Section 8-811
California Historical Building Code (Title 24, Part 8) · 2019 edition · updated 2026-09-10 · California
VENEERS 8-811.1 Terra cotta and stone. Terra cotta, cast stone and natural stone veneers shall be investigated for the presence of suitable anchorage. Steel anchors shall be investigated for
TABLE8-8A STRENGTH VALUES FOR EXISTING MATERIALS
| EXISTING MATERIALS OR CONFIGURATIONS OF MATERIALS1 | STRENGTH LEVEL CAPACITY x14.594 for N/m |
|---|---|
| 1. Horizontal diaphragms2 1.1 Roofs with straight sheathing and roofing applied directly to the sheathing 1.2 Roofs with diagonal sheathing and roofing applied directly to the sheathing 1.3 Floors with straight tongue-and-groove sheathing 1.4 Floors with straight sheathing and finished wood flooring with board edges offset or perpendicular 1.5 Floors with diagonal sheathing and finished |
300 lbs per foot for seismic shear 750 lbs per foot for seismic shear 300 lbs per foot for seismic shear 1,500 lbs per foot for seismic shear 1,800 lbs per foot for seismic shear |
| 2. Crosswalls2,3 2.1 Plaster on wood or metal lath 2.2 Plaster on gypsum lath 2.3 Gypsum wallboard, unblocked edges 2.4 Gypsum wallboard, blocked edges |
Per side: 600 lbs per foot for seismic shear 550 lbs per foot for seismic shear 200 lbs per foot for seismic shear 400 lbs per foot for seismic shear |
| 3. Existing footings, wood framing, structural steel and reinforcing steel 3.1 Plain concrete footings 3.2 Douglas fir wood 3.3 Reinforcing steel 3.4 Structural steel |
f′c = 1,500 psi (10.34 MPa) unless otherwise shown by tests3 Allowable stress same as D.F. No. 13 _ft _= 40,000 lbs per square inch (124.1 N/mm2) maximum ft= 33,000 lbs per square inch (137.9 N/mm2) maximum |
1 Material must be sound and in good condition. 2 Shear values of these materials may be combined, except the total combined value shall not exceed 900 pounds per foot (13,140 N/m). 3 Stresses given may be increased for combinations of loads as specified in the regular code.
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
TABLE 8-8B STRENGTH VALUES OF NEW MATERIALS USED IN CONNECTION WITH EXISTING CONSTRUCTION
| NEW MATERIALS OR CONFIGURATIONS OF MATERIALS | STRENGTH LEVEL CAPACITY1 |
|---|---|
| 1. Horizontal diaphragms2 1.1 15/32 inch minimum plywood sheathing fastened directly over existing straight sheathing with edges of plywood located on center of individual sheathing boards and fastened with minimum #8x 11/4 inch wood screws or nails with helical threads 0.13 inch min. diameter and 11/4 inch min. length at 4 inch centers all panel edges and 12 inch centers each way in field. 1.2 Same plywood and attachments as 1.1 fastened directly over existing diagonal sheathing. 1.3 3/8 inch plywood sheathing fastened directly over existing straight or diagonal sheathing with ends and edges on centers of individual sheathing boards and fastened with #6 wood screws or nails with helical threads 0.13 inch minimum diameter and 11/4 inch min. length at 6 inch centers tall panel edges and 12 inch centers each way in field. |
1,500 lbs per foot 1,800 lbs per foot 900 lbs per foot |
| 2. Shear walls: Plywood sheathing applied directly over wood studs. No value shall be given to plywood applied over existing plaster or wood sheathing |
100 percent of the value specified in the regular code for shear walls |
| 3. Crosswalls: (special procedure only) 3.1 Plywood sheathing applied directly over wood studs. No value shall be given to plywood applied over existing plaster or wood sheathing 3.2 Drywall or plaster applied directly over wood studs 3.3 Drywall or plaster applied to sheathing over existing wood studs |
133 percent of the value specified in the regular code for shear walls 100 percent of the values in the regular code 50 percent of the values specified in the regular code |
| 4. Tension bolts a. Bolts extending entirely through unreinforced masonry walls secured with bearing plates on far side of a three-wythe- minimum wall with at least 30 square inches (19 350 mm2) of area4,5 b. All thread rod extending to the exterior face of the wall installed in adhesive9 |
5,400 lbs (24,010 N) per bolt6 2,700 lbs (12,009 N) per bolt for two-wythe walls6 3,600 lbs (16,014 N) per bolt |
| 5. Shear bolts Bolts embedded a minimum of 8 inches (203 mm) into unreinforced masonry walls and centered in a 21/2-inch-diameter (63.5 mm) hole filled with dry-pack or nonshrink grout. Through bolts with first 8 inches (203 mm) as noted above and embedded all thread rod as noted in Item 4.b5,7,9 |
1/2 inch (12.7 mm) diameter = 1050 lbs (4671 N)6 5/8 inch (15.9 mm) diameter = 1500 lbs (6672 N)6 3/4 inch (19 mm) diameter = 2250 lbs (10,008 N)6 |
| 6. Infilled walls Reinforced masonry infilled openings in existing unreinforced masonry walls. Provide keys or dowels to match reinforcing. |
Same as values specified for unreinforced masonry walls |
| 7. Reinforced masonry Masonry piers and walls reinforced per the regular code |
Same as values specified in the regular code8 |
| 8. Reinforced concrete Concrete footings, walls and piers reinforced as specified in the regular code and designed for tributary loads |
Same as values specified in the regular code8 |
1 Values are for strength level loads as defined in regular code standards. 2 Values may be adjusted for other fasteners when approved by the enforcing authority. 3 In addition to existing sheathing value. 4 Bolts to be 1 /2-inch (12.7 mm) minimum diameter. 5 Other bolt sizes, values and installation methods may be used provided a testing program is conducted in accordance with regular code standards. Bolt spacing shall not exceed 6 feet. (1830 mm) on center and shall not be less than 12 inches (305) mm) on center. 6 Other masonry based on tests or other substantiated data. 7 Embedded bolts to be tested as specified in regular code standards. 8 Stresses given may be increased for combinations of loads as specified in the regular code. 9 Adhesives shall be approved by the enforcing agency and installed in accordance with the manufacturer’s recommendations. All drilling dust shall be removed from drilled holes prior to installation.
18 2019 CALIFORNIA HISTORICAL BUILDING CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
CHAPTER 8-9
MECHANICAL, PLUMBING AND ELECTRICAL REQUIREMENTS
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Historical Building Code (Title 24, Part 8)
- Section 8-101
- Section 8-102
- Section 8-103
- Section 8-104
- Section 8-105
- Section 8-106
- Section 8-201
- Section 8-301
- Section 8-302
- Section 8-303
- Section 8-401
- Section 8-402
- Section 8-403
- Section 8-404
- Section 8-405
- Section 8-406
- Section 8-407
- Section 8-408
- Section 8-409
- Section 8-410
- Section 8-411
- Section 8-412
- Section 8-501
- Section 8-502
- Section 8-503
- Section 8-504
- Section 8-601
- Section 8-603
- Section 8-602
- Section 8-604
- Section 8-701
- Section 8-702
- Section 8-703
- Section 8-704
- Section 8-705
- Section 8-706
- Section 8-801
- Section 8-802
- Section 8-803
- Section 8-804
- Section 8-805
- Section 8-806
- Section 8-807
- Section 8-808
- Section 8-809
- Section 8-810
- Section 8-812
- Section 8-811
- Section 8-901
- Section 8-902
- Section 8-903
- Section 8-904
- Section 8-1001
- Section 8-1002
- Section 8-1003