SEC. 99.04.100. BASIC PROVISIONS.

(Amended by Ord. No. 187,719, Eff. 1/23/23.)

Chapter 4 of the California Green Building Standards Code is adopted by reference except as amended herein.

Exceptions & meaning →

SEC. 99.04.106.

(Amended by Ord. No. 188,797, Eff. 12/31/25.)

99.04.106.2. Storm Water Drainage and Retention During Construction. Projects which disturb soil shall manage storm water drainage during construction. In order to manage storm water drainage during construction one or more of the following measures shall be implemented to prevent flooding of adjacent property, prevent erosion and retain soil runoff on the site:

  1. Retention basins of sufficient size shall be utilized to retain storm water on the site;

  2. Where storm water is conveyed to a public drainage system, collection point, gutter, or similar disposal method, water shall be filtered by use of a barrier system, wattle or other method approved by the Department; or

  3. Compliance with City of Los Angeles’ storm water management ordinance(s).

99.04.106.5. Cool Roof for Reduction of Heat Island Effect. (Amended by Ord. No. 187,208, Eff. 11/5/21.) Roofing material shall comply with both LAMC Subsections 99.04.106.5.1 and 99.04.106.5.2, or comply with LAMC Subsection 99.04.106.5.3.

EXCEPTIONS:

    1. Roof repair as defined in Section 100.1(b) of the California Energy Code; or
    1. Roof replacement when the roof area being replaced is equal to or less than 50% of the total roof area; or
    1. Roof replacement where solar systems are being installed; or
  1. Additions resulting in less than 500 square feet of added roof area or less than 50% of the total roof area, whichever is greater; or

  2. Roof construction that has a thermal mass over the roof membrane, including areas of vegetated (green) roofs, weighing at least 25 pounds per square foot.

99.04.106.5.1. Solar Reflectance. Roofing material shall have a minimum three-year aged solar reflectance equal to or greater than the values specified in LAMC Tables 99.04.106.5.1 and 99.04.106.5.2. Solar reflectance shall be determined by testing by an approved agency in accordance with ASTM C1549, ASTM E1918 or CRRC-1. Solar reflectance values shall be based on the aged reflectance value of the roofing product or the equation in California Green Building Standards Code (CALGreen) Section A4.106.5.1 if aged solar reflectance values are not available. (Amended by Ord. No. 187,208, Eff. 11/5/21.)

99.04.106.5.2. Thermal Emittance. Roofing materials shall have an emittance value equal to or greater than those specified in LAMC Tables 99.04.106.5.1 and 99.04.106.5.2. Thermal emittance shall be determined by testing by an approved agency in accordance with ASTM C1371, ASTM E408 or CRRC-1. (Amended by Ord. No. 187,208, Eff. 11/5/21.)

99.04.106.5.3. Solar Reflectance Index. Roofing materials shall have a three-year aged Solar Reflectance Index equal to or greater than those specified in LAMC Tables 99.04.106.5.1 and 99.04.106.5.2. Aged Solar Reflectance Index (SRI) may be calculated using the SRI Calculation Worksheet (SRI-WS) developed by the California Energy Commission or in compliance with ASTM E1980-01 as specified in the 2019 California Energy Code. Solar reflectance values used in the SRI-WS shall be based on the aged reflectance value of the roofing product. Certified thermal emittance used in the SRI-WS may be either the initial value or the aged value listed by the Cool Roof Rating Council. (Amended by Ord. No. 187,208, Eff. 11/5/21.)

TABLE TABLE 99.04.106.5.1 [LOW-RISE] (Added by Ord. No. 187,208, Eff. 11/5/21.)

ROOF SLOPE MINIMUM 3-YEAR AGED SOLAR REFLECTANCE THERMAL EMITTANCE 3 YEAR AGED SOLAR REFLECTANCE INDEX (SRI)
≤ 2:12 0.65 0.85 78
> 2:12 0.25 0.85 20

TABLE 99.04.106.5.2 [HIGH-RISE] (Added by Ord. No. 187,208, Eff. 11/5/21.)

ROOF SLOPE MINIMUM 3-YEAR AGED SOLAR REFLECTANCE THERMAL EMITTANCE 3 YEAR AGED SOLAR REFLECTANCE INDEX (SRI)
≤ 2:12 0.65 0.75 78
> 2:12 0.25 0.75 20

99.04.106.7. Reduction of Heat Island Effect for Nonroof Areas [N]. Reduce nonroof heat islands for 50% of pathways patios, driveways or other paved areas by using one or more of the methods listed.

