Section 8-410 — AUTOMATIC SPRINKLER SYSTEMS
2025 California Historical Building Code (Title 24, Part 8) · 2025 edition · updated 2026-07-29 · California
8-410.1 Every qualified historical building or property which cannot be made to conform to the construction requirements specified in the regular code for the occupancy or use, and which constitutes a distinct fire hazard (for definition of “Distinct Hazard,” see Chapter 8-2), shall be deemed to be in compliance if provided with an automatic sprinkler system or a life safety system or other technologies as approved by the enforcing agency. (“Automatic” is defined in the regular code. “Sprinkler System” is defined in this section.)
8-410.2 When required by the CHBC, an automatic sprinkler system is defined by the following standards as adopted by the State Fire Marshal (for nonhazardous occupancies).
Buildings of four stories or less: NFPA 13R.
For floors above the fourth, NFPA 13.
Buildings with floors above 75 feet, NFPA 13.
When the building is free standing or with property line separation, two floors and 1500 square feet per floor or less, NFPA 13D.
For exterior wall and opening protection. As required by this chapter.
Exception: When the automatic sprinkler systems are used to reach compliance using this code, in three or more occasions, NFPA 13D standard shall be increased to NFPA 13R standard, or NFPA 13R standard shall be increased to a NFPA 13 standard.
8-410.3 Automatic sprinkler systems shall not be used to substitute for or act as an alternate to the required number of exits from any facility. (See Chapter 8-5 for exiting requirements.)
8-410.4 An automatic sprinkler system shall be provided in all detention facilities.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Historical Building Code (Title 24, Part 8)
- Chapter 8-1 — ADMINISTRATION
- Chapter 8-2 — DEFINITIONS
- Chapter 8-3 — USE AND OCCUPANCY
-
▸ Chapter 8-4 — FIRE PROTECTION
Overview- Section 8-401 — PURPOSE, INTENT AND SCOPE
- Section 8-402 — FIRE-RESISTIVE CONSTRUCTION
- Section 8-403 — INTERIOR FINISH MATERIALS
- Section 8-404 — WOOD LATH AND PLASTER
- Section 8-405 — OCCUPANCY SEPARATION
- Section 8-406 — MAXIMUM FLOOR AREA
- Section 8-407 — VERTICAL SHAFTS
- Section 8-408 — ROOF COVERING
- Section 8-409 — FIRE ALARM SYSTEMS
- Section 8-410 — AUTOMATIC SPRINKLER SYSTEMS
- Section 8-411 — OTHER TECHNOLOGIES
- Section 8-412 — HIGH-RISE BUILDINGS
- Chapter 8-5 — MEANS OF EGRESS
- Chapter 8-6 — ACCESSIBILITY
- Chapter 8-7 — STRUCTURAL REGULATIONS
- Chapter 8-8 — ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
- Chapter 8-9 — MECHANICAL, PLUMBING AND ELECTRICAL REQUIREMENTS
- Chapter 8-10 — QUALIFIED HISTORICAL DISTRICTS, SITES AND OPEN …