Carlsbad Municipal Code Ch. 2.32 Cross-Connection Control Program

Carlsbad Municipal Code · 2026-10 edition · updated 2026-10-04 · Carlsbad

Cite as: Carlsbad Municipal Code Chapter 2.32 · Text as of 2026-10-04

§ 2.32.010. Purpose of provisions.

The purpose of this chapter is to:

A. Protect the public water supply against actual or potential contamination through cross connections by containing within the customer's system, sources of contamination that may occur within a customer's premises because of some undiscovered or unauthorized cross-connection on the premises;

B. To provide for the maintenance of a continuing program of cross-connection control which will systematically and effectively prevent the contamination or pollution of the District's water and recycled water systems.

(Ord. 51, 10/7/2025)

Exceptions & meaning →

§ 2.32.020. Adopted by reference.

A. Article I of Group 4 of Subchapter 1 of Chapter 5 of Title 17 of the California Administrative Code entitled "Drinking Water Supplies" (17 CAC Section 7583 et seq.) relating to the implementation of the cross-connection control program and provisions for backflow protection, testing and maintenance of records of locations, tests and repairs of backflow prevention devices and its successor regulations within the code are adopted by reference and supplemented and implemented by this chapter.

B. Backflow testing requirements and passing test criteria shall be determined in accordance with the most recent requirements and/or recommendations of the California Department of Public Health's approved laboratory.

C. The California Regional Water Quality Control Board, San Diego Region, issues orders that regulate recycled water use site conditions and inspection requirements within the District. All requirements of the current order shall be deemed part of this chapter.

(Ord. 51, 10/7/2025)

Exceptions & meaning →

§ 2.32.030. Backflow prevention assembly removal.

Approval must be obtained from the District before a backflow prevention assembly is removed or relocated.

A. The use of an assembly may be discontinued and the assembly removed from service upon presentation of sufficient evidence to the District to verify that a hazard no longer exists or is not likely to be created in the future. The District shall make the determination of whether a hazard exists or may exist in the future.

B. An assembly may be relocated following confirmation by the District that the relocation will continue to provide the required protection and satisfy installation requirements. A retest, performed at the customer's expense, will be required following relocation of the assembly.

C. An assembly may be removed for repair, provided the water use is either discontinued until the repair is completed and the assembly is returned to service, or the service connection is equipped with other backflow protection approved by the District. A retest, at the customer's expense, will be required following the repair of the assembly.

D. An assembly may be removed and replaced provided the water use is discontinued until the replacement assembly is installed and retested at the customer's cost. All replacement assemblies must be approved by the District.

(Ord. 51, 10/7/2025)

Exceptions & meaning →

§ 2.32.040. Site supervisor.

A. At each premise where recycled water is used or where it is necessary in the opinion of the District, a site supervisor shall be designated by and at the expense of the customer. This site supervisor shall be responsible for complying with applicable rules and regulations relating to recycled water use, monitoring of backflow prevention assemblies and for avoidance of cross connections.

B. The site supervisor shall attend District approved training in the use of recycled water. The site supervisor shall be responsible for monthly tailgate trainings as well as training new employees prior to their assignment to a recycled water use site. Documentation of these trainings must be made available during the annual walk-through inspection.

C. In the event of the potential for contamination or pollution of either the public or the customer's potable water system due to a cross-connection on the premises, the District shall be immediately notified by the site supervisor so that appropriate measures may be taken to overcome the potential contamination or pollution.

D. The customer shall inform the District of the site supervisor's identity (name, address, and telephone number) on an annual basis and whenever a change occurs.

E. Failure to comply with site supervisor requirements may result in discontinuance of water service.

(Ord. 51, 10/7/2025)

Exceptions & meaning →

§ 2.32.050. Water system survey.

A. Backflow prevention assemblies will be required per the current edition of the City's Engineering Standards. These backflow assemblies shall be tested by a tester who meets the requirements for a backflow assembly tester per this chapter upon installation and at the customer's expense. The test must meet passing criteria as stated in Section 2.32.020.

B. The District may require an on-premises inspection to evaluate cross-connection hazards. The Public Works Director will transmit a written notice requesting an inspection appointment to each affected customer. Any customer who cannot or will not allow an on-premises inspection of their piping system shall be required to install the backflow prevention assembly the District considers necessary.

