Woodlake Municipal Code Ch. 13.08 Cross-Connections

Woodlake Municipal Code · 2026-10 edition · updated 2026-10-04 · Woodlake

Cite as: Woodlake Municipal Code Chapter 13.08 · Text as of 2026-10-04

13.08.010 - Definitions.

The definitions attached to the ordinance codified in this chapter and noted as "Appendix A" are made a part of this chapter as though they were repeated herein.

(Ord. 468 § 2 Art. 1, 1992)

Exceptions & meaning →

13.08.020 - Rules and regulations.

The following rules and regulations concerning cross-connections to the water system of the city are adopted, and all work in respect thereto shall be performed as herein required and not otherwise.

(Ord. 468 § 2 Art. 2-01, 1992)

Exceptions & meaning →

13.08.030 - Purpose.

The purpose of this chapter is:

A. To protect the public potable water supply of the city from the possibility of contamination or pollution by isolating within the user's internal distribution system or the user's private water system such contaminants or pollutants which could backflow into the public water system;

B. To promote the elimination or control of existing cross-connections, actual or potential, between the user's in-plant potable water system and nonpotable water system, plumbing fixtures and industrial piping systems; and

C. To provide for the maintenance of a continuing program of cross-connection control which will systematically and effectively prevent the contamination or pollution of the city's water system.

(Ord. 468 § 2 Art. 2-02, 1992)

Exceptions & meaning →

13.08.040 - Enforcement responsibility.

The city council shall be responsible for the protection of the water system from contamination or pollution due to the backflow of contaminants or pollutants through a water service connection. If, in the judgment of the council, an approved backflow prevention assembly is required for the safety of the water system, the council, or its designated agent, shall give notice in writing to the user to install such an approved backflow prevention assembly at such specific locations on his premises. The user shall immediately install such approved assemblies at the user's own expense. Failure, refusal or inability on the part of the user to install, have tested and maintain the assemblies shall constitute grounds for discontinuing water service to the premises until such requirements have been satisfactorily met.

(Ord. 468 § 2 Art. 2-03, 1992)

Exceptions & meaning →

13.08.050 - Short title.

This chapter shall be known as the "cross connection ordinance of the city of Woodlake."

(Ord. 468 § 2 Art. 2-04, 1992)

Exceptions & meaning →

13.08.060 - Protection at point of connection.

Protection of the public water system at the service connection shall include, but not be limited to the following:

A. Each public water service connection supplying water to premises having an auxiliary water supply shall be protected against backflow of water from the premises into the public water system by the proper installation of an approved method of backflow protection;

B. Each public water service connection supplying water to premises on which any substance is or may be handled in such a fashion as to permit introduction into the water system shall be protected against-backflow of the substance into the public water system. This shall include the handling of process waters and waters originating from the public water system which have been subjected to deterioration in bacteriological and/or chemical quality; and

C. Approved backflow protection measures shall be initiated on the service connection from the public water system to any premises that has a cross-connection.

(Ord. 468 § 2 Art. 3-01, 1992)

Exceptions & meaning →

13.08.070 - Protection on user premises.

Protection of potable water systems within the user premises shall include, but not be limited to, the following:

A. Plumbing Connections. Where the circumstances are such that there is danger to health from the backflow of sewage, as from sewers, toilets, hospital bedpans and the like, into a drinking water system, a dependable form of backflow protection shall be installed to prevent such backflow.

Devices suited to the purpose of avoiding backsiphonage from plumbing fixtures are roof tanks or separate pressure systems which are separately piped to supply such fixtures, recognized approved vacuum or siphon breakers and other backflow protective devices which have been proved by appropriate testing laboratories to be dependable for destroying the vacuum.

More specifically, plumbing connections shall comply with the provisions of the most recent edition of the Uniform Plumbing Code.

B. Separate Drinking Water Systems. Whenever the city determines that it is not reasonably possible to protect the water system against entry of water from a source or piping system on user premises, or equipment is proposed which cannot be approved as safe or resulting in a water supply which is potable for human use, an entirely separate drinking water system shall be installed.

