Skip to content

Chapter 10 — CHIMNEYS AND FIREPLACES

Section R1001 — MASONRY FIREPLACES

2025 California Residential Code (Title 24, Part 2.5) · 2025 edition · updated 2026-07-29 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

R1001.1 General.

Masonry fireplaces shall be constructed in accordance with this section and the applicable provisions of Chapters 3 and 4.

TABLE R1001.1—SUMMARY OF REQUIREMENTS FOR MASONRY FIREPLACES AND CHIMNEYS

** ITEM** ** LETTERa** ** REQUIREMENTS**
Hearth slab thickness A 4 inches
Hearth extension (each side of opening) B 8-inch fireplace opening < 6 square feet.
12-inch fireplace opening ≥ 6 square feet.
Hearth extension (front of opening) C 16-inch fireplace opening < 6 square feet.
20-inch fireplace opening ≥ 6 square feet.
Hearth slab reinforcing D Reinforced to carry its own weight and all imposed loads.
Thickness of wall of firebox E 10-inch solid brick or 8 inches where a firebrick lining is used.
Joints in firebrick1/4-inch maximum.
Distance from top of opening to throat F 8 inches
Smoke chamber wall thickness
Unlined walls
G 6 inches
8 inches
Chimney
Vertical reinforcingb
H Four No. 4 full-length bars for chimney up to 40 inches wide.
Add two No. 4 bars for each additional 40 inches or fraction of
width or each additional flue.
Horizontal reinforcing J 1/4-inch ties at 18 inches and two ties at each bend in vertical steel.
Bond beams K No specified requirements.
Fireplace lintel L Noncombustible material.
Chimney walls with flue lining M Solid masonry units or hollow masonry units grouted solid with not
less than 4-inch nominal thickness.
Distances between adjacent flues See Section R1003.13.
Effective flue area (based on area of fireplace opening) P See Section R1003.15.
Clearances
Combustible material
Mantel and trim
Above roof
R See Sections R1001.11 and R1003.18.
See Section R1001.11, Exception 4.
3 feet at roofline and 2 feet at 10 feet.
Anchorageb
Strap Number
Embedment into chimney
Fasten to
Bolts
S 3/16-inch × 1-inch
Two
12 inches hooked around outer bar with 6-inch extension.
4 joists
Two1/2-inch diameter.
Footing
Thickness
Width
T 12 inches min.
6 inches each side of fireplace wall.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square foot = 0.0929 m2.
Note: This table provides a summary of major requirements for the construction of masonry chimneys and fireplaces. Letter references are to Figure R1001.1, which shows
examples of typical construction. This table does not cover all requirements, nor does it cover all aspects of the indicated requirements. For the actual mandatory require-
ments of the code, see the indicated section of text.
a. The letters refer to Figure R1001.1.
b. Not required in Seismic Design Category A or B.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

CHIMNEYS AND FIREPLACES

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

FIGURE R1001.1—FIREPLACE AND CHIMNEY DETAILS

R1001.2 Footings and foundations.

Footings for masonry fireplaces and their chimneys shall be constructed of concrete or solid masonry not less than 12 inches (305 mm) thick and shall extend not less than 6 inches (152 mm) beyond the face of the fireplace or foundation wall on all sides. Footings shall be founded on natural, undisturbed earth or engineered fill below frost depth. In areas not subjected to freezing, footings shall be not less than 12 inches (305 mm) below finished grade.

R1001.2.1 Ash dump cleanout. Cleanout openings located within foundation walls below fireboxes, where provided, shall be equipped with ferrous metal or masonry doors and frames constructed to remain tightly closed except when in use. Cleanouts shall be located to allow access so that ash removal will not create a hazard to combustible materials.

R1001.3 Seismic reinforcing.

Masonry or concrete chimneys in all structures regulated by this code assigned to Seismic Design Category C, D 0, D 1 or D 2 shall be reinforced. Reinforcing shall conform to the requirements set forth in Table R1001.1 and Section R606.

R1001.3.1 Vertical reinforcing. For chimneys up to 40 inches (1016 mm) wide, four No. 4 continuous vertical bars shall be placed between wythes of solid masonry or within the cells of hollow unit masonry and grouted in accordance with Section R606. Grout

10-4 2025 CALIFORNIA RESIDENTIAL CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

CHIMNEYS AND FIREPLACES

shall be prevented from bonding with the flue liner so that the flue liner is free to move with thermal expansion. For chimneys more than 40 inches (1016 mm) wide, two additional No. 4 vertical bars shall be provided for each additional flue incorporated into the chimney or for each additional 40 inches (1016 mm) in width or fraction thereof. R1001.3.2 Horizontal reinforcing. Vertical reinforcement shall be placed within [1] / 4 -inch (6.4 mm) ties, or other reinforcing of equivalent net cross-sectional area, placed in the bed joints in accordance with Section R606 at not less than every 18 inches (457 mm) of vertical height. Two such ties shall be installed at each bend in the vertical bars.

