VENEERS 8-811.1 Terra cotta and stone. Terra cotta, cast stone and natural stone veneers shall be investigated for the presence of suitable anchorage. Steel anchors shall be investigated for

TABLE8-8A STRENGTH VALUES FOR EXISTING MATERIALS

EXISTING MATERIALS OR CONFIGURATIONS OF MATERIALS1 STRENGTH LEVEL CAPACITY
x14.594 for N/m
1. Horizontal diaphragms2
1.1 Roofs with straight sheathing and roofing applied directly to the sheathing
1.2 Roofs with diagonal sheathing and roofing applied directly to the sheathing
1.3 Floors with straight tongue-and-groove sheathing
1.4 Floors with straight sheathing and finished wood flooring with board
edges offset or perpendicular
1.5 Floors with diagonal sheathing and finished
300 lbs per foot for seismic shear
750 lbs per foot for seismic shear
300 lbs per foot for seismic shear
1,500 lbs per foot for seismic shear
1,800 lbs per foot for seismic shear
2. Crosswalls2,3
2.1 Plaster on wood or metal lath
2.2 Plaster on gypsum lath
2.3 Gypsum wallboard, unblocked edges
2.4 Gypsum wallboard, blocked edges
Per side: 600 lbs per foot for seismic shear
550 lbs per foot for seismic shear
200 lbs per foot for seismic shear
400 lbs per foot for seismic shear
3. Existing footings, wood framing, structural steel and reinforcing steel
3.1 Plain concrete footings
3.2 Douglas fir wood
3.3 Reinforcing steel
3.4 Structural steel
f′c = 1,500 psi (10.34 MPa) unless otherwise shown by tests3
Allowable stress same as D.F. No. 13
_ft _= 40,000 lbs per square inch (124.1 N/mm2) maximum
ft= 33,000 lbs per square inch (137.9 N/mm2) maximum

1 Material must be sound and in good condition. 2 Shear values of these materials may be combined, except the total combined value shall not exceed 900 pounds per foot (13,140 N/m). 3 Stresses given may be increased for combinations of loads as specified in the regular code.

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION

TABLE 8-8B STRENGTH VALUES OF NEW MATERIALS USED IN CONNECTION WITH EXISTING CONSTRUCTION

NEW MATERIALS OR CONFIGURATIONS OF MATERIALS STRENGTH LEVEL CAPACITY1
1. Horizontal diaphragms2
1.1
15/32 inch minimum plywood sheathing fastened directly over existing
straight sheathing with edges of plywood located on center of individual
sheathing boards and fastened with minimum #8x 11/4 inch wood screws
or nails with helical threads 0.13 inch min. diameter and 11/4 inch min.
length at 4 inch centers all panel edges and 12 inch centers each way in
field.
1.2 Same plywood and attachments as 1.1 fastened directly over existing
diagonal sheathing.
1.3
3/8 inch plywood sheathing fastened directly over existing straight or
diagonal sheathing with ends and edges on centers of individual sheathing
boards and fastened with #6 wood screws or nails with helical threads
0.13 inch minimum diameter and 11/4 inch min. length at 6 inch centers
tall panel edges and 12 inch centers each way in field.
1,500 lbs per foot
1,800 lbs per foot
900 lbs per foot
2. Shear walls:
Plywood sheathing applied directly over wood studs. No value shall be
given to plywood applied over existing plaster or wood sheathing
100 percent of the value specified in the regular code for
shear walls
3. Crosswalls: (special procedure only)
3.1 Plywood sheathing applied directly over wood studs. No value shall be
given to plywood applied over existing plaster or wood sheathing
3.2 Drywall or plaster applied directly over wood studs
3.3 Drywall or plaster applied to sheathing over existing wood studs
133 percent of the value specified in the regular code for
shear walls
100 percent of the values in the regular code
50 percent of the values specified in the regular code
4. Tension bolts
a. Bolts extending entirely through unreinforced masonry walls secured
with bearing plates on far side of a three-wythe- minimum wall with at
least 30 square inches (19 350 mm2) of area4,5
b. All thread rod extending to the exterior face of the wall installed in
adhesive9
5,400 lbs (24,010 N) per bolt6
2,700 lbs (12,009 N) per bolt for two-wythe walls6
3,600 lbs (16,014 N) per bolt
5. Shear bolts
Bolts embedded a minimum of 8 inches (203 mm) into unreinforced
masonry walls and centered in a 21/2-inch-diameter (63.5 mm) hole filled
with dry-pack or nonshrink grout. Through bolts with first 8 inches (203
mm) as noted above and embedded all thread rod as noted in Item 4.b5,7,9
1/2 inch (12.7 mm) diameter = 1050 lbs (4671 N)6
5/8 inch (15.9 mm) diameter = 1500 lbs (6672 N)6
3/4 inch (19 mm) diameter = 2250 lbs (10,008 N)6
6. Infilled walls
Reinforced masonry infilled openings in existing unreinforced masonry
walls. Provide keys or dowels to match reinforcing.
Same as values specified for unreinforced masonry walls
7. Reinforced masonry
Masonry piers and walls reinforced per the regular code
Same as values specified in the regular code8
8. Reinforced concrete
Concrete footings, walls and piers reinforced as specified in the regular code
and designed for tributary loads
Same as values specified in the regular code8

1 Values are for strength level loads as defined in regular code standards. 2 Values may be adjusted for other fasteners when approved by the enforcing authority. 3 In addition to existing sheathing value. 4 Bolts to be 1 /2-inch (12.7 mm) minimum diameter. 5 Other bolt sizes, values and installation methods may be used provided a testing program is conducted in accordance with regular code standards. Bolt spacing shall not exceed 6 feet. (1830 mm) on center and shall not be less than 12 inches (305) mm) on center. 6 Other masonry based on tests or other substantiated data. 7 Embedded bolts to be tested as specified in regular code standards. 8 Stresses given may be increased for combinations of loads as specified in the regular code. 9 Adhesives shall be approved by the enforcing agency and installed in accordance with the manufacturer’s recommendations. All drilling dust shall be removed from drilled holes prior to installation.

18 2019 CALIFORNIA HISTORICAL BUILDING CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.