  1. Use trees or other plantings to provide shade and that mature within 15 years of planting. Trees shall be suitable in mature size and environmental requirements for the site. Tree selection and placement shall consider location and size of areas to be shaded, location of utilities, views from the structure, distance to sidewalks and foundations, overhangs onto adjacent properties and streets; other infrastructure and adjacent to landscaping. In addition, shading shall not cast a shadow, as specified, on any neighboring solar collectors pursuant to California Public Resources Code Section 25981, et seq. (Solar Shade Control Act);

  2. Use high albedo materials with an initial solar reflectance value of at least .30 as determined in accordance with American Society for Testing and Materials (ASTM) Standards E1918 or C1549;

    1. Use open grid pavement system or pervious or permeable pavement system;
    1. Use solar panel arrays to create a canopy shade system; or
    1. Other methods of reducing heat island effects acceptable to the Department.

99.04.106.8. All-Electric Buildings. (Added by Ord. No. 187,714, Eff. 1/23/23.) All newly constructed buildings shall be all-electric buildings.

EXCEPTIONS:

  1. Application for a building permit is submitted, accepted by the Department of Building and Safety, and building permit application fees are paid prior to April 1, 2023.

  2. Application for a building permit for an Affordable Housing Project, as defined in the Mayor's Executive Directive 1.3, is submitted, accepted by the Department of Building and Safety, and building permit application fees are paid prior to June 1, 2023.

  3. Attached accessory dwelling units using existing gas piping systems in conjunction with the primary dwelling.

  4. Cooking equipment contained within kitchens located in a public use area, as defined in the California Building Code Chapter 2, such as restaurants, commissaries, cafeterias, and community kitchens provided the electrical infrastructure is installed in accordance with Section 99.04.106.8.1.

  5. Gas-powered emergency life-safety systems, including emergency backup.

99.04.106.8.1. Requirements for Combustion Equipment. (Added by Ord. No. 187,714, Eff. 1/23/23.) Where required by Section 99.04.106.8, the electrical infrastructure shall be installed to accommodate the future installation of an electrical heating or cooking appliance/equipment in the following ways:

  1. Branch circuit wiring, electrically isolated and designed to serve all electrical heating and cooking appliances in accordance with manufacturer requirements and the California Electrical Code, including the appropriate voltage, phase, minimum amperage, and an electrical receptacle or junction box within 5 feet of the appliance that is accessible with no obstructions. Appropriately sized conduit may be installed in lieu of conductors; and

  2. Labeling of both ends of the unused conductors or conduit shall be with "For Future Electrical Appliance/Equipment"; and

  3. Reserved circuit breakers in the electrical panel for each branch circuit, appropriately labeled (e.g., "Reserved for Future Electric Range/Equipment"), and positioned on the opposite end of the panel supply conductor connection; and

  4. Connected subpanels, panelboards, switchboards, busbars, and transformers shall be sized to serve the future electrical heating appliances and equipment. The electrical capacity requirements shall be adjusted for demand factors in accordance with the California Electric Code.

Exceptions & meaning →

ENERGY EFFICIENCY

SEC. 99.04.201. GENERAL.

99.04.201.1. Scope. (Amended by Ord. No. 185,587, Eff. 7/16/18.) The provisions of this division shall establish means of conserving energy.

Exceptions & meaning →

SEC. 99.04.211. RENEWABLE ENERGY.

(Amended by Ord. No. 184,692, Eff. 12/30/16.)

99.04.211.4. Solar Ready Buildings. Buildings shall comply with the following:

  1. All one- and two-family dwellings shall comply with Sections 110.10(b)1A, 110.10(b)2, 110.10(b)3, 110.10(b)4, 110.10(c), 110.10(d) and 110.10(e) of the California Energy Code (CCR, Title 24, Part 6).

  2. All buildings, other than one- and two-family dwellings, shall comply with Sections 110.10(b) through 110.10(d) of the California Energy Code (CCR, Title 24, Part 6).

EXCEPTIONS:

  1. Additions having less than 2,000 sq. ft. of new roof area.

  2. Alterations.

Exceptions & meaning →

SEC. 99.04.303. INDOOR WATER USE.

(Amended by Ord. No. 187,719, Eff. 1/23/23.)

