5.1.1.2 Stock of Spare Sprinklers.¶
A supply of at least two sprinklers of each type utilized and a corresponding wrench for each type shall be maintained on the premises in an approved cabinet.
.350 Table B105.1(1) of Section B105 of Appendix B is hereby amended to read in full as follows:
Table B105.1(1). Required Fire-Flow For One- And Two-Family Dwellings, Group R-3 and R-4 Buildings and Townhouses.
| FIRE-FLOW CALCULATION AREA (SQUARE FT) | AUTOMATIC SPRINKLER SYSTEM (DESIGN STANDARD) | MINIMUM FIRE FLOW (GPM) | FLOW DURATION (HOURS) |
|---|---|---|---|
| 0 - 3,600 | No automatic sprinkler system | 1,500 | 1 |
| 3,601 and greater | No automatic sprinkler system | Value in Table B105.1(2) | Duration in Table B105.1(2) at the required fire-flow rate |
| 0 - 3,600 | Section 903.3.1.3 of the California Fire Code or Section 313.3 of the California Residential Code | 750 | 1/2 |
| 3,601 and greater | Section 903.3.1.3 of the California Fire Code or Section 313.3 of the California Residential Code | ½ value in Table B105.1(2) | 1 |
.360 Table B105.2 of Section B105 of Appendix B is hereby amended to read in full as follows:
Table B105.2 Required Fire-Flow For Buildings Other Than One- And Two-Family Dwellings, Group R-3 And R-4 Buildings And Townhouses.
| AUTOMATIC SPRINKLER SYSTEM (DESIGN STANDARD) | MINIMUM FIRE-FLOW (GPM) | FLOW DURATION (HOURS) |
|---|---|---|
| No automatic sprinkler system | Value in Table B105.1(2) | Duration in Table 105.1(2) |
| Section 903.3.1.1 of the California Fire Code | 50% of the value in Table B105.1(2) a | Duration in Table B105.1(2) at the reduced flow rate |
| Section 903.3.1.2 of the California Fire Code | 50% of the value in Table B105.1(2) a | Duration in Table B105.1(2) at the reduced flow rate |
a. The reduced fire-flow shall be not less than 1,500 gallons per minute.
(Ord. 6614 § 2 (part); September 23, 2025.)