C. Fire Systems.

  1. Water systems for fighting fires, derived from a supply and/or source that cannot be approved as safe or potable for human use shall be kept wholly separate from drinking water pipelines and equipment. In cases where the domestic water system is or may be used for fire fighting purposes, an approved form of backflow protection shall be installed to protect such individual drinking water lines as are not used for fire fighting purposes. In no instance shall the domestic water piping be utilized to carry nonpotable water for fire fighting purposes.

When disinfection of an auxiliary water supply is depended upon to render the water safe, the means of applying the disinfectant under this regulation shall be automatic with operation of the pump or pumps employed with the dangerous water in question. Adequate supplies of chlorine and its compounds must be kept on hand at all times. Chlorine dosing equipment shall be tested daily and kept in good operating condition.

The public water supply must be protected against backflow from such domestic fire systems as detailed in Sections 13.08.080 and 13.08.090; and

  1. An approved form of backflow protection shall be provided on the public water service connection supplying water to automatic fire extinguishing systems.

D. Process Waters. Potable water pipelines connected to equipment for industrial processes or operations shall be disconnected therefrom if practicable. Where disconnection is not practicable, a suitable form of backflow protection located beyond the last point from which drinking water may be taken shall be provided on the feed line to process piping or equipment. In the event the particular process liquid is especially corrosive or apt to prevent reliable action of the backflow prevention device, an approved air-gap separation shall be provided.

E. Sewage Treatment Plants and Pumping Stations. Sewage pumps shall not have priming connections directly connected to any drinking water system. No cross-connections shall exist between the drinking water system and any other piping, equipment, or tank in any sewage treatment or sewage pumping station.

F. Water Line Sizing. Inasmuch as many serious plumbing hazards are due to undersized piping, water supply piping which is too small, thereby causing vacuum conditions when fixtures are flushed or water is drawn from the system in other ways, shall be enlarged whenever possible.

(Ord. 468 § 2 Art. 3-02, 1992)

Exceptions & meaning →

13.08.080 - Protection of public water systems.

The specific type of approved backflow protection (air-gap separation, reduced pressure principle backflow prevention device, double check valve assembly or pressure type vacuum breaker) required shall depend on the degree of hazard involved. This shall include, but not be limited to, the following criteria.

A. An approved air-gap separation shall be used where there is a health hazard, system hazard, contamination hazard or a plumbing hazard which cannot be presently eliminated. The air-gap separation shall be located on the user's side of and as close to the service connection as is practicable. All water piping from the service connection to the air-gap separation shall be above grade and entirely visible. If these conditions cannot reasonably be met, the public water supply may be protected by proper installation of an approved reduced pressure principle backflow prevention device, providing this alternative is acceptable to the city.

B. An approved double check valve assembly shall be provided on the service connection to a premises on which there is an auxiliary water supply handled in a separate piping system with no known cross-connection.

C. An approved air-gap separation or an approved reduced pressure principle backflow prevention device shall be provided at the service connection to a premise on which there is an auxiliary water supply where cross-connections exist which cannot be presently eliminated.

D. An approved air-gap separation shall be provided at the service connection to any sewage treatment plant, sewage pumping station or stormwater pumping station. If these conditions cannot be reasonably met, the public water supply may be protected by the proper installation of an approved reduced pressure principle backflow prevention device, provided this alternative is acceptable to the city. The final decisions in these matters shall rest with the State Department of Health Services.

E. Low head sewage lift stations on residential and commercial premises may be protected as follows:

  1. Isolation of the pumping unit from the rest of the building, prohibition of water piping in the sewage pump room and installation of an approved double check valve assembly at the service connection; or

  2. Industrialization of the water line into the sewage pump room area (if there must be water service in the area) by providing an approved reduced pressure principle backflow prevention device on the water line supplying the area. All hose connections and/or valved outlets beyond the device that may be used for drinking water shall be identified as "DANGER-UNSAFE WATER" or "UNSAFE WATER-NOT FOR DRINKING."

F. An approved air-gap separation shall be provided at the service connection to any premises on which any materials dangerous to health or toxic substance in toxic concentration is or may be handled under pressure. If these conditions cannot reasonably be met, the public water supply may be protected by the proper installation of an approved reduced pressure principle backflow prevention device, provided this alternative is acceptable to the city.

G. An approved double check valve assembly shall be provided at the service connection to a premises on which a substance that would be objectionable, but not necessarily hazardous to health is or may be handled in such a manner as to permit entry into the water system.