R1001.4 Seismic anchorage.

Masonry or concrete chimneys in all structures regulated by this code assigned to Seismic Design Category C, D 0, D 1 or D 2 shall be anchored at each floor, ceiling or roof line more than 6 feet (1829 mm) above grade, except where constructed completely within the exterior walls. Anchorage shall conform to the requirements of Section R1001.4.1. R1001.4.1 Anchorage. Two [3] / 16 -inch by 1-inch (5 mm by 25 mm) straps shall be embedded not less than 12 inches (305 mm) into the chimney. Straps shall be hooked around the outer bars and extend 6 inches (152 mm) beyond the bend. Each strap shall be fastened to not less than four floor ceiling or floor joists or rafters with two [1] / 2 -inch (12.7 mm) bolts. R1001.4.1.1 Cold-formed steel framing. Where cold-formed steel framing is used, the location where the [1] / 2 -inch (12.7 mm) bolts are used to attach the straps to the framing shall be reinforced with not less than a 3-inch × 3-inch × 0.229-inch (76 mm × 76 mm × 5.8 mm) steel plate on top of the strap that is screwed to the framing with not fewer than seven No. 6 screws for each bolt.

R1001.5 Firebox walls.

Masonry fireboxes shall be constructed of solid masonry units, hollow masonry units grouted solid, stone or concrete. Where a lining of firebrick not less than 2 inches (51 mm) thick or other approved lining is provided, the minimum thickness of back and sidewalls shall each be 8 inches (203 mm) of solid masonry, including the lining. The width of joints between firebricks shall not be greater than [1] / 4 inch (6.4 mm). Where a lining is not provided, the total minimum thickness of back and side walls shall be 10 inches (254 mm) of solid masonry. Firebrick shall conform to ASTM C27 or C1261 and shall be laid with medium- duty refractory mortar conforming to ASTM C199.

R1001.5.1 Steel fireplace units. Installation of steel fireplace units with solid masonry to form a masonry fireplace is permitted where installed either in accordance with the requirements of their listing or the requirements of this section. Steel fireplace units incorporating a steel firebox lining shall be constructed with steel not less than [1] / 4 inch (6.4 mm) thick, and an air-circulating chamber that is ducted to the interior of the building. The firebox lining shall be encased with solid masonry to provide a total thickness at the back and sides of not less than 8 inches (203 mm), of which not less than 4 inches (102 mm) shall be of solid masonry or concrete. Circulating air ducts used with steel fireplace units shall be constructed of metal or masonry.

R1001.6 Firebox dimensions.

The firebox of a concrete or masonry fireplace shall have a depth of not less than 20 inches (508 mm). The throat shall be not less than 8 inches (203 mm) above the fireplace opening. The throat opening shall be not less than 4 inches (102 mm) deep. The cross-sectional area of the passageway above the firebox, including the throat, damper and smoke chamber, shall be not less than the cross-sectional area of the flue.

Exception: Rumford fireplaces shall be permitted provided that the depth of the fireplace is not less than 12 inches (305 mm) and not less than one-third of the width of the fireplace opening, that the throat is not less than 12 inches (305 mm) above the lintel and is not less than one-twentieth the cross-sectional area of the fireplace opening.

R1001.7 Lintel and throat.

Masonry over a fireplace opening shall be supported by a lintel of noncombustible material. The minimum required bearing length on each end of the fireplace opening shall be 4 inches (102 mm). The fireplace throat or damper shall be located not less than 8 inches (203 mm) above the lintel.

R1001.7.1 Damper. Masonry fireplaces shall be equipped with a ferrous metal damper located not less than 8 inches (203 mm) above the top of the fireplace opening. Dampers shall be installed in the fireplace or the chimney venting the fireplace, and shall be operable from the room containing the fireplace.

R1001.8 Smoke chamber.

