Title 12 — BUILDINGS AND CONSTRUCTION

Los Altos Municipal Code Ch. 57 Flammable and Combustible Liquids

Los Altos Municipal Code · 2026-09 edition · updated 2026-10-03 · Los Altos

Cite as: Los Altos Municipal Code Chapter 57 · Text as of 2026-10-03

Section 5704 STORAGE

Section 5704.2.7.5.8 is amended to read as follows and the exception in the Section is deleted:

Section 5704.2.7.5.8 Overfill Prevention.

An approved means or method in accordance with Section 5704.2.9.7.5, shall be provided to prevent the overfill of all Class I, II and IIIA liquid storage tanks. Storage tanks in refineries, bulk plants or terminals regulated by Sections 5706.4 or 5706.7 shall have overfill protection in accordance with API 2350.

Exception: Outside aboveground tanks with a capacity of 1320 gallons (5000 L) or less need only comply with Section 5704.2.9.7.5 (Item 1, Sub-item 1.1).

An approved means or method in accordance with Section 5704.2.9.7.5 shall be provided to prevent the overfilling of Class IIIB liquid storage tanks connected to fuel-burning equipment inside buildings.

Exception: Outside aboveground tanks with a capacity of 1320 gallons (5000 L) or less need only comply with Section 5704.2.9.7.5 (Item 1, Sub-item 1.1).

Section 5704.2.7.5.9 is added to read as follows:

Section 5704.2.7.5.9 Automatic and/or Remote Filling of Tanks. Systems that automatically fill flammable or combustible liquid tanks shall be equipped with overfill protection, approved by the fire code official, that sends an alarm signal to a constantly attended location and immediately stops the filling of the tank. The alarm signal and automatic shutoff shall be tested on an annual basis and records of such testing shall be maintained on-site for a period of five (5) years.

Section 5704.2.9.6.1 is amended to read as follows:

5704.2.9.6.1 Locations where above-ground tanks are prohibited. The storage of Class I and II liquids in above-ground tanks outside of building is prohibited in all locations of the City of Los Altos which are residential or congested commercial areas as determined by the fire code official.

Section 5706.2.4.4 is amended to read as follows:

5706.2.4.4 Locations where above-ground tanks are prohibited. Storage of Class I and II liquids in above- ground tanks is prohibited in all locations of the City of Los Altos which are residential or congested commercial areas as determined by the fire code official.