99.04.303.4. Water Use Reduction. (Added by Ord. No. 184,246, Eff. 6/6/16.) A 20 percent reduction in the overall use of potable water within the building shall be provided. The reduction shall be based on the maximum allowable water use per plumbing fixture and fittings as required by the Los Angeles Building Standards. The 20 percent reduction in potable water use shall be demonstrated by the following method:

99.04.303.4.1. Performance Method. A calculation demonstrating a 20% reduction in the building "water use baseline", as established in LAMC Table 99.04.303.4.1, shall be provided.

EXCEPTIONS:

  1. Projects with plumbing fixtures and fittings that comply with the maximum flow rate values in LAMC Table 99.04.303.4.2.

  2. Additions and alterations to buildings where the new fixtures and fittings comply with the maximum flow rate values in LAMC Table 99.04.303.4.2.

  3. Buildings utilizing recycled water in accordance with LAMC Subsection 99.04.305.2.

  4. Replacement of plumbing fixtures and fittings.

TABLE 99.04.303.4.1 WATER USE BASELINE 4

(Amended by Ord. No. 188,797, Eff. 12/31/25.)

FIXTURE TYPE BASELINE FLOW RATE DURATION DAILY USES OCCUPANTS 2
Showerheads 1.8 gpm @ 80 psi 8 min. 1 X 2a
Lavatory Faucets, Residential 1.2 gpm @ 60 psi .25 min. 3 X
Lavatory Faucets, Common/Public Uses 0.5 gpm @ 60 psi .25 min. 3 X
Kitchen Faucets 1.8 gpm @ 60 psi 4 min. 1 X 2b
Replacement Aerators 2.2 gpm
Metering Faucets 0.20 gallons/cycle 3 X
Water Closets 1.28 gallons/flush 1 flush 1 male 1 3 female X
Urinals 0.125 gallons/flush 1 flush 2 male X

Fixture "Water Use" = Flow rate × Duration × Occupants × Daily uses

  1. The daily use number shall be increased to three if urinals are not installed in the room.

  2. Refer to Table 4-1, Chapter 4 of the California Plumbing Code, for occupant load factors.

a. Shower use by occupants depends on the type of use of a building or portion of a building. For example, the total occupant load for a health club, but only a fraction of the occupants in an office building as determined by the anticipated number of users.

b. Kitchen faucet use is determined by the occupant load of the area served by the fixture.

  1. Floor-mounted urinals @ 0.5 GPF or wall-mounted urinals @ 0.125 GPF.

  2. Use Worksheet WS-1 of the CALGreen Code to calculate baseline water.

TABLE 99.04.303.4.2 WATER REDUCTION FIXTURE FLOW RATES

FIXTURE TYPE MAXIMUM ALLOWABLE FLOW RATE
Kitchen Faucets* 1.5 gpm @ 60 psi
Clothes Washers ENERGY-STAR certified
Dishwashers ENERGY-STAR certified

*Kitchen faucets may temporarily increase the flow to 2.2 gpm at 60 psi, and must default to 1.5 gpm at 60 psi. This requirement does not apply to a faucet in commercial kitchens or in buildings that have water closets with a maximum flush rate of 1.06 gpf installed throughout.

Exceptions & meaning →

SEC. 99.04.304. OUTDOOR WATER USE.

(Amended by Ord. No. 186,488, Eff. 12/27/19.)

99.04.304.3. Metering Outdoor Water Use. A landscape water meter provided by the City of Los Angeles Department of Water and Power shall be installed for landscape irrigation for the following:

  1. New construction projects, as defined by the California Department of Water Resources Model Water Efficient Landscape Ordinance, with aggregate landscape area over 500 square feet.

  2. When required by the California Department of Water Resources Model Water Efficient Landscape Ordinance.

  3. Additions and alterations, with a valuation of $200,000 or more, where the entire potable water system is replaced, including all underground piping to the existing meter.

99.04.304.4. Exterior Faucets. Locks shall be installed on all publicly accessible exterior faucets and hose bibs.

EXCEPTION: Single family dwellings.

99.04.304.5. Swimming Pool Covers. For one- and two-family dwellings, any permanently installed outdoor in-ground swimming pool or spa shall be equipped with a cover having a manual or power-operated reel system. For irregular-shaped pools where it is infeasible to cover 100 percent of the pool due to its irregular shape, a minimum of 80 percent of the pool shall be covered.

