Title 17 — FIRE

Chapter 17.04 — INTERNATIONAL FIRE CODE

Burlingame Municipal Code · 2026-09 edition · updated 2026-10-02 · Burlingame

Note: Ord. 2042, 11/3/2025 repealed Ords. 1208, 1285, 1315, 1413, 1463, 1536, 1614, 1695, 1749, 1793, 1800, 1808, 1814, 1855, Ord. 1888, Ord. 1932, Ord. 1974, and Ord. 2009.

§ 17.04.010. Adoption of text of the California Fire Code, International Fire Code, and

Public Resources Code, Division 4, Section 4291.

There is adopted by the city for the purpose of prescribing regulations governing conditions hazardous to life and property from fire, explosion, or wildfire that certain codes which contains building standards known as the 2025 California Fire Code (International Fire Code, 2024 Edition, as amended by the State of California), and the non-building standards known as the International Fire Code, 2024 Edition, together with all appendices, except Appendices A, D, J, and P, and the State of California amendments thereto, and the Public Resources Code, Division 4, Section 4291. (Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.020. Amendments to the California Fire Code and International Fire Code.

The California Fire Code and the International Fire Code are amended or modified as follows. (Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.025. Chapter 1, Division II, Section 102.2, IFC amended — Administrative,

operational and maintenance provisions.

Section 102.2 is amended to delete item #2 of this section. (Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.030. Chapter 1, Division II, Section 105.3.3, IFC amended — Occupancy

prohibited before approval and Examination of Documents.

Section 105.3.3 is deleted in its entirety and replaced with the following:

Section 105.3.3. No final inspection by the Building Official as to all or any portion of a development shall be deemed complete, and no certificate of occupancy or temporary certificate of occupancy shall be issued unless and until the installation of the prescribed fire protection facilities and access ways have been completed and approved by the Fire Chief. (Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.031. Chapter 1, Section 106.2, CFC amended — Examination of documents.

Section 106.2, CFC is deleted in its entirety and replaced with the following:

Section 106.2. Examination of documents. When required by the fire code official, plans submitted to the Building Official for a permit shall be reviewed by the Fire Chief to determine compliance with the California Fire Code and the International Fire Code. Upon review a written report shall be returned to the Building Official listing deficiencies or compliance with the Code. (Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.035. Chapter 1, Sections 108.1 and 108.2, CFC amended — Permits and fees.

Section 108.1.2, CFC is added to this code and shall read as follows:

Section 108.1.2. Permits and Fees.

a. The fees for the permits and other services shall be as established by resolution of the
Central County Fire Department Fire Board as amended from time to time. The fee shall
be set to cover the cost of the Fire Department to review and inspect the intended activities,
operations or functions. The fees must be applied to the appropriate agency, City of
Burlingame or Central County Fire Department, depending on the type of service.

Exception: (1) The applicant for a given permit shall be exempt from the payment when
the work to be conducted is for the City of Burlingame under written contract to the City
or for events sponsored or co-sponsored by the City.

b. In the case of multiple permits for an applicant, the permit applicant will be charged the
single highest listed rate of all the permits required. The other permittable items will be
charged at a rate of 50% of the listed fee as long as the permits are for the same address.

c. Where processes or materials are inherent with a permittable item, subsequent fees may be
waived at the discretion of fire chief.

d. All fire permits and fire construction permits shall have a set number of inspections per
permit as set forth by the Central County Fire Department Fee Schedule. Additional
inspections and additional re-inspections will be billed at an hourly rate consistent with the
Central County Fire Department Fee Schedule.

e. Application for "event" type fire code permits shall be submitted 14 days prior to the event
date. Applications submitted within 13 days prior to the event date shall be charged double
the regular permit rate as established by the Central County Fire Department Fee Schedule.

f. "After Hours" inspections shall be invoiced at a rate of one and one-half time the normal
hourly rate of the inspecting fire personnel. "After Hours" inspections will be billed at a
rate of three hours minimum. "After Hours" inspections are defined as follows: Inspections
conducted outside of normal business hours, as defined on the Central County Fire
Department website and based upon personnel availability.

g. Any person, group, organization, institution or business failing to pay the applicable fees
under this Article shall after 30 days of the due date, for either existing or new permit
applicants, shall be issued a citation for non-payment of the required permit fee. The
penalty for all permit payments delinquent after 30 days shall be a doubling of the original
fee.
(Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.036. Section 108.4, CFC amended — Investigation and fees.

Section 108.4 CFC is deleted in its entirety and replaced with the following:

Section 108.4. Investigation and Fees.

Section 108.4. Investigation — Work without a permit.

