§ 17.18.020. Appendix B105.1 amended.

Appendix B105.1 of the California Fire Code, 2022 Edition is amended to read as follows:

Appendix B105.1. The minimum fire flow and flow duration for building other than one- and two-family dwellings shall be as specified in Table B105.1.

Exceptions:

  1. A reduction in required fire flow of up to 50 percent, as approved, is allowed when the building is provided with an approved automatic sprinkler system in accordance with Section 903.3.1.2. The resulting fire flow shall not be less than 1,500 gallons per minute for the prescribed duration as specified in Table B105.1.

(Ord. 1592 § 2, 2022)