Smoke chamber walls shall be constructed of solid masonry units, hollow masonry units grouted solid, stone or concrete. The total minimum thickness of front, back and side walls shall be 8 inches (203 mm) of solid masonry. The inside surface shall be parged smooth with refractory mortar conforming to ASTM C199. Where a lining of firebrick not less than 2 inches (51 mm) thick, or a lining of vitrified clay not less than [5] / 8 inch (16 mm) thick, is provided, the total minimum thickness of front, back and side walls shall be 6 inches (152 mm) of solid masonry, including the lining. Firebrick shall conform to ASTM C1261 and shall be laid with medium-duty refractory mortar conforming to ASTM C199. Vitrified clay linings shall conform to ASTM C315.

R1001.8.1 Smoke chamber dimensions. The inside height of the smoke chamber from the fireplace throat to the beginning of the flue shall not be greater than the inside width of the fireplace opening. The inside surface of the smoke chamber shall not be inclined more than 45 degrees (0.79 rad) from vertical where prefabricated smoke chamber linings are used or where the smoke chamber walls are rolled or sloped rather than corbeled. Where the inside surface of the smoke chamber is formed by corbeled masonry, the walls shall not be corbeled more than 30 degrees (0.52 rad) from vertical.

R1001.9 Hearth and hearth extension.

Masonry fireplace hearths and hearth extensions shall be constructed of concrete or masonry, supported by noncombustible materials, and reinforced to carry their own weight and all imposed loads. Combustible material shall not remain against the underside of hearths and hearth extensions after construction.

R1001.9.1 Hearth thickness. The minimum thickness of fireplace hearths shall be 4 inches (102 mm).

R1001.9.2 Hearth extension thickness. The minimum thickness of hearth extensions shall be 2 inches (51 mm).

Exception: Where the bottom of the firebox opening is raised not less than 8 inches (203 mm) above the top of the hearth extension, a hearth extension of not less than [3] / 8 -inch-thick (10 mm) brick, concrete, stone, tile or other approved noncombustible material is permitted.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

CHIMNEYS AND FIREPLACES

R1001.10 Hearth extension dimensions.

Hearth extensions shall extend not less than 16 inches (406 mm) in front of and not less than 8 inches (203 mm) beyond each side of the fireplace opening. Where the fireplace opening is 6 square feet (0.6 m [2] ) or larger, the hearth extension shall extend not less than 20 inches (508 mm) in front of and not less than 12 inches (305 mm) beyond each side of the fireplace opening.

R1001.11 Fireplace clearance.

Wood beams, joists, studs and other combustible material shall have a clearance of not less than 2 inches (51 mm) from the front faces and sides of masonry fireplaces and not less than 4 inches (102 mm) from the back faces of masonry fireplaces. The airspace shall not be filled, except for noncombustible material or to provide fireblocking in accordance with Section R1001.12.

Exceptions:

  1. Masonry fireplaces listed and labeled for use in contact with combustibles in accordance with UL 127 and installed in accordance with the manufacturer’s instructions are permitted to have combustible material in contact with their exterior surfaces.

  2. Where masonry fireplaces are part of masonry or concrete walls, combustible materials shall not be in contact with the masonry or concrete walls less than 12 inches (306 mm) from the inside surface of the nearest firebox lining.

  3. Exposed combustible trim and the edges of sheathing materials such as wood siding, flooring and gypsum board shall be permitted to abut the masonry fireplace sidewalls and hearth extension in accordance with Figure R1001.11, provided that such combustible trim or sheathing is not less than 8 inches (203 mm) from the inside surface of the nearest firebox

For SI: 1 inch = 25.4 mm.

masonry, that is designed to absorb and store heat from a solid-fuel fire built in the firebox by routing the exhaust gases through

e fireplace opening is 6 square feet (0.6 m2) or larger, such combustible tri
masonry fireplace sidewalls and hearth extension provided that such co
inches (305 mm) from the inside surface of the nearest firebox lining.
ustible mantels or trim is permitted to be placed directly on the masonry f
ng providing such combustible materials are not placed within 6 inches (1
aterial within 12 inches (306 mm) of the fireplace opening shall not projec
mm) distance from such an opening.
FIGURE R1001.11—CLEARANCE FROM COMBUSTIBLES
MASONRY
COMBUSTIBLE SHEATHING
EDGE ABUTTING MASONRY
12 IN. FROM FIREBOX
FRAME WALL
2 IN. CLEARANCE (AIRSPA
TO COMBUSTIBLE FRAMIN
WOOD MANTEL
cking. Fireplace fireblocking shall comply with the provisions of Section R
ories. Listed and labeled fireplace accessories shall be installed in accorda
r’s instructions. Fireplace accessories shall comply with UL 907.
SECTION R1002—MASONRY HEATERS
onry heater is a heating appliance constructed of concrete or solid maso