Investigation. Whenever construction or work for which a permit is required by this code and has been commenced without first obtaining a permit, a special investigation shall be made before a permit may be issued for the work. All work done without a required permit, including demolition of all or part of a structure or system shall be subject to the investigation and fees imposed by this section.

Section 108.4.1. is added to this code and shall read as follows:

Section 108.4.1. Fee — Work without a permit.

In the event work is done without an issued permit, an investigation fee, in addition to the permit fee, shall be collected as a civil penalty, whether or not a permit is then or subsequently issued.

The investigation fee shall be up to 10 times the fire permit fee. The investigation fee shall be determined by the Fire Chief and shall be based on the staff time reasonably required to resolve all of the issues related to the work that has been performed without a permit. No construction work permit shall be issued until the investigation fee has been paid in full.

Nothing in this section shall relieve any persons from fully complying with the requirements of this code, in the execution of the work, or from any other fees or penalties prescribed by law. (Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.040. Chapter 1, Section 112, CFC amended — Board of appeals.

Section 112, CFC is deleted in its entirety and replaced with the following:

Section 112. Appeal and review.

(a) The chief of the fire department shall be charged with the duty and responsibility of administering the provisions of this chapter.

(b) Whenever it is provided herein that certain actions shall be done in accordance with an order of the fire department, such order shall be complied with. Any person aggrieved thereby, may appeal to the fire chief in writing within ten (10) days after the date of such order, except as otherwise provided in this chapter. The fire chief shall issue a written decision to affirm, modify or reverse the order within two (2) business days of the receipt of the appeal. The fire chief's written decision may be appealed to the City Council no later than ten (10) days from the date of the fire chief's written decision. The City Council's decision shall be final and conclusive. Except in the cases of immediate hazard, the enforcement of the order shall be suspended until such person has exhausted the appeal process as described above. (Ord. 2042, 11/3/2025)

§ 17.04.045. (Reserved)

Exceptions & meaning →

§ 17.04.050. Section 315, CFC amended — General storage.

Section 315.2, CFC is amended and Section 315.3.5 is added to read as follows:

Section 315.2 Permit required. A permit for miscellaneous combustible materials shall be required as set forth in Section 105.5.

Exception: Storage of combustible materials other than motorized vehicles or vessels shall not be permitted in a public parking garage or in a garage or carport serving a Group R, Division 1 or Group R, Division 2 Occupancy, unless the method of storage is approved by the Fire Code

Official.

Section 315.3.5, CFC is added to read as follows:

Section 315.3.5. Designation of storage heights. Where required by the fire code official, a visual method of indicating the maximum allowable storage height shall be provided in accordance with Section 315.3.5.1, CFC.

Section 315.3.5.1, CFC added to read as follows:

Section 315.3.5.1. The approved visual method of indicating maximum allowable storage shall be a four (4") inch wide line in contrasting color along a wall or storage rack. (Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.055. Section 503.3, IFC amended — Marking.

Section 503.3, IFC is amended by adding section 503.3.1 to read as follows:

Section 503.3.1 Fire Lane Designation. Designation of fire lanes shall be by one of the
following means:

1. By outlining and hash marking the area in contrasting colors clearly marking it with the
words "Fire Lane - No Parking."

2. By identifying the space with a red curb upon which the words "Fire Lane - No Parking"
are stenciled every 15 feet.

a. Both sides of fire lanes shall be red curbed when the fire lane is twenty (20) to twenty-
eight (28) feet in width.

b. At least one side of a fire lane shall be red curbed and stenciled when the fire lane is
over twenty-eight (28) and up to thirty-six (36) feet in width.

c. Curbs need not be painted red nor stenciled when the fire lane is more than thirty-six
(36) feet in width.

3. In areas where a red curb is not practical, and when approved by the fire official, white
signs measuring 12 inches by 18 inches with red lettering not less than 1" in height stating
the area is a fire lane and parking is prohibited, may be posted adjacent to the fire lanes.
(Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.060. Sections 505.1 through 505.1.3, CFC amended — Premises identification.

Section 505.1.1 is added to read as follows:

Section 505.1.1 Size of numbers.

1. When the structure is thirty-six (36) to fifty (50) feet from the street or fire apparatus
access, a minimum of one-half-inch (1/2") stroke by six inches (6") high is required.
2. When the structure is more than fifty (50) feet from the street or fire apparatus access, a
minimum of one-inch (1") stroke by nine inches (9") high is required.