H. The minimum of an approved double check valve assembly shall be provided at the service connection to an automatic fire extinguishing system. All systems shall be reviewed to determine when more stringent backflow protection is justified.

I. An approved backflow prevention device as designated by the city shall be provided at the service connection to any premises on which the city determines that a special hazard exists. This shall include, but not be limited to, such premises where cross-connections have been eliminated, but where the water system is of such size and the water use so extensive and diversified that a high potential exists for creating cross-connections.

J. Internal backflow protection may be accepted in lieu of master protection, provided this alternative is acceptable to the city.

K. The following is a list of premise uses which generally require backflow protection for the public water service connection. The required type of backflow prevention device is indicated. Backflow protection requirements for premises not appearing on this list shall be discussed with the city.

Premise Use Type of Device Required
1. Air conditioning plants RP
2. Animal clinics, animal grooming shops and animal boarding RP
3. Apartment or office complex with pond, lake or fountain RP
4. Automotive repair with steam cleaner, acid cleaning equipment or solvent facilities RP
5. Automobile detail shop RP
6. Automotive plants RP
7. Auxiliary water systems or sources (interconnected or not interconnected) D.C. or RP
8. Bakeries RP
9. Barber shops, beauty shops or salons RP
10. Bars, taverns or cocktail lounges RP
11. Battery manufacturing or rebuilding RP
12. Bottling plants - beverage and chemical RP
13. Boat manufacturing RP
14. Buildings with boilers or cooling towers RP
15. Buildings with landscape fountains or ponds RP
16. Buildings with storage tanks over two stories RP
17. Buildings with house booster pumps and/or approved water storage tank D.C.
18. Building with sewage pumps RP
19. Canneries or packing houses RP
20. Carbonic gas recharging facilities RP
21. Car wash (with or without water reclamation system) RP
22. Chemical plants RP
23. Chemically treated (nonpotable) water system RP
24. Chemically treated (potable) water system D.C .
25. Churches with baptismal pools RP
26. Home sprinkler systems VB
27. Cleaning and dye works RP
28. Commercial laundries A.G. or RP
29. Convalescent homes and clinics D.C. or RP
30. Convenience markets RP
31. Crematories RP
32. Dairies and cold storage plants D.C. or RP
33. Dental offices RP
34. Dialysis clinics RP
35. Experimental lab facilities RP
36. Fabricating plants (metal, fiberglass, plastic, foam) RP
37. Film processing laboratories RP
38. Fire extinguisher recharging facilities RP
39. Fire protection system with auxiliary supply RP
40. Fire protection system with pump and/or storage tank D.C.
41. Food processing facilities using nontoxic materials D.C.
42. Food processing facilities using toxic materials RP
43. Foundries RP
44. Ice manufacturing plants RP
45. Ice skating rings RP
46. Health spas RP
47. Hospitals RP
48. Laboratories RP
49. Landscaping of elevated areas or with drip irrigation system RP
50. Laundromats RP
51. Machine shop RP
52. Manufacturing, processing and fabrication facilities using nontoxic materials D.C.
53. Manufacturing processing and fabrication facilities using toxic materials RP
54. Medical offices RP
55. Metal manufacturing D.C. or RP
56. Metal stripping plants RP
57. Mobile home parks D.C.
58. Mobile equipment - pest control, drain cleaning, steam cleaning, rug and carpet cleaning RP
59. Mortuaries and morgues RP
60. Office or shopping center with uncommitted lease space RP
61. Paint manufacturing RP
62. Painting shops using water in any process RP
63. Pest control businesses RP
64. Pet shops RP
65. Photography studios with processing equipment RP
66. Plating plants RP
67. Radiator works - repair or backflushing RP
68. Reduction plants and rendering plants RP
69. Rest homes - nonambulatory or over one story RP
70. Rest homes - ambulatory only D.C.
71. Restaurants or buildings with commercial kitchen (commercial includes any of the following:
booster heater, 180° hot water or commercial dishwasher) RP
72. Restricted, classified or other closed facilities RP
73. Sand and gravel, asphalt batch and ready-mix cement plants RP
74. Sanitary dump for recreation vehicles or septic service tankers RP
75. Schools and colleges RP
76. Service stations with radiator repair or backflushing RP
77. Sewerage and storm drainage facilities RP or A.G.
78. Solar heating systems (other than domestic hot water) D.C. or RP
79. Super markets with meat cutting and/or cooling towers RP
80. Theaters with food and/or drinks D.C. or RP
81. Warehouse with uncommitted space RP
82. Where a cross-connection is maintained RP
83. Where the use of a substance, process water, or water supplied by the city is such as to subject the water to deterioration in sanitary quality RP
84. Where the water use is in conjunction with any pollutant (non-health hazard) D.C.