EXCEPTION: Additions or alterations to existing swimming pools and spas with a building valuation not exceeding $25,000.

Note: Safety pool covers installed pursuant to the exception to LAMC Subsection 91.3109.4 shall meet the requirements of ASTM F 1346. (Amended by Ord. No. 185,587, Eff. 7/16/18.)

Exceptions & meaning →

SEC. 99.04.305. WATER REUSE SYSTEMS.

(Added by Ord. No. 184,246, Eff. 6/6/16.)

99.04.305.1. Recycled Water Supply to Fixtures. (Amended by Ord. No. 186,488, Eff. 12/27/19.) When City-recycled water is available for use within 200 feet of the property line, 100 percent of water for water closets, urinals, floor drains, and process cooling and heating in that building shall come from City-recycled water. Recycled water systems shall be designed and installed in accordance with the Los Angeles Plumbing Code.

EXCEPTIONS:

  1. Additions that use any part of the existing plumbing system.

  2. Alterations that do not include replacing all of the potable water piping.

  3. Where City-recycled water quality has been deemed non-suitable for a particular fixture or equipment, connection to the City is not required. The fixture and/or equipment shall be dual-plumbed to allow for future connection.

99.04.305.2. Graywater Ready. (Amended by Ord. No. 186,488, Eff. 12/27/19.) Waste piping shall be arranged to permit the discharge from the clothes washer, bathtub, showers and bathroom/restroom washbasins to be used for a future graywater irrigation system(s). The flow from the fixtures shall be piped separately, and, at a minimum, be adequate to supply the irrigation demand as determined by the California Department of Water Resources' Model Water Efficiency Landscape Ordinance (MWELO). The point(s) of connection between graywater piping and other waste piping shall be accessible (as defined in LAMC Section 99.02.202) and provided with signage that is satisfactory to the Department.

EXCEPTIONS:

    1. Buildings with a graywater, rainwater harvesting, or other water reuse system.
    1. Sites with landscape areas not exceeding 500 square feet.
    1. Projects where graywater systems are not permitted due to geological conditions.
    1. Additions and alterations that use the existing building drain.

99.04.305.3. Cooling Towers [N]. (Amended by Ord. No. 185,587, Eff. 7/16/18.) Cooling towers shall comply with LAMC Subdivision 99.04.305.3.1 or 99.04.305.3.2.

99.04.305.3.1. Buildings 25 Stories or Less. Buildings of 25 stories or less shall comply with one of the following:

  1. Cooling towers shall have a minimum of 6 cycles of concentration (blowdown); or

  2. A minimum of 50 percent of makeup water supply to cooling towers shall come from non-potable water sources, including treated backwash.

99.04.305.3.2. Buildings Over 25 Stories. Buildings over 25 stories shall comply with all of the following:

  1. Cooling towers shall have a minimum of 6 cycles of concentration (blowdown); and

  2. 100 percent of makeup water supply to cooling towers shall come from non-potable water sources, including treated backwash.

EXCEPTION: Where the amount of graywater produced by the plumbing system is insufficient to meet the total makeup water demand, as determined by the Department, potable water can be used to compensate for the deficiency.

99.04.305.4. Groundwater Discharge [N]. Where groundwater is being extracted and discharged, a system for onsite reuse of the groundwater shall be developed and constructed. Alternatively, the groundwater may be discharged to the sewer.

Exceptions & meaning →

SEC. 99.04.407. WATER RESISTANCE AND MOISTURE MANAGEMENT.

99.04.407.3. Flashing Details. Provide flashing details on the building plans which comply with accepted industry standards or manufacturer’s instructions at the following locations:

    1. Around windows and doors;
    1. Roof valleys;
    1. Chimneys to roof intersections.

99.04.407.4. Material Protection. Protect building materials delivered to the construction site from rain and other sources of moisture.

Exceptions & meaning →

SEC. 99.04.408. CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RECYCLING.

(Amended by Ord. No. 184,692, Eff. 12/30/16.)

99.04.408.1. Construction Waste Management. Comply with LAMC Section 66.32, et seq., of the Los Angeles Municipal Code.

Exceptions & meaning →

SEC. 99.04.504. POLLUTANT CONTROL

(Amended by Ord. No. 186,486, Eff. 1/28/20.)

99.04.504.6. Filters. (Amended by Ord. No. 187,719, Eff. 1/23/23.) Mechanically ventilated buildings shall meet the air filtration requirements of the California Energy Code.