Sections 505.1.2, 505.1.3, and 505.1.4 CFC are added to read as follows:

Section 505.1.2 Multi-Tenant Buildings. Numbers or letters shall be designated on all
occupancies within a building. Size shall be a minimum of one-half inch (1/2") stroke by four
inches (4") high and on a contrasting background. Directional address numbers or letters shall be
provided. Said addresses or numbers shall be posted at a height no greater than 5 feet, 6 inches
(5' 6") above the finished floor and shall be either internally or externally illuminated in all new
construction.

Section 505.1.3 Rear Addressing. When required by the chief, approved numbers or addresses
shall be placed on all new and existing buildings in such a position as to be plainly visible and
legible from the fire apparatus road at the back of a property or where rear parking lots or alleys
provide and acceptable vehicular access. Number stroke and size shall comply with Section
505.1.1.

Section 505.1.4 ADU Addressing. Address for Residential Accessory Dwelling Units shall
meet City of Burlingame specifications.
(Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.065. Sections 506.1, CFC amended — Key boxes.

Section 506.1, CFC is amended and 506.1.1.1, CFC is added to read as follows:

Section 506.1 is modified to include:

Section 506.1 Where Required. The key box shall be of an approved type and shall contain contents as established in Section 506.1.1.1. A key box shall be installed in accordance with Fire Department standards for all new buildings. For existing buildings equipped with key box, it shall be upgraded to current Fire Department standards at time of Building permit issuance including modifications or alterations to front entrance of building.

An emergency gate key switch shall be installed on all new electronic driveway or entryway gates. The key switch shall conform to current Fire Department standards.

Section 506.1.1.1, CFC is added to read as follows:

Section 506.1.1.1 Key Box Contents Requirements. Required keys include but are not limited to: a master entry key, elevator control, fire alarm control panels, fire sprinkler control valve access, and building utilities. Based on specific site conditions, the fire department may notify the property owner of additional required keys. Contents inside key box shall follow approved fire department standards. If the business/operation is required to have a Hazardous Material Inventory Statement (HMIS), the HMIS shall be included in the key box. Electronic key cards or keyless remotes may be provided as long as the locking system has a failsafe feature at loss of building power and doors are operational without a key or special knowledge. (Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.070. Section 507 CFC, amended — Fire protection water supplies.

Section 507.5.4.1 CFC is added to read as follows:

Section 507.5.4.1. Private Hydrants. Whenever any on-site fire protection equipment or access ways have been installed as provided in this section, the following provision shall apply:

With respect to hydrants located along private access ways where curbs exist, said curbs shall be painted red or otherwise appropriately marked by the owner, lessee or other person in charge of the premises, to prohibit parking for a distance of 10 feet in either direction from such hydrant.

In such cases where curbs do not exist, there shall be appropriate markings painted on the pavement, or signs erected, or both giving notice that parking is prohibited for a distance of 10 feet from any such hydrant. Hydrant caps shall be color-coded in accordance with NFPA 291 (National Fire Protection Association). The base of the hydrant shall be painted either reflective red or yellow. (Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.075. Section 508, CFC amended — Fire command center.

Section 508.1.1.1 CFC is added to read as follows:

Section 508.1.1.1. Requirements. Fire command center shall be equipped with an exterior door
and be located at the exterior of the building at a location approved by the Fire Chief.

Section 508.2 CFC is added to read as follows:

Section 508.2 Fire Control Room. An approved fire control room shall be provided for all
new buildings or buildings undergoing substantial improvement and requiring protection by an
automatic fire sprinkler system. The room shall only contain all main system control valves, fire
alarm control panels ERRCS equipment, and other fire equipment required by the Fire Chief.
Fire control rooms shall be located within the building at a location approved by the Fire Chief
and shall be provided at grade with a means to access the room directly from the exterior.
Durable signage shall be provided on the exterior side of the access door to identify the fire
control room. Fire Control Rooms shall not be less than 35 square feet.

Exceptions:

1. Group R, Division 3 Occupancies.

2. Occupancies with a fire pump shall have a fire control room that is a minimum of 200
square feet.

3. In high-rise buildings, the fire control room shall not be less than 200 square feet.
(Ord. 2042, 11/3/2025)

§ 17.04.080. (Reserved)

§ 17.04.085. (Reserved)

Exceptions & meaning →

§ 17.04.090. Section 903.1.2, CFC added — Additions and alterations.

Section 903.1.2, CFC is added to read as follows:

Section 903.1.2 Additions and Alterations. The standard for calculating the size of addition
and/or alteration for determining the threshold for fire sprinkler systems shall be:

1. The square footage of every room being added and/or altered shall be included in the
calculation of total square footage of addition and/or alteration.

