Earlier editions: 2026-09
Title 15 — BUILDINGS AND CONSTRUCTION
East Palo Alto Municipal Code Ch. 15.25 Energy Code
East Palo Alto Municipal Code · 2026-10 edition · updated 2026-10-04 · East Palo Alto
Cite as: East Palo Alto Municipal Code Chapter 15.25 · Text as of 2026-10-04
15.25. - Title.¶
This chapter shall be known and may be cited and referred to as the "Energy Code for the City of East Palo Alto."
(Ord. No. 339B, § 2(Exh. A), 12-21-2010; Ord. No. 369, § 2(Exh. A), 11-19-2013)
15.25.010 - Adoption by reference.¶
The "2022 California Energy Code" is hereby adopted by reference as the energy code of the City of East Palo Alto. All references to jurisdictional requirements are found in the East Palo Alto Municipal Code or other appropriate schedules.
(Ord. No. 339B, § 2(Exh. A), 12-21-2010; Ord. No. 369, § 2(Exh. A), 11-19-2013; Ord. No. 426, 12-17-2019; Ord. No. 07-2020, § 2, 10-21-2020; Ord. No. 10-2022, § 8, 12-6-2022)
15.25.020 - Energy Code amendments.¶
Energy Code amendments are as follows:
SECTION 100.0—Scope.
(e) Sections applicable to particular buildings. TABLE 100.0-A and this subsection list the provisions of Part 6 that are applicable to different types of buildings covered by Section 100.0(a).
- All buildings. Sections 100.0 through 110.12 apply to all buildings.
EXCEPTION to Section 100.0(e) 1: Spaces or requirements not listed in TABLE 100.0-A.
- Newly constructed buildings.
A. All newly constructed buildings. Sections 110.0 through 110.12 apply to all newly constructed buildings within the scope of Section 100.0(a). In addition, newly constructed buildings shall meet the requirements of Subsections B, C, D or E, as applicable and shall be an All-Electric Building as defined in Section 100.1(b). For the purposes of All-Electric Building requirements, newly constructed buildings as defined in Section 100.1 shall include a construction project where an alteration includes replacement of over 50% of the existing foundation for purposes other than a repair or reinforcement as defined in California Existing Building Code Section 202; or when over 50% of the existing framing above the sill plate is removed or replaced for purposes other than repair. If either of these criteria are met within a 3-year period, measured from the date of the most recent previously obtained permit final date, that structure is considered new construction and shall be subject to the All-Electric Building requirements. The final determination whether a project meets the definition of substantial reconstruction/alteration shall be made by a designated building official.
Exception 1: Non-Residential Buildings containing a Scientific Laboratory Building, such area may contain a non-electric Space Conditioning System.
Exception 2: All-Electric domestic water heating requirements shall not apply to new residential structures that have central water heating and entirely consist of affordable rental units, defined as units rented at an amount consistent with the maximum rent levels for a housing development that receives an allocation of state or federal low-income housing tax credits from the California Tax Credit Allocation Committee. Residential developments meeting the above definition must have an Inclusionary Housing Plan that is approved by the Housing Division pursuant to Section 18.37.090.
Exception 3: Exemption for public agency owned and operated emergency centers. To take advantage of this exception applicant shall provide third party verification that All-Electric space heating requirement is not cost effective and feasible.
Exception 4: Multifamily residential building projects that have been granted planning entitlements within two years or less, or have been approved, before the effective date of this ordinance, are not required to install all-electric water heating systems. If the Building Official grants a modification pursuant to this Exception, the applicant shall comply with the pre-wiring provision of Note 1 below.
Exception 5: If the applicant establishes that there is not an all-electric prescriptive compliance pathway for the building under the Energy Code, and that the building is not able to achieve the performance compliance standard applicable to the building under the Energy Code using commercially available technology and an approved calculation method, then the Building Official may grant a modification. If the Building Official grants a modification pursuant to this Exception, the applicant shall comply with the pre-wiring provision of Note 1 below.
Exception 6: Accessory Dwelling Units and Junior Accessory Dwelling Units shall be exempt from the all-electric building provisions of this section. For purposes of this exception, "Accessory Dwelling Unit" and "Junior Accessory Dwelling Unit" have the same definitions as set out in Government Code Sections 65852.2 and 65852.22, respectively.
Exception 7: Non-residential buildings containing a for-profit restaurant open to the public or an employee kitchen may apply to the Building Official for an exception to install gas-fueled cooking appliances. This request must be based on a business-related reason to cook with a flame that cannot be reasonably achieved with an electric fuel source. Examples include barbeque-themed restaurants and pizza ovens. The Building Official may grant this exception if they find the following:
There is a business-related reason to cook with a flame;
This need cannot be reasonably achieved with an electric fuel source;
The applicant has employed reasonable methods to mitigate the greenhouse gas impacts of the gas-fueled appliance;
The applicant shall comply with the pre-wiring provision of Note 1 below.