C. The Public Works Director may, at his or her discretion, require a re-inspection for cross-connection hazards of any premises to which the District serves water. The District will transmit a written notice requesting an inspection appointment to each affected customer.

D. Any customer who cannot or will not allow an on-premises inspection of the customer's piping system must install the backflow prevention assembly the Public Works Director considers necessary. In addition, the District may use any lawful procedure to enter and inspect any premises.

(Ord. 51, 10/7/2025)

Exceptions & meaning →

§ 2.32.060. Customer notification.

A. Assembly Installation.

  1. The Public Works Director will notify the customer of the survey findings, listing the corrective actions to be taken if any are required. A period of thirty days will be given to complete all corrective actions required including the installation of backflow assemblies and passing test results submitted to the District. Backflow assembly installation standards will be in accordance with the current edition of the City's Engineering Standards.

  2. A second notice will be sent to each customer who does not take the required corrective actions prescribed in the first notice within the thirty calendar days allowed. The second notice will give the customer a two-week period to take the required corrective action.

  3. A third and final notice shall be sent to each customer who does not take the required corrective actions as prescribed in the first two notices. The final notice will give the customer ten days to take the required action. If the customer fails to complete the corrective action within the ten-day period, the District shall terminate water service to the affected customer until the required corrective actions are taken and the customer has paid all applicable fees associated with water service termination.

B. Testing and Maintenance.

  1. The Public Works Director will notify each affected customer in writing thirty days prior to the due date that the backflow prevention assembly installed on their service connection must be tested, repaired if necessary and then retested. This written notice will include the form the customer must complete and resubmit to the District. The customer shall have a certified tester perform the test and document the results of the testing on the prescribed form. The customer is responsible for ensuring that the completed form is returned to the District in the prescribed time frame. Tests that do not meet passing criteria will not be accepted.

  2. A second notice shall be sent to each customer who does not have the backflow prevention assembly tested as prescribed in the first notice within the thirty-calendar-day period allowed. The second notice will give the customer a two-week period to have the backflow prevention assembly tested with passing test criteria.

  3. A third and final notice shall be sent to each customer who does not have the backflow prevention assembly tested as prescribed in the first two notices. The final notice will give the customer ten days to have the backflow prevention assembly tested with passing criteria. If no action is taken within the ten-day period, the District shall terminate water service to the affected customer. Water service shall not be reactivated until the customer has paid all applicable fees associated with water service termination and the District has been notified by an approved tester that they have been contracted to perform the backflow assembly test. The District will make an appointment with the tester to restore water service so that the test may be performed. Any needed repairs and a passing re-test must be completed within five business days or water service will be discontinued, with all applicable fees being reapplied.

(Ord. 51, 10/7/2025)

Exceptions & meaning →

§ 2.32.070. Retrofitting fire protection systems with backflow prevention assemblies.

A. Upon modification to existing fire protection systems that are not currently protected by either a reduced pressure principle detector assembly (RPDA) or a double check detector assembly (DCDA), the District will require the fire service supply line be retrofitted with either a DCDA or an RPDA when any of the following occurs:

  1. Any change in the fire protection water supply that would require an upgraded increase in the fire service supply line;

  2. Any renovation work to a structure or structures involving changes and/or additions to the fire sprinkler system, which require an increase in the minimum approved fire flow requirements from the underground fire service supply line;

  3. When a leak is detected in the underground backflow swing-check valve, requiring replacement;

  4. Any failure in the post indicator valve system, which would require more work than the standard maintenance procedures;

  5. Anytime a fire service supply line for an existing fire protection system fails, including maintenance, testing, and seismic failures, and the fire protection system shall be retrofitted with approved backflow prevention assemblies.

B. In all cases of a retrofit, the fire protection system shall be hydraulically calculated to meet the minimum fire flow demand of the fire sprinkler system. This determination shall be based on compliance with the National Fire Protections Association's standard for minimum design and water flow requirements for sprinkler systems.

C. The District shall determine the degree of hazard to determine whether the fire service must be retrofitted with a DCDA or an RPDA.

