Chapter 3 — NONRESIDENTIAL, HOTEL/MOTEL OCCUPANCIES, AND COVERED PROCESSES—MANDATORY REQUIREMENTS
Section 120.3 — REQUIREMENTS FOR PIPE INSULATION
2025 California Energy Code (Title 24, Part 6) · 2025 edition · updated 2026-07-25 · California
Nonresidential and hotel/motel buildings shall comply with the applicable requirements of Sections 120.3(a) through 120.3(c).
(a) General requirements. The piping conditions listed below for space-conditioning, service water-heating, and process heating and process cooling systems piping with fluid normal operating temperatures listed in Table 120.3-A-1 or Table 120.3-A2, and the fluid distribution system, shall have at least the amount of insulation specified in Subsection (c):
- Space cooling systems. All refrigerant suction, chilled water, and brine fluid distribution systems.
- Space heating systems. All refrigerant suction, steam, steam condensate and hot water fluid distribution systems.
- Service water-heating systems. A. Recirculating system piping, including the supply and return piping to the water heater. B. The first 8 feet of hot and cold outlet piping, including piping between a storage tank and a heat trap, for a nonrecirculating storage system.
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
NONRESIDENTIAL, HOTEL/MOTEL OCCUPANCIES, AND COVERED PROCESSES—MANDATORY REQUIREMENTS
C. Pipes that are externally heated. 4. Process heating system piping. All refrigerant, steam, steam condensate and hot water fluid distribution systems for heating a process unrelated to space conditioning or service water heating. 5. Process cooling system piping. All refrigerant suction, chilled water, and brine fluid distribution systems for cooling a process unrelated to space conditioning.
Insulation conductivity shall be determined in accordance with ASTM C335 at the mean temperature listed in Table 120.3-A1 or Table 120.3-A2, and shall be rounded to the nearest [1] / 100 Btu-inch per hour per square foot per °F. Fluid distribution systems include all elements that are in series with the fluid flow, such as pipes, fittings, pumps, valves, strainers, coil u-bends, and air separators, but not including elements that are not in series with the fluid flow, such as expansion tanks, fill lines, chemical feeders, and drains.
Exception to Section 120.3(a)2: Heat pump refrigerant vapor line shall be installed with a minimum of 0.5-inch-thick or R-3.0 insulation for nonresidential buildings and 0.75-inch-thick or R-6.0 insulation for residential buildings. No insulation is required on the refrigerant liquid line.
(b) Insulation protection. Pipe insulation shall be protected from damage due to sunlight, moisture, equipment maintenance and wind. Protection shall, at minimum, include the following:
- Pipe insulation exposed to weather shall be protected by a cover suitable for outdoor service. The cover shall be water retardant and provides shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be used to provide this protection.
- Pipe insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space shall include, or be protected by, a Class I or Class II vapor retarder. All penetrations and joints shall be sealed.
- Pipe insulation buried below grade must be installed in a water proof and noncrushable casing or sleeve.
(c) Insulation thickness.
- For insulation with a conductivity in the range shown in Table 120.3-A-1 or Table 120.3-A-2 for the applicable fluid temperature range, the insulation shall have the applicable minimum thickness or R -value shown in Table 120.3-A1 or Table 120.3-A-2.
- For insulation with a conductivity outside the range shown in Table 120.3-A-1 or Table 120.3-A-2 for the applicable fluid temperature range, the insulation shall have a minimum R -value shown in Table 120.3-A-1 or Table 120.3-A-2 or thickness as calculated:
MINIMUM INSULATION THICKNESS EQUATION
K
[-] k [-]
T = PR 1 + ------ PRt – 1
where:
T = minimum insulation thickness for material with conductivity K, inches.
PR = pipe actual outside radius, inches.
t = insulation thickness from Table 120.3-A 1 or Table 120.3-A2, inches.