The Building Official's decision shall be final unless the applicant appeals to the City Council within 15 days of the appointed body's decision. The City Council's decision on the appeal shall be final.
Exception 8: When improvements to existing buildings contain physical constraints that prevent conformance to the All-Electric Building requirements, the applicant may request an exception. In applying for an exception, the burden is on the applicant to identify the size requirements to comply with an All-Electric Building.
Note 1: If natural gas appliances are used in any of the above exceptions 1-8, natural gas appliance locations must also be electrically pre-wired for future electric appliance installation. They shall include the following:
A dedicated circuit, phased appropriately, for each appliance, with a minimum amperage requirement for a comparable electric appliance (see manufacturer's recommendations) with an electrical receptacle or junction box that is connected to the electric panel with conductors of adequate capacity, extending to within 3 feet of the appliance and accessible with no obstructions. Appropriately sized conduit may be installed in lieu of conductors;
Both ends of the conductor or conduit shall be labeled with the words "For Future Electric appliance" and be electrically isolated;
A circuit breaker shall be installed in the electrical panel for the branch circuit and labeled, an example is as follows (i.e., "For Future Electric Range;") and
All electrical components, including conductors, receptacles, junction boxes, or blank covers, related to this section shall be installed in accordance with the California Electrical Code.
Note 2: If any of the exceptions 1-8 are granted, the Building Official shall have the authority to approve alternative materials, designs and methods of construction per CBC 104,
Section 100.1(b) is modified by adding the following definitions:
ALL ELECTRIC BUILDING: is a building that has no natural gas or propane plumbing installed within the building, and that uses electricity as the source of energy for its space heating, water heating (including pools and spas), cooking appliances, and clothes drying appliances. All Electric Buildings may include solar thermal pool heating.
Scientific Laboratory Building: is a building or area where research, experiments, and measurement in medical, and life sciences are performed and/or stored requiring examination of fine details. The building may include workbenches, countertops, scientific instruments, and supporting offices.
Section 110.2 is modified as follows:
SECTION 110.2 - MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT
Certification by Manufacturers. Any space-conditioning equipment listed in this section, meeting the requirements of section 100.0 (e)2A, may be installed only if the manufacturer has certified to the Commission that the equipment complies with all the applicable requirements of this section.
Section 110.3 is modified as follows:
SECTION 110.3 - MANDATORY REQUIREMENTS FOR SERVICE WATER-HEATING SYSTEMS AND EQUIPMENT
(a) Certification by manufacturers. Any service water-heating system or equipment, meeting the requirements of section 100.0 (e)2A, may be installed only if the manufacturer has certified that the system or equipment complies with all of the requirements of this subsection for that system or equipment.
Section 110.4 is modified as follows:
SECTION 110.4 - MANDATORY REQUIREMENTS FOR POOL AND SPA SYSTEMS AND EQUIPMENT
(a) Certification by Manufacturers. Any pool or spa heating system or equipment, meeting the requirements of section 100.0 (e)2A, may be installed only if the manufacturer has certified that the system or equipment has all of the following:
Section 110.5 is modified as follows:
SECTION 110.5 - NATURAL GAS CENTRAL FURNACES, COOKING EQUIPMENT, POOL AND SPA HEATERS, AND FIREPLACES: PILOT LIGHTS PROHIBITED
Any natural gas system or equipment, meeting the requirements of Section 100.0 (e)2A, listed below may be installed only if it does not have a continuously burning pilot light:
SECTION 140.0(b) is modified as follows:
(b) The requirements of Sections 120.0 through 130.5 (mandatory measures for nonresidential, high-rise residential and hotel/motel buildings)and for all newly constructed buildings:
- The entire solar zone, as specified in Section 110.10, shall have a solar photovoltaic system installed.
Exception 1 to 140.0(b)1: The building official may grant a modification if the applicant demonstrates that the required percentage of PV installation will over-generate the annual kWh required to operate the proposed building.
Exception 2 to 140.0(b)1: If the applicant demonstrates that conditions exist where excessive shading occurs, a performance equivalency approved by the Building Official may be used as an alternative.
Exception 3 to 140.0(b)1: Vegetative roofs covering 35 percent of the roof area or greater, meeting all relevant code requirements including considerations for wind, fire, and structural loads.
(Ord. No. 07-2020, § 2, 10-21-2020)
Get a plain-English answer with a citation back to this text.
Ask AI about this code