NOTE:

Whenever a water service includes a combination of two or more usages, the usage with the most restrictive device shall control. An air gap is the most restrictive and a vacuum breaker is the least restrictive device.

DEVICE DEFINITIONS:

AG - Approved air gap—all piping visible between customer service valve and receiving tank with no taps or tees.
D.C. - Approved double check valve assembly.
RP - Approved reduced pressure principle assembly.
VB - Approved pressure type vacuum breaker assembly.

(Ord. 468 § 2 Art. 4-01, 1992)

Exceptions & meaning →

13.08.090 - Protection of internal (on premises) domestic water supplies.

The specific type of approved backflow prevention device (air-gap separation, approved reduced pressure principle backflow preventer, approved double check valve assembly, approved pressure type vacuum breaker, and atmospheric type vacuum breaker) required shall depend on the degree of hazard involved. These requirements shall include, but not be limited to, those requirements established by other administrative authorities having jurisdiction in the area. Attention is called to the California Administrative Code, Title 17, Regulations Relating to Cross-Connections, Article 1 (Section 7583) and Article 4, Article 8 Administrative Procedures; the Uniform Plumbing Code requirements; and special requirements adopted by the city.

(Ord. 468 § 2 Art. 4-02, 1992)

Exceptions & meaning →

13.08.100 - Backflow prevention devices—Types to be used.

Potential types of backflow prevention devices which can be submitted for approval, as applicable, include the following types:

A. Air-gap separation;

B. Reduced pressure principle backflow prevention device;

C. Double check valve assembly;

D. Pressure type vacuum breaker; and

E. Atmospheric type vacuum breaker (on premises only).

(Ord. 468 § 2 Art. 5-01, 1992)

Exceptions & meaning →

13.08.110 - Backflow prevention devices—Approval of device.

Only those devices that have met the specifications and received the approval of an approved testing laboratory and have been accepted by both the city and the State Department of Health Services shall be approved for use in protecting public water supplies. Internal (on premises) protection may be afforded by use of an atmospheric type vacuum breaker provided this type of device has met the specifications and received the approval of an approved testing laboratory and has been accepted by the city. City approval shall also be required if an atmospheric type vacuum breaker is to be accepted in lieu of master protection.

(Ord. 468 § 2 Art. 5-02, 1992)

Exceptions & meaning →

13.08.120 - Backflow prevention devices—Installation requirements.

Public water service connection protection installations shall be as follows and shall be at the expense of the water user:

A. Air-Gap Separation (A.G.). The air-gap separation shall be located on the user's side of and as close to the service connection as is practicable. All piping from the service connection to the receiving tank shall be above grade and be entirely visible. No water use shall be provided from any point between the service connection and the air-gap separation. The water inlet piping shall terminate a distance of at least two pipe diameters of the supply inlet, but in no case less than one inch above the overflow rim of the receiving tank.

B. Reduced Pressure Principle Backflow Prevention Device (R.P.). The approved reduced pressure principle backflow prevention device shall be installed on the user's side of and as close to the service connection as is practicable. The device shall be installed not more than three feet nor less than twelve (12) inches above the surrounding grade and shall be readily accessible for maintenance and testing. Water supplied from any point between the service connection and the R.P. shall be protected in a manner approved by the city.

C. Double Check Valve Assembly (D.C.). The approved double check valve assembly shall be located on the user's side of and as close to the service connection as is practicable. The double check valve assembly shall be installed not more than three feet nor less than twelve (12) inches above surrounding grade, and shall be readily accessible for maintenance and testing. Water supplied from any point between the service connection and the D.C. shall be protected in a manner approved by the city.

