Appendix A — GENERAL REQUIREMENTS
Section A107 — PROTECTION OF PUMPS AND WATER STORAGE FACILITIES
2025 California Wildland-Urban Interface Code (Title 24, Part 7.5) · 2025 edition · updated 2026-07-27 · California
A107.1 General. ¶
The reliability of the water supply shall be in accordance with Sections A107.2 through A107.5.
A107.2 Objective. ¶
The intent of this section is to increase the reliability of water storage and pumping facilities and to protect such systems against loss from intrusion by fire.
A107.3 Fuel modification area. ¶
Water storage and pumping facilities shall be provided with a defensible space of not less than 30 feet (9144 mm) clear of nonfire-resistive vegetation or growth around and adjacent to such facilities.
Persons owning, controlling, operating or maintaining water storage and pumping systems requiring this defensible space are responsible for clearing and removing nonfire-smart vegetation and maintaining the defensible space on the property owned, leased or controlled by said person.
A107.4 Trees. ¶
Portions of trees that extend to within 30 feet (9144 mm) of combustible portions of water storage and pumping facilities shall be removed.
A107.5 Protection of electrical power supplies. ¶
Where electrical pumps are used to provide the required water supply, such pumps shall be connected to a standby power source to automatically maintain electrical power in the event of power loss. The standby power source shall be capable of providing power for not less than 2 hours in accordance with Chapter 27 of the California Building Code, Section 1203 of the California Fire Code and the California Electrical Code.
Exception: A standby power source is not required where the primary power service to pumps is underground as approved by the code official.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Wildland-Urban Interface Code (Title 24, Part 7.5)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — WILDLAND-URBAN INTERFACE AREAS
- Chapter 4 — WILDLAND-URBAN INTERFACE AREA REQUIREMENTS
- Chapter 5 — SPECIAL BUILDING CONSTRUCTION REGULATIONS
- Chapter 6 — FIRE PROTECTION REQUIREMENTS
- Chapter 7 — REFERENCED STANDARDS
-
▸ Appendix A — GENERAL REQUIREMENTS
Overview- Section A101 — GENERAL
- Section A102 — VEGETATION CONTROL
- Section A103 — ACCESS RESTRICTIONS
- Section A104 — IGNITION SOURCE CONTROL
- Section A105 — CONTROL OF STORAGE
- Section A106 — DUMPING
- Section A107 — PROTECTION OF PUMPS AND WATER STORAGE FACILITIES
- Section A108 — LAND USE LIMITATIONS
- Section A109 — REFERENCED STANDARDS
- Appendix B — VEGETATION MANAGEMENT PLAN
- Appendix C — COMMUNITY WILDLAND-URBAN INTERFACE (WUI) FIRE HAZ…
- Appendix D — MODEL ORDINANCE FOR FIRE HAZARD SEVERITY ZONE ADO…
- Appendix E — RESERVED
- Appendix F — CHARACTERISTICS OF FIRE-SMART VEGETATION
- Appendix G — VOLUNTARY HOME-HARDENING RECOMMENDATIONS
- Appendix H — REFERENCED CALIFORNIA DOCUMENTS
- Appendix I — BOARD OF APPEALS