderate to highly combustible materials), increased sources of ignition (welding, automotive repair with use of flammable liquids and open flames).

(Ord. No. 2368 N.S., § 5, 11-19-2025)

15.44.110 - Chapter 33—Fire Safety During Construction and Demolition.

A.

Section 3307.1 is hereby added to read:

3307.1 Required Access: All construction sites shall be accessible by fire department apparatus by means of roadways having an all-weather driving service of not less than 20ft. of unobstructed width. The roads shall have the ability to withstand the live loads of a 75,000 pound fire apparatus, and have a minimum 13ft. 6 in. of vertical clearance. Dead end fire access roads in excess of 150 ft. in length shall be provided with approved turnarounds.

be accessible by fire department apparatus by means of roadways having an all-weather driving service of not less than 20ft. of unobstructed width. The roads shall have the ability to withstand the live loads of a 75,000 pound fire apparatus, and have a minimum 13ft. 6 in. of vertical clearance. Dead end fire access roads in excess of 150 ft. in length shall be provided with approved turnarounds.

When approved by the Fire Code Official, temporary access roadways may be utilized until such time that the permanent roadways are installed. As a minimum, the roadway shall consist of a compacted sub base and eight (8") inches of road base material (Class 2 aggregate base rock) both compacted to a minimum 95%. The perimeter edges of the roadway shall be contained and delineated by curb and gutter or other approved method. The use of geotextile reinforcing fabric underlayment or soils lime-treatment may be required if so determined by the project civil engineer. Provisions for surface drainage shall also be provided where necessary. The integrity of the roadway shall be maintained at all times.

(Ord. No. 2368 N.S., § 5, 11-19-2025)

15.44.120 - Chapter 50—Hazardous Materials—General Provisions.

A.

Section 5001.2.2.2 of the 2025 California Fire Code is hereby amended to read in its entirety:

5001.2.2.2 Health hazards. The material categories listed in this section are classified as health hazards. A material with a primary classification as a health hazard can also pose a physical hazard.

1.

Highly toxic and toxic materials.

2.

Corrosive materials.

3.

Moderately toxic gas.

4.

Health hazards-Other.

B.

Section 5003.2.2.1 of the 2025 California Fire Code is hereby amended to read in its entirety:

5003.2.2.1 Design and construction. Piping, tubing, valves, fittings and related components used for hazardous materials shall be in accordance with the following:

1.

Piping, tubing, valves, fittings, and related components shall be designed and fabricated from materials compatible with the material to be contained and shall be of adequate strength and durability to withstand the pressure, structural and seismic stress, and exposure to which they are subject.

2.

Piping and tubing shall be identified in accordance with ASME A13.1 and Santa Clara County Fire Chiefs Marking Requirements and Guidelines for Hazardous Materials and Hazardous Waste to indicate the material conveyed.

3.

Readily accessible manual valves or automatic remotely activated fail-safe emergency shutoff valves shall be installed on supply piping and tubing at the following locations:

3.1

The point of use.

3.2

The tank, cylinder or bulk use.

4.

Manual emergency shutoff valves and controls for remotely activated emergency shutoff valves shall be identified and the location shall be clearly visible accessible and indicated by means of a sign.

5.

Backflow prevention or check valves shall be provided when the backflow of hazardous materials could create a hazardous condition or cause the unauthorized discharge of hazardous materials.

6.

Where gases or liquids having a hazard ranking of Health hazard Class 3 or 4, Flammability Class 4, or Reactivity Class 4 in accordance with NFPA 704 are carried in pressurized piping above 15 pounds per square inch gauge (psig)(103 Kpa), an approved means of leak detection, emergency shutoff and excess flow control shall be provided. Where the piping originates from within a hazardous material storage room or area, the excess flow control shall be located within the storage room or area. Where the piping originates from a bulk source, the excess flow control shall be located as close to the bulk source as practical.

Exceptions:

1.

Piping for inlet connections designed to prevent backflow.

Piping for pressure relief devices.