D. Pressure Type Vacuum Breaker (P.V.B.). The approved pressure type vacuum breaker shall be located on the user's side of and as close to the service connection as is practicable. The P.V.B. shall be installed such that the critical level (C-L) is a minimum of twelve (12) inches above the highest point reached by any water downstream from the device, not less than twelve (12) inches, nor more than sixty (60) inches, above the surrounding floor or grade and shall be readily accessible for maintenance and testing. The P.V.B. shall not be exposed to any back-pressure. Water supplied from any point between the service connection and the P.V.B. must be protected in a manner approved by the city.

E. Atmospheric (Nonpressure) Type Vacuum Breaker (A.V.B.). The atmospheric (non-pressure) type vacuum breaker shall be located such that the critical level is at least six (6) inches above the highest point any water reaches downstream from the A.V.B. Fixtures with integral vacuum breakers manufactured and approved as a unit may be installed in accordance with their approval requirements. At no time shall the vacuum breaker be subjected to back-pressure.

(Ord. 468 § 2 Art. 5-03, 1992)

Exceptions & meaning →

13.08.130 - Backflow prevention devices—Testing and maintenance.

A. It shall be the duty of the water user on any premises on which reduced pressure principle backflow prevention devices, double check valve assemblies and/or pressure type vacuum breakers are installed to have competent inspections made of these devices to verify effective operation on an annual basis. The City shall perform the tests and charge a fee to the water user in accordance with a resolution adopted from time-to-time by the city council.

B. All testing of devices and completion of backflow prevention device test and maintenance reports shall be restricted to those persons that have been certified by the Department of Health Services and are in possession of a current valid backflow prevention device tester identification card.

C. The device shall be tested immediately upon being put into operation and at least once each year thereafter should the device continue in service. A backflow prevention device test and maintenance report must be filed for each test performance. Additional and/or more frequent testing shall be required because of, but not limited to, the following conditions:

  1. Relocation. If a device is relocated, a test shall be made prior to putting the device back into service.

  2. Repiping. If the supply line is changed, the device shall be tested prior to being put back into service.

  3. Repair or Overhaul. If repaired, the device shall be tested prior to being put back into service. The device may be required to be tested again in three months. Cleaning is considered to represent repair.

  4. Devices or assemblies that are not commensurate with the degree of hazard involved shall be tested at least every three months. Devices or assemblies in this category shall be replaced with approved devices either upon successive inspections indicating repeated mechanical failure (excluding cleaning) or as directed by the city.

  5. All backflow prevention devices, installation, tests, repairs, overhaul and/or replacement shall be at the expense of the water user.

(Ord. 468 § 2 Art. 5-04, 1992)

Exceptions & meaning →

13.08.140 - Backflow prevention device removal.

Approval must be obtained from the city before a backflow prevention device is removed, relocated or replaced.

A. Removal. The use of a device may be discontinued and the device removed from service upon presentation of sufficient evidence to the city to verify that a hazard no longer exists or is likely to be created in the future.

B. Relocation. A device may be relocated following confirmation by the city that the relocation will continue to provide the required protection and satisfy installation requirements. A retest will be required.

C. Repair. A device may be removed for repair, provided the water use is either discontinued until repair is completed and the device is returned to service, or the water use is equipped with other backflow protection approved by the city. A retest will be required.

D. Replacement. A device may be removed and replaced provided the water use is discontinued until the replacement device is installed. All replacement devices must be approved and must be commensurate with the degree of hazard involved.

Note: Nonapproved devices (assemblies) and/or approved devices (assemblies) that are not commensurate with the degree of hazard involved shall be replaced immediately.

(Ord. 468 § 2 Art. 5-05, 1992)

Exceptions & meaning →

13.08.150 - Records.

A. Records of such tests, repairs, overhaul, relocation and/or replacement shall be filed with the city. The city shall provide forms for this purpose. A copy of this report shall be submitted to the water user as follows:

  1. Upon notification of a newly installed device (new or replacement);

  2. Annually: to comply with the requirements set forth in Chapter 5, Subchapter 1, Group 4, of the California Administrative Code;

  3. Three months following repair or overhaul (if deemed necessary).

B. The report shall be accompanied by correspondence directing the water user to have the necessary repairs made if necessary, and to return a card to the city within a thirty (30) day period. The time period shall be identified by a return date typed on the report form. In the event that there is need to exceed the return date, information explaining such delay shall be filed with the city in writing prior to expiration of said return date.

