Appendix BK — COB CONSTRUCTION (MONOLITHIC ADOBE)
Section BK108 — FIRE RESISTANCE
2025 California Residential Code (Title 24, Part 2.5) · 2025 edition · updated 2026-07-27 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
BK108.1 Fire-resistance rating. ¶
Cob walls that comply with Table BK108.1 have a 2-hour fire-resistance rating.
TABLE BK108.1—TWO-HOUR FIRE-RESISTANCE-RATED COB WALLS
| ALLOWABLE SUPER- IMPOSED LOAD (plf) |
DENSITYa, d (pcf) |
MINIMUM COMPRES- SIVE STRENGTH PER SECTION BK106.6.1 (psi) |
WALL-TYPE REINFORCEMENT PER TABLE BK105.3 |
MINIMUM THICKNESSc, e, f AT TOP OF WALL (inches) |
MINIMUM THICKNESSc, e, f AT BOTTOM OF WALL (inches) |
|---|---|---|---|---|---|
| 1,200 | 100 | 85 | E | 9 | 12 |
| 475 | ≥ 50 pcf: less than 40 inches from top of wall |
40b | E or F | 8 | 12 |
| 475 | ≥ 70 pcf: from 40 inches to 80 inches from top of wall |
55b | 55b | 55b | 55b |
| 475 | ≥ 90 pcf: more than 80 inches from top of wall |
85 | 85 | 85 | 85 |
| Nonload bearing | 50 to 100 | ≥ 60 psi < 60 psib |
E or F | 9 | 9 |
| For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 0.45 kg, 1 pound per cubic foot = 16.02 kg/m3. a. Density is to be measured at equilibrium moisture content. Average wall density shall be within ±5 pcf of the tabulated value. b. Requires an approved engineered design per Section BK106.6. c. Cob thickness only. The interior and exterior cob faces shall be permitted to be unfinished or receive any plaster finish allowed by this appendix. d. Cob walls with more than one density shall be built with heavier densities below lighter densities. e. Minimum cob wall thickness shall be whichever is greater in Tables BK105.3, BK106.11(1) and BK108.1. f. Wall thicknesses less than 10 inches require an engineered design. |
BK108.2 Clearance to fireplaces and chimneys. ¶
Cob walls or other cob surfaces shall not require clearance to fireplaces and chimneys, except where clearance to noncombustibles is required by the manufacturer’s instructions.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Residential Code (Title 24, Part 2.5)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — BUILDING PLANNING
- Chapter 4 — FOUNDATIONS
- Chapter 5 — FLOORS
- Chapter 6 — WALL CONSTRUCTION
- Chapter 7 — WALL COVERING
- Chapter 8 — ROOF-CEILING CONSTRUCTION
- Chapter 9 — ROOF ASSEMBLIES
- Chapter 10 — CHIMNEYS AND FIREPLACES
- Chapter 44 — REFERENCED STANDARDS
- Appendix AA — BOARD OF APPEALS
- Appendix AB — PERMIT FEES
- Appendix AC — RESERVED
- Appendix BA — RESERVED
- Appendix BB — TINY HOUSES
- Appendix BC — RESERVED
- Appendix BD — RESERVED
- Appendix BE — RADON CONTROL METHODS
- Appendix BF — PATIO COVERS
- Appendix BG — SOUND TRANSMISSION
- Appendix BH — AUTOMATIC VEHICULAR GATES
- Appendix BI — LIGHT STRAW-CLAY CONSTRUCTION
- Appendix BJ — STRAWBALE CONSTRUCTION
-
▸ Appendix BK — COB CONSTRUCTION (MONOLITHIC ADOBE)
Overview- Section BK101 — GENERAL
- Section BK102 — DEFINITIONS
- Section BK103 — MATERIALS, MIXING AND INSTALLATION
- Section BK104 — FINISHES
- Section BK105 — COB WALLS—GENERAL
- Section BK106 — COB WALLS—STRUCTURAL
- Section BK107 — COB FLOORS
- Section BK108 — FIRE RESISTANCE
- Section BK109 — THERMAL PERFORMANCE
- Section BK110 — REFERENCED STANDARDS
- Appendix BL — HEMP-LIME (HEMPCRETE) CONSTRUCTION
- Appendix BM — 3D-PRINTED BUILDING CONSTRUCTION
- Appendix BN — EXTENDED PLATE WALL CONSTRUCTION
- Appendix BO — EXISTING BUILDINGS AND STRUCTURES
- Appendix CA — RESERVED
- Appendix CB — RESERVED
- Appendix CC — RESERVED
- Appendix CD — RESERVED
- Appendix CE — RESERVED
- Appendix CF — RESERVED
- Appendix CG — NONSEWERED SANITATION SYSTEMS
- Appendix CH — PRIVATE SEWAGE DISPOSAL
- Appendix CI — SWIMMING POOL SAFETY ACT
- Appendix CJ — EMERGENCY HOUSING
- Appendix CK — AREAS PROTECTED BY THE FACILITIES OF THE CENTRAL…