Skip to content

Earlier editions: 2026-09

Title 19 — BUILDINGS AND CONSTRUCTION›Chapter 19.48 — BERKELEY FIRE CODE

Berkeley Municipal Code Art. 12 Fire Flow Requirements for Buildings

Berkeley Municipal Code · 2026-10 edition · updated 2026-10-05 · Berkeley

Cite as: Berkeley Municipal Code Article 12 · Text as of 2026-10-05

19.48.130 Amendments to Appendix B Fire Flow Requirements for Buildings.

Appendix B of the California Fire Code is partially adopted with adopted sections below. (Sections adopted by the State Fire Marshal remain unless modified below.)

APPENDIX B – FIRE FLOW REQUIREMENTS FOR BUILDINGS

Section B105.2 (Appendix B), Table B105.2, “Required Fire-Flow for Buildings Other Than One- And Two-Family Dwellings, Group R-3 And R-4 Buildings And Townhouses”

TABLE B105.2 - REQUIRED FIRE·FLOW FOR BUILDINGS OTHER THAN ONE- & TWO-FAMILY DWELLINGS, GROUP R·3 & R·4 BUILDINGS AND TOWNHOUSES

AUTOMATIC SPRINKLER SYSTEM (Design Standard) MINIMUM FIRE-FLOW (gallons per minute) FLOW DURATION (hours)
No automatic sprinkler system Value in Table B105.1(2) Duration in Table B105.1(2)
Section 903.3.1.1 of the California Fire Code 25 50 % of the value in Table B105.1(2) a Duration in Table Bl 05.1(2) at the reduced flow rate
Section 903.3.1.2 of the California Fire Code 25 50 % of the value in Table B105.1(2) b Duration in Table Bl05.1(2) at the reduced flow rate
For SI: 1 gallon per minute= 3.785 Lim. a. The reduced fire-flow shall be not less than 1,000 gallons per minute. b. The reduced fire-flow shall be not less than 1,500 gallons per minute. For SI: 1 gallon per minute= 3.785 Lim. a. The reduced fire-flow shall be not less than 1,000 gallons per minute. b. The reduced fire-flow shall be not less than 1,500 gallons per minute. For SI: 1 gallon per minute= 3.785 Lim. a. The reduced fire-flow shall be not less than 1,000 gallons per minute. b. The reduced fire-flow shall be not less than 1,500 gallons per minute.

(Ord. 7990-NS § 1, 2025)

Exceptions & meaning →

19.48.140 Validity.

Should any section, paragraph, sentence or word of this Chapter or of the Code or Standards be declared invalid, all other portions of this Chapter shall remain in effect. (Ord. 7990-NS § 1, 2025)

Exceptions & meaning →

Get a plain-English answer with a citation back to this text.

Ask AI about this code
▸Contents — Berkeley Municipal Code

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.