Section 8-705
California Historical Building Code (Title 24, Part 8) · 2022 edition · updated 2026-09-10 · California
STRUCTURAL REGULATIONS 8-705.1 Gravity loads. The capacity of the structure to resist gravity loads shall be evaluated and the structure strengthened as necessary. The evaluation shall include all parts of the load path. Where no distress is evident, and a complete load path is present, the structure may be assumed adequate by having withstood the test of time if anticipated dead and live loads will not exceed those historically present.
8-705.2 Wind and seismic loads. The ability of the structure to resist wind and seismic loads shall be evaluated. Wind loads shall be considered when appropriate, but need not exceed 75% of the wind loads prescribed by the regular code. The evaluation shall be based on the requirements of Section 8-706.
8.705.2.1 Any unsafe conditions in the lateral-load-resisting system shall be corrected, or alternative resistance shall be provided. When strengthening is required, additional resistance shall be provided to meet the minimum requirements of the CHBC. The strengthening measures shall be selected with the intent of meeting the performance objectives set forth in Sectio 8-701.2. The evaluation of structural members and structural systems for seismic loads shall consider the inelastic performance of structural members and their ability to maintain load-carrying capacity during the seismic loadings prescribed by the regular code.
8.705.2.2 The architect or engineer shall consider additional measures with minimal loss of, and impact to, his
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
STRUCTURAL REGULATIONS
torical materials which will reduce damage and needed repairs in future earthquakes to better preserve the historical structure in perpetuity. These additional measures shall be presented to the owner for consideration as part of the rehabilitation or restoration.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Historical Building Code (Title 24, Part 8)
- Section 8-101
- Section 8-102
- Section 8-103
- Section 8-104
- Section 8-105
- Section 8-106
- Section 8-201
- Section 8-301
- Section 8-302
- Section 8-303
- Section 8-401
- Section 8-402
- Section 8-403
- Section 8-404
- Section 8-405
- Section 8-406
- Section 8-407
- Section 8-408
- Section 8-409
- Section 8-410
- Section 8-411
- Section 8-412
- Section 8-501
- Section 8-502
- Section 8-503
- Section 8-504
- Section 8-601
- Section 8-603
- Section 8-602
- Section 8-604
- Section 8-701
- Section 8-702
- Section 8-703
- Section 8-704
- Section 8-705
- Section 8-706
- Section 8-801
- Section 8-802
- Section 8-803
- Section 8-804
- Section 8-805
- Section 8-806
- Section 8-807
- Section 8-808
- Section 8-809
- Section 8-810
- Section 8-812
- Section 8-811
- Section 8-901
- Section 8-902
- Section 8-903
- Section 8-904
- Section 8-1001
- Section 8-1003
- Section 8-1002