If information is not received, a second notice will be sent. Noncompliance with the second notice will be followed by a city council hearing to discuss discontinuance of water service.

(Ord. 468 § 2 Art. 5-06, 1992)

Exceptions & meaning →

13.08.160 - Marking safe and unsafe water lines.

The water user shall be responsible for marking safe and unsafe water lines. When the premises contains dual or multiple water systems and piping, the exposed portions of these pipelines shall be painted, banded and/or marked at sufficient intervals to distinguish clearly which lines contain water that is safe for drinking purposes (potable/domestic) and which lines contain water which is not safe (nonpotable/industrial). All outlets from potentially contaminated water systems shall be posted as being contaminated and unsafe for drinking purposes. All outlets intended for drinking purposes shall be plainly marked to indicate that fact.

(Ord. 468 § 2 Art. 6-01, 1992)

Exceptions & meaning →

13.08.170 - Methods of line identification.

A. Identification of water line shall be as follows:

  1. Complete color painting of all visible parts of the pipe; or

  2. A color band a minimum of ten inches in width, located at least every twenty-five (25) feet of line length and on each side where a pipe passes through a wall. The color shall be Federal Safety Green (933). This color and requirement has been selected to be in concurrence with the recommendations of the American Standards Association and not to be in conflict with Title 17 of the California Administrative Code or Title 8, Division of Industrial Safety General Industry Safety Orders which cite line and outlet identification standards;

B. 1. The name of the type of water being transported shall be lettered or stenciled on the piping adjacent to each band or at least every twenty-five (25) feet at a minimum of two locations on the exposed piping and on each side where a pipe passes through a wall if all visible parts of the pipe are painted. The letter size and color of the letters and the letter background shall be such as to be immediately legible (see subsection D of this section for names); or

  1. A sub-color band two inches in width, identifying the type of water is applicable when applied at a visible edge of the ten-inch band described in subsection A(2) of this section or every twenty-five (25) feet on each side where a pipe passes through a wall as described in subsection A(2) of this section. (See subsection D of this section for colors);

C. The names and sub-banding legibility shall be maintained;

D. The names and the four sub-band codes shall be as follows:

2″ BAND LABEL
Domestic Water (Raw) lt. green
Domestic Water (Softened) lt. blue
Industrial Water
(Nonpotable; treated or
untreated) lt. orange
On-site well water yellow

E. A placard identifying the color code/labeling designation shall be posted at sufficient locations to prevent confusion.

(Ord. 468 § 2 Art. 6-02, 1992)

Exceptions & meaning →

13.08.180 - Method of outlet identification.

Identification shall be as follows:

A. Tags or labels of metal or other suitable materials with applicable wording:

"SAFE WATER"

or

"DANGER - UNSAFE WATER"

shall be securely fastened at or to each respective outlet;

B. The tag or label shall be affixed in such a manner as to be immediately identifiable to the outlet user;

C. The tag or label letter size, color and background shall be such as to be easily legible; and

D. The tag or label legibility shall be maintained.

(Ord. 468 § 2 Art. 6-03, 1992)

Exceptions & meaning →

13.08.190 - Designated representative.

At each premises where it is necessary, in the opinion of the city, a designated representative shall be designated by and at the expense of the water user. This designated representative shall be responsible for the monitoring of the backflow prevention devices and for avoidance of cross-connections. In the event of contamination or pollution of the drinking water system due to a cross-connection on the premises, the city shall be promptly advised by the designated representative so that appropriate measures may be taken to overcome the contamination. The city shall be kept informed of the designated representative's identity.

(Ord. 468 § 2 Art. 7-01, 1992)

Exceptions & meaning →

13.08.200 - Initial survey.

The initial survey shall consist of a thorough investigation of all water uses, planned or existing, within a user's premises to identify existing hazards and/or code infractions. The initial survey shall be performed for at least the following circumstances.

A. New service investigation request as received from water user;

B. Investigation of existing services upon request or upon notification that a hazard may exist; and

C. Investigation of remaining user premises selected as to the suspected degree of hazard.

(Ord. 468 § 2 Art. 8-01, 1992)

Exceptions & meaning →

13.08.210 - Consumer notification.

