SEC. 91.1507. REQUIREMENTS FOR ROOF COVERINGS.

Los Angeles Building Code — LAMC Chapter IX · 2026-08 edition · updated 2026-09-09 · Los Angeles

(Amended by Ord. No. 187,719, Eff. 1/23/23.)

Section 1507 of the CBC is adopted by reference, except Table 1507.3.7 of the CBC is not adopted and, in lieu, Los Angeles Municipal Code Table 1507.3.7 is added.

TABLE 1507.3.7

CLAY AND CONCRETE TILE ATTACHMENTa, b, c (Amended by Ord. No. 181,758, Eff. 8/8/11.)

GEN
ERAL – CLAY OR CONCRETE ROOF TILE

Maximum basic wind
speed (mph)
Mean roof height
(feet)
Roof slope up to <3:12
Roof slope 3:12 and over
85 0-60 Two fasteners per tile.
Two fasteners per tile.
100 0-40
100 >40-60 The head of all tiles shall be nailed. The nose of all eave tiles shall be fastened with approved
clips. All rake tiles shall be nailed with two nails. The nose of all ridge, hip and rake tiles shall
be set in a bead of roofer’s mastic.
110 0-60 The fastening system shall resist the wind forces in CBC Section 1609.5.3.
120 0-60 The fastening system shall resist the wind forces in CBC Section 1609.5.3.
130 0-60 The fastening system shall resist the wind forces in CBC Section 1609.5.3.
All >60 The fastening system shall resist the wind forces in CBC Section 1609.5.3.
INTERLOCKING CLAY OR CONCRETE ROOF TILE WITH PROJECTING ANCHOR LUGSd, e
(In
stallations on solid sheathi
ng with battens)
Maximum basic wind
speed (mph)
Mean roof height
(feet)
Roof slope
up to < 5:12
Roof slope
5:12 < 12:12
Roof slope
12:12 and over
85 0-60 Minimum slope is 4:12.
One fastener per tile.
One fastener per tile. Tiles
with installed weight less
th 9 lb/ ft i
One fastener required for every
tile. Tiles with installed weight
l th 9 lb/ ft i
100 0 - 40 an s.sq. . requre a
minimum of one fastener
per tile.
ess an s.sq. . requre a
minimum of one fastener per tile.
100 >40-60 The head of all tiles shall b
clips. All rake tiles shall be
be set in a bead of roofer’s
e nailed. The nose of all eave ti
nailed with two nails. The nos
mastic.
les shall be fastened with approved
e of all ridge, hip and rake tiles shall
110 0-60 The fastening system shall resist the wind forces in CBC S ection 1609.5.3.
120 0-60 The fastening system shall resist the wind forces in CBC S ection 1609.5.3.
130 0-60 The fastening system shall resist the wind forces in CBC S ection 1609.5.3.
All >60 The fastening system shall resist the wind forces in CBC S ection 1609.5.3.
INTERLOCKING CLAY OR CONCRETE ROOF TILE WITH PROJECTING ANCHOR LUGS
(Ins
tallations on solid sheathing without battens)
Maximum basic wind
speed (mph)
Mean roof height
(feet)
Minimum roof slopes 4 units vertical in 12 units horizontal Maximum slope 7 units
vertical in 12 units horizontal
85 0-60 One fastener per tile.
100 0-40 One fastener per tile.
100 >40-60 The head of all tiles shall be nailed. The nose of all eave tiles shall be fastened with approved
clips. All rake tiles shall be nailed with two nails The nose of all ridge, hip and rake tiles shall
be set in a bead of roofer’s mastic.
110 0-60 The fastening system shall resist the wind forces in CBC Section 1609.5.3.
120 0-60 The fastening system shall resist the wind forces in CBC Section 1609.5.3.
130 0-60 The fastening system shall resist the wind forces in CBC Section 1609.5.3.
All >60 The fastening system shall resist the wind forces in CBC Section 1609.5.3.

For SI: one inch = 25.4 mm, one foot = 304.8 mm, one mile per hour = 0.447 m/s, one pound per square foot= 4.882 kg/m2 .

a Minimum fastener size. Hot dipped galvanized ring shank or other corrosion-resistant nails not less than No. 11 gage with 5/16-inch head. Fasteners shall be long enough to penetrate into the sheathing 0.75 inch or through the thickness of the sheathing, whichever is less. Attaching wire for clay and concrete tile shall not

be smaller than 0.083 inch and shall be copper, brass or stainless steel.

b Snow areas. A minimum of two fasteners per tile are required or battens and one fastener.

  • c Roof slopes greater than 24:12. The nose of all tiles shall be securely fastened.

  • d Horizontal battens. Battens shall be not less than one-inch by two-inch nominal. Provisions shall be made for drainage by a minimum of 1/8-inch riser at each nail or by four-foot-long battens with at least a 0.5-inch separation between battens. Horizontal battens are required for slopes over 7:12.

e Perimeter fastening areas include three tile courses but not less than 36 inches from either side of hips or ridges and edges of eaves and gable rakes.