9-1-11: ADOPTION OF 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE:¶
Part 11 of Title 24 of the California Code of Regulations, also known as the “California Green Building Standards Code,” which is part of the California Building Standards Code, 2025 Edition, as adopted by the California Building Standards Commission, is hereby adopted and made a part of this Code, with certain amendments, additions, and deletions as stated in this Article. [Added by Ord. No. 25-4,034, eff. 1/1/26.]
9-1-11-4.509: COOL ROOF FOR REDUCTION OF HEAT ISLAND EFFECT:
The following section is added to Chapter 4, Part 11 of the CBC to read as follows:
9-1-11-4.509: Cool roof for reduction of heat island effect.
Roofing materials shall comply with the solar reflectance and thermal emittance requirements of this section.
Exceptions:
Roof repair
Installation of building-integrated photovoltaics
Roof construction that has a thermal mass over the roof membrane, including areas of vegetated (green) roofs, weighing at least 25 pounds per square foot
A. Solar Reflectance
Roofing materials shall have a minimum 3-year aged solar reflectance equal to or greater than the values specified in Table 4.509(1) and Table 4.509(2)
B. Thermal Emittance
Roofing materials shall have a Cool Roof Rating Council initial or aged thermal emittance equal to or greater than the values specified in Table 4.509(1) and Table 4.509(2)
C. Solar Reflective Index Alternative
Roofing materials having a Solar Reflectance Index (SRI) equal to or greater than the values specified in Table 4.509(1) and Table 4.509(2) may be used as an alternative to compliance with the 3-year aged solar reflectance and thermal emittance values.
Table 4.509(1) – LOW-RISE RESIDENTIAL
MIN 3-YEAR AGED
THERMAL ROOF SLOPE SOLAR SRI
EMITTANCE REFLECTANCE
≤ 2:12 0.65 0.85 78
> 2:12 0.23 0.85 20
Table 4.509(2) – HIGH-RISE RESIDENTIAL, HOTELS, AND MOTELS
MIN 3-YEAR AGED
THERMAL ROOF SLOPE SOLAR SRI
EMITTANCE REFLECTANCE
≤ 2:12 0.65 0.75 78
> 2:12 0.23 0.75 20
[Added by Ord. No. 25-4,034, eff. 1/1/26.]
9-1-11-5.509: COOL ROOF FOR REDUCTION OF HEAT ISLAND EFFECT:
The following section is added to Chapter 5, Part 11 of the CBC to read as follows:
9-1-11-5.509: Cool roof for reduction of heat island effect.
Roofing materials shall comply with the solar reflectance and thermal emittance requirements of this section.
Exceptions:
Roof repair
Installation of building-integrated photovoltaics
Roof construction that has a thermal mass over the roof membrane, including areas of vegetated (green) roofs, weighing at least 25 pounds per square foot
A. Solar Reflectance
Roofing materials shall have a minimum 3-year aged solar reflectance equal to or greater than the values specified in Table 5.509
B. Thermal Emittance
Roofing materials shall have a Cool Roof Rating Council initial or aged thermal emittance equal to or greater than the values specified in Table 5.509
C. Solar Reflective Index Alternative
Roofing materials having a Solar Reflectance Index (SRI) equal to or greater than the values specified in Table 5.509 may be used as an alternative to compliance with the 3-year aged solar reflectance and thermal emittance values.
Table 5.509 – NON-RESIDENTIAL
MIN 3-YEAR AGED THERMAL
ROOF SLOPE SOLAR SRI EMITTANCE REFLECTANCE
≤ 2:12 0.68 0.85 82
2:12 0.28 0.85 27
[Added by Ord. No. 25-4,034, eff. 1/1/26.]