Customer notification of action requests shall be performed as follows:

A. Prepare and transmit a letter to the user confirming survey findings and listing corrective action to be taken if required. This may be accomplished by furnishing a copy of the on site survey report;

B. Follow up on delinquent requests to correct plumbing violations as follows:

  1. A second notice shall be sent to the user if evidence that corrective action is being taken, has not been filed with the city office within ten working days following the date of the original user notification.

  2. If the user fails to respond to the second notice to correct violations, the city shall pursue the following action:

a. The user and/or his representative, which may include counsel, shall be notified by certified mail to appear for an office hearing to show cause for noncompliance. The request shall advise specific date, time and place for the office hearing. This hearing shall be attended by the public works director, the designated representative and the engineer.

b. The above may be preceded by personal contact between the public works director or engineer and the user. This action may be taken at the discretion of the public works director or at the direction of the city council. A single personal contact shall be considered as being appropriate.

  1. The city may discontinue water service to the premises if:

a. The office hearing does not provide evidence that corrective action is being taken, or

b. The user does not appear for the office hearing, or

c. It is determined at the time of the survey that water shut-off is in the best interest for the protection of the city's potable water supply.

(Ord. 468 § 2 Art. 8-02, 1992)

Exceptions & meaning →

13.08.220 - Reinspection.

A. A reinspection will be made at the request of the user to verify corrective action.

B. A reinspection may be made prior to sending a second notice.

C. A reinspection may be made prior to having an office hearing.

(Ord. 468 § 2 Art. 8-03, 1992)

Exceptions & meaning →

13.08.230 - Printed information.

The following printed information shall be available to users for the city:

A. A list of backflow prevention devices (assemblies) approved by recommended testing agencies;

B. Illustrations of requirements for properly installing a backflow prevention device (assembly); and

C. Information sheets regarding specific backflow prevention requirements.

(Ord. 468 § 2 Art. 8-04, 1992)

Exceptions & meaning →

13.08.240 - Backflow prevention device testing program.

The following program is adopted to insure proper operation of installed backflow prevention devices.

A. Inspection of all newly installed backflow prevention devices shall be required to verify proper location. A test to verify effective operation and obtain other pertinent information (manufacturer, size, type, model, serial number, ownership, etc.) shall be required. The user may be requested to file a maintenance report verifying satisfactory operation of any newly installed backflow prevention device;

B. Maintenance of a record of backflow prevention devices in use;

C. Maintenance of a testing program for all backflow prevention devices in use including the following:

  1. Notification to users of responsibility in testing and maintaining backflow prevention devices,

  2. Notifying users when tests are required. Required tests as a minimum shall be as follows:

a. At least annually as required by the California Administrative Code, or

b. In three months following repair or overhaul (this requirement may be omitted at the discretion of the city), or

c. Every three months for those devices (assemblies) that are not commensurate with the degree of hazard involved (this shall include both approved and non-approved devices),

  1. Supply necessary backflow prevention device test and maintenance report forms,

  2. Provide at the user's expense, the required testing services necessary for certification of performance of backflow prevention devices,

  3. Review completed test and maintenance report forms,

  4. Follow up on delinquent test and/or maintenance report forms as follows:

a. A second notice shall be sent to the user if the test and maintenance report is not received by the scheduled return date (this date shall coincide with the last working day of the testing month).

b. If a test and maintenance report indicating proper operation has not been returned or evidence that corrective action is being taken has not been filed with the city within ten working days following the date of the second notice, the matter shall be referred to the public works director with a recommendation to pursue the following course of action:

i. The user and/or his representative, which may include counsel, shall be notified by certified mail to appear for an office hearing to show cause for noncompliance. The request shall advise specific date, time and place for the office hearing. This hearing shall be attended by the public works director and/or the engineer.

ii. The city may discontinue water service to the premises if:

(A) The office hearing does not provide evidence that a satisfactory test has been performed and the report is forthcoming within five working days, or

(B) The user does not appear for the office hearing;

  1. Notify the user to repair and test a faulty backflow prevention device. (Note: Repair should be made immediately and satisfactory operation confirmed by testing before the device is returned to service. The thirty (30) day test period is deemed to be adequate.)