7.

Secondary containment or equivalent protection from spills shall be provided for piping for liquid hazardous materials and for highly toxic and toxic corrosive gases above threshold quantities listed in Tables 6004.2.1.4. Secondary containment includes but is not limited to double walled piping.

Exceptions:

1.

Secondary containment is not required for toxic corrosive gases if the piping is constructed of inert materials.

2.

Piping under sub-atmospheric conditions if the piping is equipped with an alarm and fail-safe-to-close valve activated by a loss of vacuum.

8.

Expansion chambers shall be provided between valves whenever the regulated gas may be subjected to thermal expansion. Chambers shall be sized to provide protection for piping and instrumentation and to accommodate the expansion of regulated materials.

C.

Section 5003.2.2.2 of the 2025 California Fire Code is hereby amended to read in its entirety:

5003.2.2.2 Additional regulation for supply piping for health hazard materials. Supply piping and tubing for gases and liquids having a health hazard ranking of 3 or 4 shall be in accordance with ASME B31.3 and the following:

1.

Piping and tubing utilized for the transmission of toxic, highly toxic, or highly volatile corrosive liquids and gases shall have welded, or brazed connections throughout except for connections within an exhausted enclosure if the material is a gas, or an approved method of drainage or containment is provided for connections if the material is a liquid.

2.

Piping and tubing shall not be located within corridors, within any portion of a means of egress required to be enclosed in fire-resistance-rated construction or in concealed spaces in areas not classified as Group H Occupancies.

All primary piping for toxic, highly toxic and moderately toxic gases shall pass a helium leak test of 1x10-9 cubic centimeters/second where practical, or shall pass testing in accordance with an approved, nationally recognized standard. Tests shall be conducted by a qualified "third party" not involved with the construction of the piping and control systems.

D.

Section 5004.2.1 of the 2025 California Fire Code is hereby amended to read in its entirety:

5004.2.1 Spill control for hazardous material liquids. Rooms, buildings or areas used for storage of hazardous material liquids shall be provided with spill control to prevent the flow of liquids to adjoining areas. Floors in indoor locations and similar surfaces in outdoor locations shall be constructed to contain a spill from the largest single vessel by one of the following methods:

1.

Liquid-tight sloped or recessed floors in indoor locations or similar areas in outdoor locations.

2.

Liquid-tight floors in indoor and outdoor locations or similar areas provided with liquid-tight raised or recessed sills or dikes.

3.

Sumps and collection systems, including containment pallets in accordance with Section 5004.2.3.

4.

Other approved engineered systems.

Except for surfacing, the floors, sills, dikes, sumps and collection systems shall be constructed of noncombustible material, and the liquid-tight seal shall be compatible with the material stored. When liquid-tight sills or dikes are provided, they are not required at perimeter openings having an open-grate trench across the opening that connects to an approved collection system.

E.

Section 5004.2.2.2 of the 2025 California Fire Code is hereby amended to read in its entirety:

5004.2.2.2 Incompatible materials. Incompatible materials shall be separated from each other in independent secondary containment systems.

(Ord. No. 2368 N.S., § 5, 11-19-2025)

15.44.130 - Chapter 56—Explosives and fireworks.

A.

Section 5601.1.3 of the 2025 California Fire Code is hereby amended to read in its entirety:

5601.1. 3 Fireworks. The possession, manufacture, storage, sale, handling, and use of fireworks, including those fireworks classified as Safe and Sane by the California State Fire Marshal, are prohibited.

Exception: The use of fireworks for fireworks displays as allowed in Section 5608.

15.44.140 - Chapter 57—Flammable and Combustible Liquids.

A.

Section 5704.2.7.5.8 of the 2025 California Fire Code is hereby amended to read in its entirety:

5704.2.7.5.8 Overfill prevention. An approved means or method in accordance with Section 5704.2.9.7.5 shall be provided to prevent the overfill of all Class I, II and IIIA liquid storage tanks. Storage tanks in refineries, bulk plants or terminals regulated by Sections 5706.4 or 5706.7 shall have overfill protection in accordance with API 2350.

