Chapter 8-9 — MECHANICAL, PLUMBING AND ELECTRICAL REQUIREMENTS
Section 8-902 — MECHANICAL
2025 California Historical Building Code (Title 24, Part 8) · 2025 edition · updated 2026-07-29 · California
8-902.1 General. Mechanical systems shall comply with the regular code unless otherwise modified by this chapter.
8-902.1.1 The provisions of the CHBC shall apply to the acceptance, location, installation, alteration, repair, relocation, replacement or addition of any heating, ventilating, air conditioning, domestic incinerators, kilns or miscellaneous heat-producing appliances or equipment within or attached to a historical building.
8-902.1.2 Existing systems which do not, in the opinion of the enforcing agency, constitute a safety hazard may remain in use.
8-902.1.3 The enforcing agency may approve any alternative to the CHBC which would achieve equivalent life safety.
8-902.2 Heating facilities. All dwelling-type occupancies covered under this chapter shall be provided with heating facilities. Woodburning or pellet stoves or fireplaces may be acceptable as heating facilities.
8-902.3 Fuel oil piping and tanks. Fuel oil piping and tanks shall comply with regular code requirements except that the enforcing agency may waive such requirements where the lack of compliance does not create a safety or environmental hazard.
8-902.4 Heat-producing and cooling equipment. Heat-producing and cooling equipment shall comply with the regular code requirements governing equipment safety, except that the enforcing agency may accept alternatives which do not create a safety hazard.
8-902.5 Combustion air.
8-902.5.1 All fuel-burning appliances and equipment shall be provided a sufficient supply of air for proper fuel combustion, ventilation and draft hood dilution.
8-902.5.2 The enforcing agency may require operational tests for combustion air systems which do not comply with applicable requirements of the regular code.
8-902.6 Venting of appliances.
8-902.6.1 Every appliance required to be vented shall be connected to an approved venting system. Venting systems shall develop a positive flow adequate to convey all combustion products to the outside atmosphere.
8-902.6.2 Masonry chimneys in structurally sound condition may remain in use for all fuel-burning appliances, provided the flue is evaluated and documentation provided that the masonry and grout are in good condition. Terra cotta chimneys and Type C metallic vents installed in concealed spaces shall not remain in use unless otherwise mitigated and approved on a case-by-case basis.
8-902.6.3 The enforcing agency may require operational tests for venting systems which do not comply with applicable requirements of the regular code.
8-902.7 Ducts.
8-902.7.1 New ducts shall be constructed and installed in accordance with applicable requirements of the regular code.
8-902.7.2 Existing duct systems which do not comply with applicable requirements of the regular code and do not, in the opinion of the enforcing agency, constitute a safety or health hazard may remain in use.
8-902.8 Ventilating systems.
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MECHANICAL, PLUMBING AND ELECTRICAL REQUIREMENTS
8-902.8.1 Ventilating systems shall be installed so that no safety hazard is created.
8-902.8.2 Grease hoods and grease hood exhaust systems shall be furnished and installed in accordance with applicable requirements of the regular code. Existing systems which are altered shall comply with the regular code.
8-902.9 Miscellaneous equipment requirements.
8-902.9.1 The following appliances and equipment shall be installed so that no safety hazard is created: warm air furnaces, space heating equipment, vented decorative appliances, floor furnaces, vented wall furnaces, unit heaters, room heaters, absorption units, refrigeration equipment, duct furnaces, infrared radiant heaters, domestic incinerators, miscellaneous heat-producing appliances and water heaters.
8-902.9.2 Storage-type water heaters shall be equipped with a temperature- and pressure-relief valve in accordance with applicable requirements of the regular code.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Historical Building Code (Title 24, Part 8)
- Chapter 8-1 — ADMINISTRATION
- Chapter 8-2 — DEFINITIONS
- Chapter 8-3 — USE AND OCCUPANCY
- Chapter 8-4 — FIRE PROTECTION
- Chapter 8-5 — MEANS OF EGRESS
- Chapter 8-6 — ACCESSIBILITY
- Chapter 8-7 — STRUCTURAL REGULATIONS
- Chapter 8-8 — ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
-
▸ Chapter 8-9 — MECHANICAL, PLUMBING AND ELECTRICAL REQUIREMENTS
- Chapter 8-10 — QUALIFIED HISTORICAL DISTRICTS, SITES AND OPEN …