a. A second notice shall be sent to the user if a test and maintenance report indicating proper operation has not been returned or evidence that corrective action is being taken has not been filed with the city within ten working days.

b. If a test and maintenance report indicating proper operation is not returned or evidence that corrective action is being taken has not been filed with the city within ten working days following the date of the second notice, the matter shall be referred to the public works director with a recommendation to pursue the following action:

i. The user and/or his representative, which may include counsel, shall be notified by certified mail to appear for an office hearing to show cause for noncompliance. The request shall advise specific date, time and place for the hearing. This hearing shall be attended by the public works director and/or engineer.

ii. The city may discontinue water service to the premises if:

(A) The office hearing does not provide evidence that satisfactory repair has been performed and a report is forthcoming within five working days, or

(B) The user does not appear for the office hearing, or

(C) Continued operation without repair is not in the best interest for protecting the city's potable water supply,

  1. Notify the user to replace a faulty backflow prevention device. (Note: Replacement shall be made following three successive tests indicating repeated mechanical failure.

a. A second notice shall be sent to the user if a test and maintenance report indicating proper operation of a replacement device is not returned or evidence that corrective action is being taken has not been filed with the city in writing within ten working days following the date of the original notification.

b. If a test and maintenance report indicating proper operation of a replacement device is not returned or evidence that corrective action is being taken has not been filed with the city within twenty (20) working days following the date of the second city notice, the matter shall be referred to the public works director with a recommendation to pursue the following action:

i. The user and/or his representative, which may include counsel, shall be notified by certified mail to appear for an office hearing to show cause for noncompliance. The request shall advise specific date, time and place for the office hearing. This hearing shall be attended by the public works director and/or engineer.

Either of the above may be preceded by personal contact between the public works director and the user. This action may be taken at the discretion of the public works director or at the direction of the city council. A single personal contact shall be considered as being appropriate.

ii. The City may discontinue water service to the premises if:

(A) The office hearing does not provide evidence that satisfactory replacement has been performed and the report is forthcoming within five working days, or

(B) The user does not appear for the office hearing, or

(C) Continued operation without replacement is not in the best interest for protecting the city's potable water supply,

  1. Maintain a history of each device including test results, repairs, and replacements,

  2. Periodically review records to note particular devices that exhibit a poor history of effective operation.

(Ord. 468 § 2 Art. 8-05, 1992)

Exceptions & meaning →

13.08.250 - Water shut-off—Cause and procedure.

A. General. From time-to-time the public works director will encounter water uses that represent a clear and immediate hazard to the potable water supply. In the event that these hazards cannot be immediately abated, either because of mechanical problems, inconvenience and/or refusal on the part of the user, the public works director shall institute the procedure for discontinuing the city's water supply.

B. Basis for Termination. Conditions or water uses that create a basis for water service termination shall include, but are not limited to, the following items:

  1. Refusal to test backflow prevention device; or

  2. Refusal to repair faulty backflow prevention device; or

  3. Refusal to replace faulty backflow prevention device; or

  4. Refusal to satisfy office hearing requirements; or

  5. Direct or indirect connection between a potable water system or sewer line; or

  6. Unprotected direct or indirect connection between a potable water system and a system or equipment containing chemicals or sewage; or

  7. Unprotected direct or indirect connection between potable and auxiliary water system; or

  8. Unprotected direct connection to non- potable pressure or nonpressure system; or

  9. Refusal to correct violations.

C. Water Service Termination Procedures.

  1. For conditions listed in subsections B(1), (2), (3), (4) and (9) of this section, service termination procedures shall be in accordance with the provisions of the city's adopted water ordinance.

  2. For conditions listed in subsections B(5), (6), (7) and (8) of this section, the following procedure shall apply:

a. Make reasonable effort to advise user of intent to terminate water service;

b. Advise State Department of Health Services of pending water termination; and

c. Terminate water supply and lock service valve. The water supply will remain inactive until correction of violations has been approved by the city.

(Ord. 468 § 2 Art. 9, 1992)

Exceptions & meaning →

13.08.260 - Testing charges.

Cross-connection testing service charges for tests performed by the city shall be established from time-to-time by resolution of the city council.

(Ord. 468 § 2 Art. 10-01, 1992)

Exceptions & meaning →