Exception: Outside aboveground tanks with a capacity of 1320 gallons (5000 L) or less need only comply with Section 5704.2.9.7.5.1 (Item 1, Sub-item 1.1)

An approved means or method in accordance with Section 5704.2.9.7.5 shall be provided to prevent the overfilling of Class IIIB liquid storage tanks connected to fuel-burning equipment inside buildings.

(Ord. No. 2368 N.S., § 5, 11-19-2025)

15.44.150 - Chapter 58—Flammable gases and flammable cryogenic fluids.

A.

Section 5809.3.3 of the 2025 California Fire Code is hereby amended to read in its entirety:

5809.3.3 Site plan. For other than emergency roadside service, a site plan shall be developed for each location at which mobile gaseous hydrogen fueling occurs. The site plan shall be of sufficient detail to indicate the following:

1.

All buildings and structures.

2.

Lot lines or property lines.

3.

Solar photovoltaic parking lot canopies.

4.

Appurtenances on-site and their use and function.

All uses adjacent to the lot lines of the site.

6.

Hydrogen fueling locations.

7.

Scale of the site plan.

(Ord. No. 2368 N.S., § 5, 11-19-2025)

15.44.160 - Appendix C—Fire hydrant locations and distribution.

A.

Section C102.1 of the 2025 California Fire Code is hereby amended to read in its entirety:

C102.1 Minimum number of fire hydrants for a building. The number of fire hydrants available to a building shall be not less than the minimum specified in Table C102.1, utilizing the base fire flow without fire sprinkler reduction.

B.

Section C103.1 of the 2025 California Fire Code is hereby amended to read in its entirety:

C103.1 Hydrant spacing. Fire apparatus access roads and public streets providing required access to buildings in accordance with Section 503 of the California Fire Code shall be provided with one or more fire hydrants, as determined by Section C102.1. Where more than one fire hydrant is required, the distance between required fire hydrants shall be in accordance with Sections C103.2 and C103.3, but in no case shall the average spacing be more than 300 feet on center.

(Ord. No. 2368 N.S., § 5, 11-19-2025)

15.44.170 - Violation.

A.

A violation of the code adopted by this chapter occurs when a person:

1.

Fails to comply with this code;

2.

Violates or fails to comply with any order made under this code;

Builds in violation of any detailed statement of specifications or plans submitted and approved thereunder or any certificate or permit issued thereunder and from which no appeal has been taken; or

4.

Fails to comply with such an order as affirmed or modified by the city council or by a court of competent jurisdiction, within the time fixed in this chapter.

B.

Such person may be liable severally and for each and every such violation and noncompliance respectively.

C.

The imposition of one penalty for any violation shall not excuse the violation or permit it to continue and all such persons shall be required to correct or remedy such violations or defects within a reasonable time.

D.

The application of the above penalty shall not be held to prevent the enforced removal of prohibited conditions.

(Ord. No. 2368 N.S., § 5, 11-19-2025)

Chapter 15.52 - MOVING BUILDINGS

15.52.010 - Definitions.

For the purposes of this chapter, certain terms, phrases and words shall be construed as follows:

A.

"Building" means any structure built for the support, shelter or enclosure of persons, animals, chattels or property of any kind.

B.

"Building official" means the building official of the city or his regularly authorized deputy.

C.

"Person" means a natural person, his heirs, executors, administrators or assigns, and also includes a firm, partnership or corporation, its or their successors or assigns, or the agent of any of them.

D.

"Structure" means that which is built or constructed, an edifice, or building of any kind, or any piece of work artificially built up or composed of parts joined together in some definite manner.

E.

"Termite inspector" means any person who is duly licensed by the state to perform the work of pest or termite control or inspection.

(Ord. 1861 N.S. § 13 (part), 2007: Ord. 64 N.S. § 1, 1956; Ord. No. 2095 N.S., § 2, 11-20-2013)