Earlier editions: 2026-09
Title 13 — Public Services›Chapter 13.04 — FIRE PROTECTION WATER SYSTEMS
Angels Camp Municipal Code Art. II Water Mains
Angels Camp Municipal Code · 2026-10 edition · updated 2026-10-05 · Angels Camp
Cite as: Angels Camp Municipal Code Article II · Text as of 2026-10-05
§ 13.04.030. Diameter – Residential areas.¶
Water mains in residential areas shall not be less than six inches in diameter.
(Ord. 179 § 1(2), 1971)
§ 13.04.040. Diameter – Mercantile and manufacturing districts.¶
Water mains in mercantile and manufacturing districts shall not be less than eight inches in diameter.
(Ord. 179 § 1(3), 1971)
§ 13.04.050. Feederline diameter.¶
No feeder line, or main, from the water source, or supply, in residential or commercial areas shall be less in diameter size than the main which it serves.
(Ord. 179 § 1(4), 1971)
§ 13.04.060. Gridiron looping of water mains.¶
Water main, in residential or commercial areas, shall be looped into a gridiron system to avoid deadends. Eight-inch and larger lines are excepted.
(Ord. 179 § 1(5), 1971)
Get a plain-English answer with a citation back to this text.
Ask AI about this code