Tables 4.504.1, 4.504.2, and 4.504.3 of the California Green Building Standards Code, Title 24, Part 11 are not adopted. The following tables shall apply instead:

TABLE 99.04.504.1

ADHESIVE VOC LIMIT 1, 2

Less Water and Less Exempt Compounds in Grams per Liter

(Amended by Ord. No. 188,797, Eff. 12/31/25.)

ARCHITECTURAL APPLICATIONS VOC LIMIT
Indoor carpet adhesives 50
Carpet pad adhesives 50
Outdoor carpet adhesives 150
Wood flooring adhesives 100
Rubber floor adhesives 60
Subfloor adhesives 50
Ceramic tile adhesives 65
VCT and asphalt tile adhesives 50
Drywall and panel adhesives 50
Cove base adhesives 50
Multipurpose construction adhesives 70
Structural glazing adhesives 100
Single-ply roof membrane adhesives 250
Other adhesives not specifically listed 250
SPECIALTY APPLICATIONS VOC LIMIT
PVC welding 510
CPVC welding 490
ABS welding 325
Plastic cement welding 100
Adhesive primer for plastic 550
Contact adhesive 80
Special purpose contact adhesive 250
Structural wood member adhesive 140
Top and trim adhesive 540
SUBSTRATE SPECIFIC APPLICATIONS VOC LIMIT
Metal to metal 30
Plastic foams 50
Porous material (except wood) 50
Wood 30
Fiberglass 80
  1. If an adhesive is used to bond dissimilar substrates together, the adhesive with the highest VOC content shall be allowed.

  2. For additional information regarding methods to measure the VOC content specified in this table, see South Coast Air Quality Management District Rule 1168.

TABLE 99.04.504.2

SEALANT VOC LIMIT

Less Water and Less Exempt Compounds in Grams per Liter

(Amended by Ord. No. 188,797, Eff. 12/31/25.)

SEALANTS VOC LIMIT
Architectural 50
Marine deck 760
Non-membrane roof 300
Roadway 250
Single-ply roof membrane 450
Other 420
SEALANT PRIMERS VOC LIMIT
Architectural
Nonporous 250
Porous 775
Modified bituminous 500
Marine deck 760
Other 750

TABLE 99.04.504.3

VOC CONTENT LIMITS FOR ARCHITECTURAL COATINGS 2, 3

Grams of VOC per Liter of Coating Less Water and Less Exempt Compounds

(Amended by Ord. No. 188,797, Eff. 12/31/25.)

COATING CATEGORY VOC LIMIT
Flat coatings 50
Nonflat coatings 50
Nonflat-high gloss coatings 50
SPECIALTY COATINGS VOC LIMIT
Aluminum roof coatings 100
Basement specialty coatings 400
Bituminous roof coatings 50
Bituminous roof primers 350
Bond breakers 350
Concrete curing compounds 100
Concrete curing compounds, Roadways & Bridges 350
Concrete/masonry sealers 100
Driveway sealers 50
Dry fog coatings 50
Faux finishing coatings
Clear Top Coat 100
Decorative Coatings 350
Glazes 350
Japan 350
Trowel Applied Coatings 50
Fire resistive coatings 150
Floor coatings 50
Form-release compounds 100
Graphic arts coatings (sign paints) 200
High temperature coatings 420
Industrial maintenance coatings 100
Low solids coatings 1 120
Magnesite cement coatings 450
Mastic texture coatings 100
Metallic pigmented coatings 150
Multicolor coatings 250
Pretreatment wash primers 420
Primers, sealers, and undercoaters 100
Reactive penetrating sealers 350
Recycled coatings 250
Roof coatings 50
Roof coatings, aluminum 100
Rust preventative coatings 100
Shellacs
Clear 730
Opaque 550
Specialty primers, sealers and undercoaters 100
Stains 100
Stains, Interior 250
Stone consolidants 450
Swimming pool coatings 340
Traffic marking coatings 100
Tub and tile refinish coatings 420
Waterproofing membranes 100
Wood coatings 275
Wood preservatives 350
Zinc-rich primers 100
  1. Grams of VOC per liter of coating, including water and including exempt compounds.

  2. The specified limits remain in effect unless revised limits are listed in subsequent columns in the table.

  3. Values in this table are derived from those specified by the South Coast Air Management District (SCAQMD) Rule 1113. More information is available from the SCAQMD.

Exceptions & meaning →