K = conductivity of alternate material at the mean rating temperature indicated in Table 120.3-A for the applicable fluid temperature range, in Btu-inch per hour per square foot per °F.
k = The lower value of the conductivity range listed in Table 120.3-A for the applicable fluid temperature range, Btu-inch per hour per square foot per °F.
Exception 1 to Section 120.3: Factory-installed piping within space-conditioning equipment certified under Section 110.1 or 110.2.
Exception 2 to Section 120.3: Piping that conveys fluids with a design operating temperature range between 60°F and 105°F.
Exception 3 to Section 120.3: Where the heat gain or heat loss to or from piping without insulation will not increase building
source energy use.
Exception 4 to Section 120.3: Piping that penetrates framing members shall not be required to have pipe insulation for the distance of the framing penetration. Metal piping that penetrates metal framing shall use grommets, plugs, wrapping or other insulating material to assure that no contact is made with the metal framing.
Exception 5 to Section 120.3: Fluid pumps, steam traps, blow-off valves, and piping within process equipment.
Exception 6 to Section 120.3: Valves, strainers, coil u-bends, air separators with at least 0.5 inches of insulation, and piping within process equipment.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code.
76 2025 CALIFORNIA ENERGY CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
NONRESIDENTIAL, HOTEL/MOTEL OCCUPANCIES, AND COVERED PROCESSES—MANDATORY REQUIREMENTS
TABLE 120.3-A-1—SPACE HEATING AND SERVICE WATER HEATING SYSTEMS (STEAM, STEAM CONDENSATE,
REFRIGERANT, SPACE HEATING, SERVICE HOT WATER) AND PROCESS HEATING SYSTEM PIPE INSULATION THICKNESS
| FLUID OPERATING TEMPERATURE RANGE (°F) |
INSULATION CONDUCTIVITY (Btu·in/h·ft2· °F) |
INSULATION MEAN RATING TEMPERATURE (°F) |
NOMINAL PIPE DIAMETER < 1 INCH |
NOMINAL PIPE DIAMETER 1 TO < 1.5 INCHES |
NOMINAL PIPE DIAMETER 1.5 TO < 4 INCHES |
NOMINAL PIPE DIAMETER 4 TO < 8 INCHES |
NOMINAL PIPE DIAMETER 8 INCHES AND LARGER |
|---|---|---|---|---|---|---|---|
| Above 350 | 0.32–0.34 | 250 | 4.5 inches | 5.0 inches | 5.0 inches | 5.0 inches | 5.0 inches |
| Above 350 | 0.32–0.34 | 250 | R-37 | R-41 | R-37 | R -27 | R-23 |
| 251–350 | 0.29–0.32 | 200 | 3.0 inches | 4.0 inches | 4.5 inches | 4.5 inches | 4.5 inches |
| 251–350 | 0.29–0.32 | 200 | R-24 | R-34 | R-35 | R-26 | R-22 |
| 201–250 | 0.27–0.30 | 150 | 2.5 inches | 2.5 inches | 2.5 inches | 3.0 inches | 3.0 inches |
| 201–250 | 0.27–0.30 | 150 | R -21 | R-20 | R-17.5 | R-17 | R-14.5 |
| 141–200 | 0.25–0.29 | 125 | 1.5 inches | 1.5 inches | 2.0 inches | 2.0 inches | 2.0 inches |
| 141–200 | 0.25–0.29 | 125 | R-11.5 | R-11 | R-14 | R-11 | R-10 |
| 105–140 | 0.22–0.28 | 100 | 1.0 inch | 1.5 inches | 1.5 inches | 1.5 inches | 1.5 inches |
| 105–140 | 0.22–0.28 | 100 | R 7.7 | R 12.5 | R-11 | R-9 | R-8 |
Footnote to Table 120.3-A-1 and Table 120.3-A-2: These thicknesses are based on energy efficiency considerations only. Issues such as water vapor permeability or surface condensation sometimes require vapor retarders or additional insulation.