cking. Firepl
ories. Listed
r’s instructio
onry heater

WOO
cking. Firepl
ories. Listed
r’s instructio
onry heater

WOO
cking. Firepl
ories. Listed
r’s instructio
onry heater

WOO
a
a
n
is

c
n
s.
a

D
e f
d
F


M
ir
la
ir
he

A
e
b
e
S
a

N
bl
e
pl
E
ti

T
o
le
a
C
n

E
m
cc
s s
—M
on
p
es
h
A
s
ly
s
a
S
tr
ly
s
a
S
tr
ly
s
a
S
tr
ly
s
a
S
tr
ly
s
a
S
tr
ly
s
a
S
tr
ly
s
a
S
tr
cking. Firepl
ories. Listed
r’s instructio
onry heater

WOO
a
a
n
is

c
n
s.
a

D
e f
d
F


M
ir
la
ir
he

A
e
b
e
S
a

N
bl
e
pl
E
ti

T
o
le
a
C
n

E
c
d
ce
TI
g

L
ki
f

O
a

n
ir
ac
N
p
g
ep
c

pl
cking. Firepl
ories. Listed
r’s instructio
onry heater

WOO
a
a
n
is

c
n
s.
a

D
e f
d
F


M
ir
la
ir
he

A
e
b
e
S
a

N
bl
e
pl
E
ti

T
o
le
a
C
n

E
c
d
ce
TI
g

L
ki
f

O
a

n
ir
ac
N
p
g
ep
c

pl
sh
l
e
R1
ia
a
ac
ss
0
n
ll
e
o
0
c
co
a
rie
2
e c
co
a
rie
2
e c
co
a
rie
2
e c
co
a
rie
2
e c
co
a
rie
2
e c
co
a
rie
2
e c
co
a
rie
2
e c
co
a
rie
2
e c
co
a
rie
2
e c
co
a
rie
2
e c

internal heat exchange channels in which the flow path downstream of the firebox includes flow in a horizontal or downward direction before entering the chimney and that delivers heat by radiation from the masonry surface of the heater.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Residential Code (Title 24, Part 2.5)
2025 California Residential Code (Title 24, Part 2.5)
  1. Chapter 1 — ADMINISTRATION
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — BUILDING PLANNING
  4. Chapter 4 — FOUNDATIONS
  5. Chapter 5 — FLOORS
  6. Chapter 6 — WALL CONSTRUCTION
  7. Chapter 7 — WALL COVERING
  8. Chapter 8 — ROOF-CEILING CONSTRUCTION
  9. Chapter 9 — ROOF ASSEMBLIES
  10. Chapter 10 — CHIMNEYS AND FIREPLACES
  11. Chapter 44 — REFERENCED STANDARDS
  12. Appendix AA — BOARD OF APPEALS
  13. Appendix AB — PERMIT FEES
  14. Appendix AC — RESERVED
  15. Appendix BA — RESERVED
  16. Appendix BB — TINY HOUSES
  17. Appendix BC — RESERVED
  18. Appendix BD — RESERVED
  19. Appendix BE — RADON CONTROL METHODS
  20. Appendix BF — PATIO COVERS
  21. Appendix BG — SOUND TRANSMISSION
  22. Appendix BH — AUTOMATIC VEHICULAR GATES
  23. Appendix BI — LIGHT STRAW-CLAY CONSTRUCTION
  24. Appendix BJ — STRAWBALE CONSTRUCTION
  25. Appendix BK — COB CONSTRUCTION (MONOLITHIC ADOBE)
  26. Appendix BL — HEMP-LIME (HEMPCRETE) CONSTRUCTION
  27. Appendix BM — 3D-PRINTED BUILDING CONSTRUCTION
  28. Appendix BN — EXTENDED PLATE WALL CONSTRUCTION
  29. Appendix BO — EXISTING BUILDINGS AND STRUCTURES
  30. Appendix CA — RESERVED
  31. Appendix CB — RESERVED
  32. Appendix CC — RESERVED
  33. Appendix CD — RESERVED
  34. Appendix CE — RESERVED
  35. Appendix CF — RESERVED
  36. Appendix CG — NONSEWERED SANITATION SYSTEMS
  37. Appendix CH — PRIVATE SEWAGE DISPOSAL
  38. Appendix CI — SWIMMING POOL SAFETY ACT
  39. Appendix CJ — EMERGENCY HOUSING
  40. Appendix CK — AREAS PROTECTED BY THE FACILITIES OF THE CENTRAL…

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.