2. The entire square footage shall be considered added or altered when at least fifty percent
(50%) or greater of interior wall sheeting or ceiling of any one wall within a room or area
is new, removed, or replaced.

(Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.091. Section 903.1.3, CFC added — Provisions for all sprinklered buildings.

Section 903.1.3, CFC is added to read as follows:

Section 903.1.3, Provisions for All Sprinklered Buildings.

  1. When a commercial or multi-family building is partially retrofitted with an approved automatic sprinkler fire extinguishing system pursuant to this section, the building owner shall complete the fire extinguishing system retrofit throughout the unprotected building interior areas within six (6) years of completing the initial partial retrofit or within every tenant space where a building permit is obtained, whichever is less.

  2. When a residential building is partially retrofitted with an approved automatic sprinkler fire extinguishing system pursuant to this section, the building fire extinguishing system retrofit shall be completed throughout the unprotected building interior areas within two (2) years from completing the initial partial retrofit.

  3. When a property owner or responsible party of a commercial or residential building chooses option 1 or 2 from above, the property owner shall file a deed restriction with San Mateo County Assessor's Office and obtain a performance bond to ensure compliance with Section 17.04.091. The bond shall be in an amount equal to or greater than the estimated cost of completion, as determined by Central County Fire Department. (Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.092. Section 903.2, CFC amended — Where required.

Section 903.2, CFC shall be deleted and replaced as follows:

Section 903.2 Where required. Approved automatic fire sprinkler systems shall be installed in
all new occupiable and/or habitable buildings and structures. In addition, approved automatic fire
sprinkler systems shall be provided in locations described in Sections 903.2.1 through 903.2.23.

Exceptions:

1. When approved by the fire chief, canopy structures used solely for vehicular parking
which have a photovoltaic system attached are not required to be equipped with a fire
sprinkler system as long as the structure meets distance requirements to other structures
and property lines.
2. Group U occupancies less than 1,200 square feet.

Section 903.2.10.3, CFC is added to read as follows:

Section 903.2.10.3 Lithium-Ion Batteries in Vehicles. Areas which contain electric vehicle
charging stations shall have a fire sprinkler density design of a minimum Extra Hazard, Group 2
for the coverage of charging stations and for 15' in any direction of charging stations.

Section 903.2.10.4, CFC is added to read as follows:

Section 903.2.10.4 Additional Commercial and Multi-family Dwelling Sprinkler Locations.
Rooms or spaces which contain vehicle parking lifts or vehicle stacking systems shall be designed as an Extra-High Hazard Classification. Sprinkler design to include sidewall sprinkler
heads designed at minimum Ordinary Group 2 in between each level.

Exception: Buildings classified as single-family dwellings.
(Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.093. Sections 903.2.22 and 903.2.23 CFC added — Existing buildings and

structures.

Section 903.2.22 is added to read as follows:

Section 903.2.22, CFC Existing Buildings and Structures. All existing buildings and
structures shall be retroactively protected by an approved automatic extinguishing system when
the following conditions exist:

a. Commercial and multi-family residential buildings with a total building floor area in excess
of 2,000 square feet or more than two stories in height, and when additions or alterations
for which a building permit is required will exceed 1,200 square feet in area.

Exception: Group U occupancies less than 1,200 square feet and separated from primary
structure by a minimum of ten (10) feet.

b. Residential one- and two-family dwellings and structures with a total building floor area in
excess of 2,000 square feet or more than two stories in height, and when additions or
alterations for which a building permit is required will exceed 750 square feet in area.

Exceptions:

1. Additions or alterations of commercial, multi-family residential, and one and two-
family residential buildings that do not exceed 20% of the total square footage of the
entire completed building.

2. The following scopes of work are excluded from calculations to determine area of
alteration: building roof repair/replacement; fire damage repair; building heating and/
or cooling unit repair/replacement; and any other federal, state and local construction
code upgrade requirements including but not limited to the seismic retrofit
requirements, asbestos, and other hazardous material abatement.

Section 903.2.23, CFC is added with the following:
Section 903.2.23 Aggregate. When more than one (1) addition and/or alteration for which
building permits are required are submitted within a two (2) year period from the closure date
of the initial permit, the sum of the square footage of these additions and/or alterations shall be
aggregated for the purpose of determining calculations in Section 17.04.090.

(Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.094. Section 903.3.1.4, CFC amended — Inspector's test.

Section 903.3.1.4, CFC is added to read as follows:

Section 903.3.1.4 Inspectors Test Valves. Single-family residential fire sprinkler systems within buildings greater than 3,600 square feet shall be equipped with an inspector's test valve for each system and located the furthest point away from the sprinkler riser. (Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.095. Section 903.3.1.5, CFC added — Additional sprinkler locations.