TABLE 120.3-A-2—SPACE COOLING SYSTEMS (CHILLED WATER, REFRIGERANT AND BRINE)
AND PROCESS COOLING SYSTEM PIPE INSULATION THICKNESS
| FLUID OPERATING TEMPERATURE RANGE (°F) |
INSULATION CONDUCTIVITY (Btu·in/h·ft2· °F) |
INSULATION MEAN RATING TEMPERATURE (°F) |
NOMINAL PIPE DIAMETER < 1 INCH |
NOMINAL PIPE DIAMETER 1 TO < 1.5 INCHES |
NOMINAL PIPE DIAMETER 1.5 TO < 4 INCHES |
NOMINAL PIPE DIAMETER 4 TO < 8 INCHES |
NOMINAL PIPE DIAMETER 8 INCHES AND LARGER |
|---|---|---|---|---|---|---|---|
| Residential 40–60 |
0.21–0.27 | 75 | 0.75 inch | 0.75 inch | 1.0 inch | 1.0 inch | 1.0 inch |
| Residential 40–60 |
0.21–0.27 | 75 | R-6 | R-5 | R-7 | R-6 | R-5 |
| Nonresidential 40–60 |
0.21–0.27 | 75 | 0.5 inch | 0.5 inch | 1.0 inch | 1.0 inch | 1.0 inch |
| Nonresidential 40–60 |
0.21–0.27 | 75 | R-3 | R-3 | R-7 | R-6 | R-5 |
| Below 40 | 0.20–0.26 | 50 | 1.0 inch | 1.5 inches | 1.5 inches | 1.5 inches | 1.5 inches |
| Below 40 | 0.20–0.26 | 50 | R 8.5 | R 14 | R 12 | R 10 | R 9 |
Footnote to Table 120.3-A-1 and Table 120.3-A-2: These thicknesses are based on energy efficiency considerations only. Issues such as water vapor permeability or surface condensation sometimes require vapor retarders or additional insulation.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Energy Code (Title 24, Part 6)
- Chapter 1 — ALL OCCUPANCIES—GENERAL PROVISIONS
- Chapter 2 — ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MAN…
-
▸ Chapter 3 — NONRESIDENTIAL, HOTEL/MOTEL OCCUPANCIES, AND COVER…
Overview- Section 120.0 — GENERAL
- Section 120.1 — REQUIREMENTS FOR VENTILATION AND INDOOR AIR QU…
- Section 120.2 — REQUIRED CONTROLS FOR SPACE-CONDITIONING SYSTEMS
- Section 120.3 — REQUIREMENTS FOR PIPE INSULATION
- Section 120.4 — REQUIREMENTS FOR AIR DISTRIBUTION SYSTEM DUCTS…
- Section 120.5 — REQUIRED NONRESIDENTIAL MECHANICAL SYSTEM ACCE…
- Section 120.6 — MANDATORY REQUIREMENTS FOR COVERED PROCESSES
- Section 120.7 — MANDATORY REQUIREMENTS FOR BUILDING ENVELOPES
- Section 120.8 — NONRESIDENTIAL BUILDING COMMISSIONING
- Section 120.9 — MANDATORY REQUIREMENTS FOR COMMERCIAL BOILERS
- Section 120.10 — MANDATORY REQUIREMENTS FOR FANS
- Chapter 4 — NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—MANDATO…
- Chapter 5 — NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—PERFORM…
- Chapter 6 — NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—
- Chapter 7 — SINGLE-FAMILY RESIDENTIAL BUILDINGS—
- Chapter 8 — SINGLE-FAMILY RESIDENTIAL BUILDINGS—PERFORMANCE AN…
- Chapter 9 — SINGLE-FAMILY RESIDENTIAL BUILDINGS—ADDITIONS AND …
- Chapter 10 — MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
- Chapter 11 — MULTIFAMILY BUILDINGS—PERFORMANCE AND PRESCRIPTIV…
- Chapter 12 — MULTIFAMILY BUILDINGS—ADDITIONS, ALTERATIONS AND …