§ 13.04.030. Diameter – Residential areas.

Water mains in residential areas shall not be less than six inches in diameter.

(Ord. 179 § 1(2), 1971)

Exceptions & meaning →

§ 13.04.040. Diameter – Mercantile and manufacturing districts.

Water mains in mercantile and manufacturing districts shall not be less than eight inches in diameter.

(Ord. 179 § 1(3), 1971)

Exceptions & meaning →

§ 13.04.050. Feederline diameter.

No feeder line, or main, from the water source, or supply, in residential or commercial areas shall be less in diameter size than the main which it serves.

(Ord. 179 § 1(4), 1971)

Exceptions & meaning →

§ 13.04.060. Gridiron looping of water mains.

Water main, in residential or commercial areas, shall be looped into a gridiron system to avoid deadends. Eight-inch and larger lines are excepted.

(Ord. 179 § 1(5), 1971)