D. Detector assemblies will be installed per the current edition of the City's Engineering Standards.

(Ord. 51, 10/7/2025)

Exceptions & meaning →

§ 2.32.080. Water service termination.

A. When the District encounters water uses that represent a clear and immediate hazard to the water supply that cannot be immediately abated, the District shall institute the procedure for discontinuing the District water service.

B. Conditions or water uses that create a basis for water service termination shall include, but are not limited to the following items:

  1. Refusal to install a required backflow prevention assembly;

  2. Refusal to test a backflow prevention assembly;

  3. Refusal to repair a faulty backflow prevention assembly;

  4. Refusal to replace a faulty backflow prevention assembly;

  5. Direct or indirect connection between the public water system and a sewer line;

  6. Unprotected direct or indirect connection between the public water system and a system or equipment containing contaminants;

  7. Unprotected direct or indirect connection between the public water system and an auxiliary water system;

  8. A situation which presents an immediate health hazard to the public water system.

C. For conditions 1, 2, 3 or 4, the District will terminate service to a customer's premises after three written notices have been sent specifying the corrective action needed and the time period in which it must be done. If no action is taken within the allowed time period, water service shall be terminated. The water service will remain inactive until correction of violations has been approved by the District and payment received for all applicable fees associated with water service termination.

D. For conditions 5, 6, 7 or 8, the District will take the following steps:

  1. Make reasonable effort to advise customer of intent to terminate water service;

  2. Terminate water supply and lock service valve. The water service will remain inactive until correction of violations has been approved by the District and payment received for all applicable fees associated with water service termination.

(Ord. 51, 10/7/2025)

Exceptions & meaning →

§ 2.32.090. Requirements for backflow prevention assembly testers.

A. Competency in all phases of backflow prevention assembly testing and repair must be demonstrated by means of education and/or experience to obtain certification.

B. The following are minimum requirements:

  1. Applicants shall hold and submit a copy to the District of a valid backflow prevention assembly tester certificate from the American Water Works Association (AWWA) California-Nevada Section, American Backflow Prevention Association (ABPA), or have equivalent certification in the opinion of the District and the California Department of Public Health.

  2. All backflow testers shall submit to the District current gauge calibration certificates for test kits to be used within the District service area. Gauges must undergo an annual calibration check. The tester shall be responsible for the competency and accuracy of all tests and reports prepared by him or her.

C. A tester may have his or her testing privileges revoked or suspended by the District for improper testing, repairs and/or reporting.

(Ord. 51, 10/7/2025)

Exceptions & meaning →

§ 2.32.100. Recycled water use.

A. The inspection of recycled water use sites will be performed per the requirements of the State of California Department of Public Health, County of San Diego Department of Environmental Health, California Regional Water Quality Control Board, San Diego Region, or other regulatory agency or as determined by the District.

B. The recycled water user shall provide the District with an accurate set of controller charts. Each chart is to be a reduced drawing of the as-built system. The chart shall use a different color to show the area of coverage for each station.

(Ord. 51, 10/7/2025)

Exceptions & meaning →

§ 2.32.110. Fees.

Fees to implement, maintain, administer, and enforce this chapter shall be established by resolution of the Board.

(Ord. 51, 10/7/2025)

Exceptions & meaning →

§ 2.32.120. Violations.

It is unlawful for any person to violate any provision or fail to comply with any requirement of this chapter. Any person violating any of the provisions or failing to comply with any of the provisions of this chapter shall be guilty of a misdemeanor and shall be punished by a fine of not more than one thousand dollars, or by imprisonment in the County Jail for a period not exceeding six months, or by both.

(Ord. 51, 10/7/2025)

Exceptions & meaning →

§ 2.32.130. Severability.

If any section, subsection, subdivision, paragraph, sentence, clause, or phrase of this chapter, or any part thereof, is for any reason held to be invalid, such decision shall not affect the validity of the remaining portions of this chapter or any part thereof. The Board declares that it would have passed each section, subsection, subdivision, paragraph, sentence, clause, or phrase, thereof, irrespective of the fact that any one or more sections, subsections, subdivision, paragraphs, sentences, clauses, or phrases be declared invalid.

(Ord. 51, 10/7/2025)