Section 903.3.1.5, CFC is added to read as follows:

Section 903.3.1.5 Additional Residential Sprinkler Locations. The installation of a residential
fire sprinkler system shall conform to the following:

1. Sprinklers shall be required throughout carports and garages.

Exception: Detached carports and garages less than 2,000 square feet in area and separated
from residential buildings by a minimum of 10 feet.

2. Sprinkler coverage shall be provided in the following locations:

a. Attic access openings.

b. Areas of attics and crawl spaces containing storage, mechanical and/or electrical
equipment.
(Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.096. Section 903.4.4 CFC added — Fire sprinkler monitoring systems.

Section 904.4.4 CFC is amended by adding the following:

Section 904.4.4 Monitoring. For new fire sprinkler monitoring systems, the approved supervisory station shall be defined as a UL approved central receiving station. (Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.097. Section 905.4 CFC amended — Location of Class I standpipe hose

connections.

Section 905.4 CFC, subsection 1 is deleted and replaced with the following:

1. In every required interior exit stairway, a hose connection shall be provided for each story
above and below grade plane. Hose connections shall be located at an intermediate floor
level landing between floors, when such a landing exists. See section 909.20.2.3 of the
California Building Code for additional provisions in smoke-proof enclosures.
(Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.098. Section 907.7 CFC amended — Acceptance tests and certification.

Section 907.7 CFC is amended to add the following:

Section 907.7 Acceptance Test and Certification. Upon completion of the installation, the fire alarm system and all fire alarm components shall be tested in accordance with NFPA 72. New fire alarm systems installed in commercial and multi-family buildings shall be UL-Certified. Certificate shall be posted next to fire alarm control panel at time of final inspection. (Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.099. Section 3307.5.3 CFC amended — Standpipe supply.

Section 3307.5.3, CFC is added to read as follows:

Section 3307.5.3 Operational Standpipes. Where a standpipe is required in accordance with Section 3307.5, that standpipe is required to remain wet and operational. (Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.100. Section 5003.5, CFC amended — Hazard identification signs.

Section 5003.5.2, CFC is added to read as follows:

Section 5003.5.2 Sign Size and Locations. Two NFPA 704 diamonds shall be placed on
buildings so that they are clearly visible from at least two directions of travel.

1. The signs shall be at least fifteen inches by fifteen inches (15" x 15"). The signs shall not
be placed on windows.

2. When NFPA 704 diamonds are required for the interior doors, the signs shall be applied to
the doors at a level no higher than the doorknob. The signs for the interior doors shall be at
least six inches by six inches (6" x 6").

3. The Fire Code Official may require fewer or more NFPA diamonds if the building
configuration or size makes it reasonably necessary.
(Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.101. Section 5707, CFC amended — On-demand mobile fueling operations.

Section 5707.6.5 is deleted in its entirety and replaced with the following:

Section 5707.6.5 Adequate Lighting. Adequate site lighting shall be provided for all mobile fueling operations which are performed in dim or dark outdoor conditions. Acceptable means of lighting are flood or box lights which are self-standing or mountable. (Ord. 2042, 11/3/2025)

Exceptions & meaning →

§ 17.04.105. Deposits of hazardous materials and unlawful burning — Liability for costs.

(a) The fire department is authorized to clean up or abate the effects of any hazardous material deposited upon or into property or facilities of the City. Any person who intentionally or negligently caused such deposit shall be liable for the payment of all cleanup or abatement costs incurred by the fire department. The remedy provided by this section shall be in addition to any other remedies provided by law.

(b) For the purposes of this section, "hazardous materials" shall be defined as any substances or materials, in a quantity or form which, in the determination of the fire chief or his authorized representative, poses an imminent risk to life, health or safety of persons or property or to the ecological balance of the environment, and shall include, but not be limited to, such substances as explosives, radioactive materials, petroleum or petroleum products or gases; poisons, etiologic (biologic) agents, flammables and corrosives.

(c) Any person in violation of Sections 17.04.010 and 17.04.020 which results in fire damage to persons or property shall be charged as unlawfully burning and is liable for costs incurred by the fire department and other responding county or state fire agencies for suppression activities.

(d) For purposes of this section, costs incurred by the fire department shall include, but shall not necessarily be limited to, the following: actual labor costs of city personnel, including workers' compensation benefits, fringe benefits, administrative overhead; cost of equipment operation, cost of materials obtained directly by the city; and cost of any contract labor and materials. (Ord. 2042, 11/3/2025)

Exceptions & meaning →