Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
Section 5.504 — POLLUTANT CONTROL
2025 California Green Building Standards Code (Title 24, Part 11) · 2025 edition · ingested 2026-07-07 · California
Full text via GoCodebook AI
We have the complete 2025 text of this code. Ask a question and get the exact controlling section with a citation.
5.504.1 Temporary ventilation. The permanent HVAC system shall only be used during construction if necessary to condition the building or areas of addition or alteration within the required temperature range for material and equipment installation. If the HVAC system is used during construction, use return air filters with a Minimum Efficiency Reporting Value (MERV) of 13, based on ASHRAE 52.2. Replace all filters immediately prior to occupancy, or, if the building is occupied during alteration, at the conclusion of construction. 5.504.2 Reserved. 5.504.3 Covering of duct openings and…